13-96R (2)-023
SPLIT SYSTEM NOTES: / 9 \ 1. OUTSIDE DESIGN CONDITIONS: 91TDB - 78TDB (MIAMI, FL) 2. PROVIDE AHU WITH VENSTAR T2950 PROGRAMMABLE THERMOSTAT W/ REMOTE TEMPERATURE SENSING CAPABILITY. (SEE ALSO MECHANICAL NOTES.) 3. PROVIDE CONDENSING UNITS W/ FACTORY PRE - COATED COILS. 4. SIZE AND RUN REFRIGERANT PIPING AS MANUFACTURER'S LATEST PUBLISHED RECOMMENDATIONS. 5. PROVIDE PROPER VII�RATION ISOLATORS AS PER ISOLATION MANUFACTURER S RECOMMENDATIONS. 6. INSULATE REFRIGERANT SUCTION LINE WITH 3/4" FIRE RETARDANT ARMAFLEX. 8. INSTALL CHEMICAL DRYER AND STRAINER IN REFRIGERANT LIQUID LINES. 9. PROVIDE BUILT -IN DISCONNECT WITH ALL AIR HANDLING UNITS. 10. PROVIDE HURRICANE TIE -DOWN KIT FOR CONDENSING UNITS, 11. PROVIDE AUXILIARY CONDENSATE FLOAT SWITCH. 12. PROVIDE FILTER RACK W/ 2" MERV 8 FILTERS. 13. AHU - VERTICAL CONFIGURATION. 14. CONDENSING UNITS TO BE PROVIDED WITH TIME DELAY AND PHASE LOSS PROTECTION 15. PROVIDE 1 YEAR PARTS AND LABOR WARRANTY, 5 YEAR COMPRESSOR WARRANTY. 16. PROVIDE VFD ON FAN FOR VAV OPERATION. 17. PROVIDE RAWAL DEVICE FOR VAV OPERATION. 18. PROVIDE ULTRASMART CONTOLLER FOR VAV OPERATION. 1 Z� A10 1( 71, "JA I VAV BOX UNIT SCHEDULED SPLIT SYSTEM SCHEDULE PRIMARY AIR DATA UNIT NUMBER AHU -1 AHU -2 MANUF. & MODEL( *) TYPE MANUFACTURER YORK YORK MIN. Ps( ") KW MODEL NUMBER AVL- 085 -ISDO AHE2483XH21 WEIGHT(LB) W/ HEAT LxHxW( ") W/O HEAT TOTAL C.F.M. 8000 800 WARREN ST- 04L(EH) SGL. DUCT 0 A C.F.M. 900 200 * 1.0 ENT. AIR TEMP 'F 78/67 80/67 32 13X19X10 SENSIBLE COOLING CAP. MBH 186.8 16.1 WARREN ST- 04L(EH) SGL. DUCT TOTAL COOLING CAP. MBH 301.9 23.4 * 1.0 EXT. STATIC PRESS, IN. H2O 3.44 0.5 32 13X19X10 BLOWER MOTOR H.P. 10 173 WARREN ST- 04L(EH) SGL. DUCT UNIT WEIGHT LBS. 1815 120 * 1.0 MATCHING CONDENSING UNIT CU -1 CU -2 32 13X19X10 ELECTRIC HEATER kW OV - 7 BTUH - 23,891 STAGE - 1 1 208/3/60 VOLTAGE 208 -3 -60 208 -1 -60 25 208 -3 -60 MCA (Amps.) - 25.0 8 350 MOP (Amps.) - 30.0 1 208/3/60 19X25X10 35 19X19X10 28 - UNIT NUMBER CU -1 CU -2 6 250 MANUFACTURER YORK YORK 1 208/3/60 MODEL NUMBER YC300C YCJD24 26 1400 NOMINAL TONS 25 2 10 600 No OF COMPRESSORS 2 1 1 208/3/60 R.L.A. EACH L.R.A. EACH 48.1 245 21 X19X10 32 44.8 No. CONDENSER FANS 4 2 8 350 F.L.A. EACH 3.0 - 1 208/3/60 VOLTAGE 208 -3 -60 208 -1 -60 26 230 MCA 120.3 12.4 4 100 MAX. BREAKER SIZE 150 20 1 208/3/60 UNIT WEIGHT Lbs 945 129 25 125 SYSTEM E.E.R. S.E.E.R. 10.2/- -/14.5 6 250 LIQUID LINE IN 7/8 3/8 1 208/3/60 SUCTION LINE (IN) 1 5/8 3/4 26 18.6 AREA SERVED ISEE DRAWING SEE DRAWING SPLIT SYSTEM NOTES: / 9 \ 1. OUTSIDE DESIGN CONDITIONS: 91TDB - 78TDB (MIAMI, FL) 2. PROVIDE AHU WITH VENSTAR T2950 PROGRAMMABLE THERMOSTAT W/ REMOTE TEMPERATURE SENSING CAPABILITY. (SEE ALSO MECHANICAL NOTES.) 3. PROVIDE CONDENSING UNITS W/ FACTORY PRE - COATED COILS. 4. SIZE AND RUN REFRIGERANT PIPING AS MANUFACTURER'S LATEST PUBLISHED RECOMMENDATIONS. 5. PROVIDE PROPER VII�RATION ISOLATORS AS PER ISOLATION MANUFACTURER S RECOMMENDATIONS. 6. INSULATE REFRIGERANT SUCTION LINE WITH 3/4" FIRE RETARDANT ARMAFLEX. 8. INSTALL CHEMICAL DRYER AND STRAINER IN REFRIGERANT LIQUID LINES. 9. PROVIDE BUILT -IN DISCONNECT WITH ALL AIR HANDLING UNITS. 10. PROVIDE HURRICANE TIE -DOWN KIT FOR CONDENSING UNITS, 11. PROVIDE AUXILIARY CONDENSATE FLOAT SWITCH. 12. PROVIDE FILTER RACK W/ 2" MERV 8 FILTERS. 13. AHU - VERTICAL CONFIGURATION. 14. CONDENSING UNITS TO BE PROVIDED WITH TIME DELAY AND PHASE LOSS PROTECTION 15. PROVIDE 1 YEAR PARTS AND LABOR WARRANTY, 5 YEAR COMPRESSOR WARRANTY. 16. PROVIDE VFD ON FAN FOR VAV OPERATION. 17. PROVIDE RAWAL DEVICE FOR VAV OPERATION. 18. PROVIDE ULTRASMART CONTOLLER FOR VAV OPERATION. 1 Z� A10 1( 71, "JA I VAV BOX UNIT SCHEDULED SELECTM DATA PRIMARY AIR DATA HEATER DATA GEN. DATA UNIT TAG MANUF. & MODEL( *) TYPE INLET DIA. MIN. CFM MAX. CFM MIN. Ps( ") KW STEPS VOLTAGE LxHxW( ") W/ HEAT WEIGHT(LB) W/ HEAT LxHxW( ") W/O HEAT WEICHT(LB) W10 HEAT NOTES VAV -1 -1 WARREN ST- 04L(EH) SGL. DUCT 4 100 300 * 1.0 1 208/3/60 13X25X10 32 13X19X10 25 RLA VAV -1 -2 WARREN ST- 04L(EH) SGL. DUCT 4 100 300 * 1.0 1 208/3/60 13X25X10 32 13X19X10 25 33.6 VAV -1 -3 WARREN ST- 04L(EH) SGL. DUCT 4 100 300 * 1.0 1 208/3/60 13X25X10 32 13X19X10 25 YORK DIEX036 VAV -1 -4 WARREN ST- 04L(EH) SGL. DUCT 4 100 300 * 1.0 1 208/3/60 13X25X10 32 13X19X10 25 208 -3 -60 VAV -1 -5 WARREN ST- 08L(EH) SGL. DUCT 8 350 900 * 4.0 1 208/3/60 19X25X10 35 19X19X10 28 - VAV -1 -6 WARREN ST- 06L(EH) SGL. DUCT 6 250 700 * 3.0 1 208/3/60 15X25X10 33 15X19X10 26 1400 VAV-1-7 WARREN ST- 10L(EH) SGL. DUCT 10 600 1300 * 5.0 1 208/3/60 21 X25X10 40 21 X19X10 32 44.8 VAV -1 -8 WARREN ST- 08L(EH) SGL. DUCT 8 350 900 * 3.0 1 208/3/60 19X25X10 33 19X19X10 26 230 VAV -1 -9 WARREN ST- 04L(EH) SGL. DUCT 4 100 300 * 1.0 1 208/3/60 13X25X10 32 13X25X10 25 125 VAV -1 -10 WARREN ST- 06L(EH) SGL. DUCT 6 250 700 * 3.0 1 208/3/60 15X25X10 33 15X19X10 26 18.6 VAV -1-'11 WARREN ST- 06L(EH) SGL, DUCT 6 250 700 * 3.0 1 208/3/60 15X25X10 33 15X19X10 26 15 VAV -1 -12 WARREN ST- 06L(EH) SGL, DUCT 6 250 700 * 3.0 1 208/3/60 15X25X10 33 15X19X10 26 8. PROVIDE RTU WITH VENTSTAR T2950 PROGRAMMABLE 365 -DAY VAV -1 -13 WARREN ST- 06L(EH) SGL. DUCT 6 250 700 * 3.0 1 208/3/60 15X25X10 33 15X19X10 26 ISOLATORS. VAV -1 -14 WARREN ST- 10L(EH) SGL. DUCT 10 600 1300 * 5.0 1 208/3/60 21 X25X10 40 21 X19X10 32 6. VAV -1 -15 WARREN ST- 12M(EH) SGL. DUCT 12 1000 2000 * 6.5 1 208/3/60 21X15X20 45 15X15X20 36 WARRANTY, 5 YEAR COMPRESSOR 125 OFFICE OFFICE SPACE 187 3 WARRANTY. 1 0.06 15 11.22 26.22 1 1 1 26.22 520 0.05 126 STAFF LOUNGE LOUNGES ROOM 148 6 7.5 0.18 45 26.64 56.64 1 56.64 600 0.09 127 DOCTOR OFFICE OFFICE SPACE 148 1 25 - 25 - 25 1 25 600 0.04 401 ELEVATOR LOBBY MAIN ENTRY LOBBY 243 3 5 0.06 15 14.58 29.58 1 29.58 100 0.29 3 3 0.9 73.38 0.8 91.73 200 RTU -1 409 CORRIDOR CORRIDORS 112 - - 0.06 - 6.72 6.72 1 6.72 50 0.13 416 CORRIDOR CORRIDORS ( *) BOX MODEL IS "TSS" FOR COOLING ONLY AND "TSS -EH" FOR COOLING WITH ELECTRIC HEATER STANDARD FEATURES VAV -X -XX 1. ARI 880 CERTIFIED AND LABELED, ELECTRIC HEAT STANDARD FEATURES LEVEL) I� 1. cETL LISTED AS AN ASSEMBLY FOR SAFETY COMPLIANCE. 2. 22 GAUGE GALVANIZED STEEL CASING AND VALVE. 3. 3/4" THICK FIBERGLASS INSULATION OR DOUBLE WALL CONSTRUCTION WITH 22 GAUGE LINER. 2. AUTOMATIC RESET PRIMARY AND BACK -UP SECONDARY THERMAL LIMITS. 3. AIRFLO SWITCH. 4. cETL LISTED FOR SAFETY COMPLIANCE WITH UL 1996. - 4. SINGLE POINT POWER CONNECTION AND FUSING PER NEC. 5. ELECTRICAL DEVICES INSTALLED WITHIN A NEMA 1 ENCLOSURE. 6. FLOWSTAR MULTI -AXIS, CENTER AVERAGING AIRFLOW SENSOR. 5. DOOR INTERLOCKING DISCONNECT SWITCH AND MAGNETIC CONTACTORS. 7. SELECTION IS BASED ON WARREN. UALS ARE ACCEPTABLE. 6. HINGED ELECTRICAL ENCLOSURE DOOR. 8. MANUFACTURER SHALL PROVIDE ETE WITH. 24 VOLT TRANSFORMER FOR CONTROLS. 9. PROVIDE UNOBSTRUCTED CLEARANCE IN FRONT OF ELECTRICAL COMPONENTS AS REQUIRED BY THE NATIONAL ELECTRIC CODE. OUTSIDE AIR CALCULATIONS MULTIPLE -ZONE RECIRCULATING SYSTEMS (BASED ON ASHRAE STANDARD 62.1 -2004) 10 OCCUPANCY CATEGORY ROOFTOP SCHEDULE Pz (p) Rp (CFM /p)(CFM MARK MODEL CFM HEATER FAN COMPRESSOR COND. FAN TOTAL MAX ELECTRICAL CAPACITY EER WT SERVICE Fresh Air Intake (CFM) NUMBER VOLTS -PH -HZ MAIN ENTRY LOBBY LBS 5 TOTAL ❑A KW STEP ESP HP I FLA N❑, TONS RLA NO. 1 MCA FUSE TMBH SMBH AHU -2 102 WAITING RECEPTION AREA 560 17 5 0.06 85 33.6 1180 1 (EACH) SW (EACH) 76 76 1.0 746.7 0.9 829.6 900 AHU -1 RTU -1 YORK DIEX036 940 200 7,5 1 0.5 OS 4,3 1 3A 11,1 1 0,85 31.4 35 208 -3 -60 34.3 25.1 12.36 400 SEE 1 23.4 420 0.06 106 EXAM ROOM PAPIENT ROOM 124 1 25 - 25 - 25 1 1 25 130 0.19 107 EXAM ROOM PAPIENT ROOM 123 1 DRAWING RTU-2 YORK DIEX048 1400 150 7,5 1 0.5 0.75 6.8 1 4.0 13.4 1 0.25 47.6 - 208 -3 -60 44.8 34.5 12.3 440 SEE MEDICAL PROCEDURE 116 3 15 - 45 - 1 45 1 45 230 0.19 110 MALE GOWNED WAITING ROOM RECEPTION AREA 154 E30 5 0.06 30 9.24 39.24 DRAWING RTU -3 YORK 900 125 3.8 1 1,0 0.5 1,2 1 210 10,x? 1 0.25 27.9 0.13 208 -1 -60 24.9 18.6 12.3 355 SEE 10 5.34 20.34 1 20.34 300 0.07 116 HOT LAB ROOM MEDICAL PROCEDURE 98 2 15 - 30 - 30.0 1 30.0 60 0.5 117 CONTROL ROOM OFFICE SPACE 1. OUTSIDE AIR DESIGN CONDITIONS: 91'FDB - 77'FDB. 8. PROVIDE RTU WITH VENTSTAR T2950 PROGRAMMABLE 365 -DAY 2. PROVIDE 0 -25% MOTORIZED OUTSIDE AIR INTAKE WITH RAINHOOD 8c WMS. THERMOSTAT. 0.1 119 STORAGE ROOM 3. PROVIDE 24" FACTORY FABRICATED ROOFCURB WITH PROPER VIBRATION 9. STANDARD FACTORY INSTALLED DIRECT DRIVE ECM BLOWER MOTOR. 15.48 ISOLATORS. 1 10. UNIT RATED IN ACCORDANCE WITH ARI STANDARDS 210/240 OR 4. PROVIDE SINGLE POINT KIT FOR ELECTRICAL HOOK -UP. 360 AND 270. 6 5 5. PROVIDE DISCONNECT SWITCH WITH ALL ROOFTOP PACKAGE UNITS. 11. PROVIDE FIELD INSTALLED ROOF CURB WITH HURRICANE KIT. 6. PROVIDE "ULTRA- GUARD" COASTAL CORROSION PROTECTION FOR 121 CONFERENCE ROOM CONFERENCE ROOM 397 14 CONDENSER COILS. 0.06 10 23.82 93.82 7. PROVIDE 1 YEAR PARTS AND LABOR WARRANTY, 5 YEAR COMPRESSOR 125 OFFICE OFFICE SPACE 187 3 WARRANTY. 1 0.06 15 11.22 26.22 OUTSIDE AIR CALCULATIONS MULTIPLE -ZONE RECIRCULATING SYSTEMS (BASED ON ASHRAE STANDARD 62.1 -2004) VENTILATION ZONE OCCUPANCY CATEGORY Az (SF) Pz (p) Rp (CFM /p)(CFM Ra /SF) Rp x Pz (CFM) Ra x Az (CFM) Vbz (CFM) Ez Voz (CFM) IVpz (CFM) Zp Pa (p) E[P;] (p) D (p) Vou (CFM) Ev Vot (CFM) Fresh Air Intake (CFM) VIA 101 LOBBY MAIN ENTRY LOBBY 458 5 5 0.06 25 27,48 5148 1 52,48 345 0.15 5 5 1 52.48 1.0 52.48 200 AHU -2 102 WAITING RECEPTION AREA 560 17 5 0.06 85 33.6 1180 1 118.6 SW 0.15 76 76 1.0 746.7 0.9 829.6 900 AHU -1 CORRIDOR CORRIDORS 897 - - 0.06 - 53.82 1 53.82 1 53.82 375 0.14 OFFICE CORRIDOR OFFICE SPACE 140 3 5 0.06 15 8.4 23.4 1 23.4 420 0.06 106 EXAM ROOM PAPIENT ROOM 124 1 25 - 25 - 25 1 1 25 130 0.19 107 EXAM ROOM PAPIENT ROOM 123 1 25 - 25 - 25 1 1 25 130 0.19 108 EXAM ROOM PAPIENT ROOM 123 1 25 - 25 - 25 1 25 130 0.19 109 CONSULT ROOM MEDICAL PROCEDURE 116 3 15 - 45 - 1 45 1 45 230 0.19 110 MALE GOWNED WAITING ROOM RECEPTION AREA 154 6 5 0.06 30 9.24 39.24 1 39.24 300 0.13 113 FEMALE GOWNED WAITING ROOM RECEPTION AREA 154 6 5 0.06 30 9.24 39.24 1 39.24 300 0.13 115 CONTROL ROOM OFFICE SPACE 89 2 5 0.06 10 5.34 20.34 1 20.34 300 0.07 116 HOT LAB ROOM MEDICAL PROCEDURE 98 2 15 - 30 - 30.0 1 30.0 60 0.5 117 CONTROL ROOM OFFICE SPACE 262 4 1 5 0.06 20 15.72 35.72 1 35.72 360 0.1 119 STORAGE ROOM STORAGE ROOM 129 - - 0.12 - 15.48 15.48 1 15.48 30 0.5 120 WORK ROOM OFFICE SPACE 153 6 5 0.06 30 9.18 39.18 1 39.18 200 0.19 121 CONFERENCE ROOM CONFERENCE ROOM 397 14 5 0.06 70 23.82 93.82 1 93.82 580 0.18 125 OFFICE OFFICE SPACE 187 3 5 1 0.06 15 11.22 26.22 1 1 1 26.22 520 0.05 126 STAFF LOUNGE LOUNGES ROOM 148 6 7.5 0.18 45 26.64 56.64 1 56.64 600 0.09 127 DOCTOR OFFICE OFFICE SPACE 148 1 25 - 25 - 25 1 25 600 0.04 401 ELEVATOR LOBBY MAIN ENTRY LOBBY 243 3 5 0.06 15 14.58 29.58 1 29.58 100 0.29 3 3 0.9 73.38 0.8 91.73 200 RTU -1 409 CORRIDOR CORRIDORS 112 - - 0.06 - 6.72 6.72 1 6.72 50 0.13 416 CORRIDOR CORRIDORS 643 - - 0.06 - 38.58 38.58 1 38.58 320 0.12 402 RECEPTION RECEPTION AREA 273 8 5 0.06 40 16738 56.38 1 56.18 250 0.22 15 12 0.8 119.46 0.9 132.76 150 RTU -2 403 CONSULT. CONFERENCE ROOM 87.5 4 5 0.06 20 5.25 25.25 1 25.25 120 0.21 404 STORAGE ROOM STORAGE ROOM 80 - - 0.12 - 9.6 9.6 1 9,6 30 0.32 405 OFFICE OFFICE SPACE 120.5 1 5 0.06 5 1 7.23 12.23 1 12.23 300 0,04 406 OFFICE OFFICE SPACE 122 1 5 0.06 5 1 7.32 12.32 1 12.32 220 0.05 407 OFFICE OFFICE SPACE 228 1 5 0106 5 13.68 18.68 1 18.68 450 0.04 411 CONFERENCE ROOM CONFERENCE ROOM 433 14 5 0.06 70 25.98 95.98 1 95.98 1 1040 0.09 14 12 0.8 81.98 1 1 81.98 125 RTU -3 419 BILLING OFFICE SPACE 485 4 5 0.06 20 29.1 49.1 1 49.1 8 8 1.0 87.1 87.1 100 RTU -4 420 OFFICE OFFICE SPACE 150 2 5 0.06 10 9.0 1 19.0 1 19.0 421 OFFICE OFFICE SPACE 150 2 5 0.06 10 9.0 1910 1 19.0 114 BRACHY MEDICAL PROCEDURE 258 1 15 - - 15.0 15.0 1 15.0 1070 0.01 1 1 1 1.0 15.0 1.0 15.0 1 70 AHU -3 118 VAULT MEDICAL PROCEDURE 552 2 30 - - 30.0 30.0 1 30.0 2100 0.01 2 1 2 1.0 30.0 1.0 1 30.0 1 180 AHU -4A & AHU -4B DEFINITIONS: Az: NET OCCUPIED FLOOR AREA Ra: OUTDOOR AIRFLOW RATE REQUIRED PER UNIT AREA AS DETERMINED FROM TABLE 6 -1 Ev: SYSTEM VENTILATION EFFICIENCY AS DETERMINED FROM TABLE 6 -3 Pz: ZONE POPULATION (BASED ON MAX. Zp) Rp: OUTDOOR AIRFLOW RATE REQUIRED PER PERSON AS DETERMINED FROM TABLE 6 -1 Zp: ZONE PRIMARY OUTDOOR AIR FRACTION Vou: UNCORRECTED OUTDOOR AIR INTAKE Zp - Voz/Vpz Vou - D i_ Rp X Pz + 1_ Ra X Az Vpz: ZONE PRIMARY AIRFLOW D: OCCUPANT DIVERSITY Voz: ZONE OUTDOOR AIRFLOW Voz = Vbz /Ez D = Ps /]L- Pz Ez: ZONE AIR DISTRIBUTION EFFECTIVENESS AS DETERMINED FROM TABLE 6 -2 Ps: TOTAL POPULATION IN THE AREA SERVED BY THE SYSTEM Vbz: BREATHING ZONE OUTDOOR AIR FLOW Vot: DESIGN OUTDOOR AIR INTAKE FLOW Vbz = Rp X Pz + Ra X Az Vot= Vou /Ev FAN SCHEDULE MARK SELECTI ❑N BASED ON TYPE/ CFM TSP CONTROL SYSTEM DATA MOTOR DATA DRIVE S❑NES UNIT REMARKS HEATER SERVICE MAX. IN WG MARK BRAND WT OR NC WEIGHT FAN MAKE MODEL N❑. HP RPM VOLTS -PH -HZ EF -1 COOK 70SQN15D INLINE 1ST. FLR. TOILET EXHAUST 100 0.375 ® M ❑DEL N❑, 0.05 1656 115 -1 -60 DIRECT 4.0 70 SEE NOTES EF -2 -9 GREENHECK CSP -B50 INLINE 1ST. FLR. TOILET EXHAUST 51 0.125 2 O FLA 38 W 625 115 -1 -60 DIRECT 1.4 SPHE. 9 SEE NOTES GEF -1 COOK 195SQN -B SEE DRAWING 4300 0.500 O 60 1.00 1725 208 -3 -60 BELT 16.4 256 SEE NOTES SF -1 COOK 90SQN10D SEE DRAWING 250 0.440 �4 5/8" 0.167 1420 115 -1 -60 DIRECT 6.3 90 SEE NOTES EF -10 GREENHECK SQ -70 -VG HOT LAB 135 0.5 ® 143 1/6 1725 115 -1 -60 DIRECT 5.7 f 34 SEE NOTES GENERAL FAN NOTES: 32.6 20.16 14.6 5 8" 1. PROVIDE MOTOR STARTERS DISDONNECTS AND ALL ASSOCIATED CONTROLS AHU -4B 1 7. PROVIDE MOTOR HEATERS SIZED AS REQUIRED FOR FIELD CONDITIONS, ON ALL FANS. 0.9 0 8. PROVIDE FACTORY FAN MOUNTING SUPPORTS -LEGS, CURBS, HANGING CLIPS, ETC.. 2. PROVIDE BACKDRAFT FOR ALL EXHAUST FANS . 60 CU -4B 9. PROVIDE SPEED CONTROLLER ADJACENT TO FAN FOR BALANCING. 3. FIELD ADJUST OPENINGS WITH STRUCTURE. 1 3.5 O1 CONTROL BY OCCUPANCY SENSORS IN EACH RESTROOM. SEE ELECTRICAL, 4. PROVIDE BIRDSCREEN ON ALL INLETS AND OUTLETS. 17.3 35 35 32.6 5. COORDINATE WITH ELECTRICAL CONTRACTOR BEFORE BIDDING OR ORDERING 14.6 0 INTERLOCKED WITH LIGHT SWITCH. ANY EQUIPMENT. AHU -5 PANASONIC MODEL : S- 42PU1U6 1050 70 6. SEE GENERAL, AIR CONDITIONING, DUCTWORK, AND COORDINATION NOTES FOR OTHER Q INTERLOCKED WITH CO SENSOR FIELD SUPPLIED ITEMS. 15 60 �4 RUNNING CONTINUOUS PANASONIC MODEL: U- 42PS1U6 220 208 230 -1 -60 / 1 3.5 AIR BALANCE SCHEDULE MINI SPLIT CASSETTE DUCTLESS SYSTEM SCHEDULE OUTSIDE AIR AIR HANDLING UNIT VIA AIR COOLED CONDENSING UNIT VIA SYSTEM DATA MARK BRAND/ZONE MODEL N❑, CFM ESP FAN HEATER CIRC , MAX. WT MARK BRAND WT ELECTRICAL COMPRESSOR FAN CIRC. MAX, CAPACITY 200 REF. LINES AHU -2 100 EF -1 AMP. FUSE LBS M ❑DEL N❑, LBS VOLTS -PH -HZ AMP. FUSE SEER TOTAL_ ❑A FLA KW STEP QTY, TONS RLA QTY FLA TMBH SMBH SUCTION LIQUID AHU -3 PANASONIC MODEL : S- 42PU1U6 1050 70 - 1.0 0 - 15 15 60 CU -3 PANASONIC MODEL: U- 42PS1U6 220 208/230 -1 -60 1 3.5 18.1 1 19.7 40 40 39.5 23.53 14.6 5/8" 3AHU -4A PANASONIC 1050 90 - 0.9 0 - 15 15 60 CU -4A PANASONIC 143 208 230 -1 -60 1 3.5 16.4 1 17.3 35 35 32.6 20.16 14.6 5 8" AHU -4B MODEL : S- 36PU1U6 1050 90 - 0.9 0 - 15 15 60 CU -4B MODEL: U- 42PS1U6 143 208 230 -1 -60 1 3.5 16.4 1 17.3 35 35 32.6 20.16 14.6 5 8" AHU -5 PANASONIC MODEL : S- 42PU1U6 1050 70 - 1.0 0 - 15 15 60 CU -5 PANASONIC MODEL: U- 42PS1U6 220 208 230 -1 -60 / 1 3.5 18.1 1 19.7 40 40 39.5 23.53 14.6 5 8" / 3 8" / 122 ELECTRICAL ROOM 123 JANITOR 124 STAFF TOILET 125 OFFICE 126 STAFF LOUNGE 127 DOCTOR OFFICE 130 TELECOM. 114 BRANCHY 1050 70 980 AHU -3 - - SPLIT SYSTEM NOTES: 118 VAULT 2100 1. OUTSIDE AIR DESIGN CONDITIONS: 917DB - 79'FDB. 6. MATERIALS: 1920 AHU -4A 2. PROVIDE A/C UNITS WITH PROGRAMMABLE HEATING AND COOLING THERMOSTAT WITH _ A. ON -OFF SWITCH SUB -BASE. (WIRED AND INSTALLED BY ELECTRICAL CONTRACTOR) REFRIGERANT PIPING: SHALL BE TYPE L SOFT DRAWN, COPPER TUBING, DEHYDRATED FOR REFRIGERANT USE. SIZED AS SHOWN ON DRAWINGS OR AS 3. PROVIDE PROPER VIBRATION ISOLATORS AS PER ISOLATION PER AIR CONDITIONING EQUIPMENT MANUFACTURER'S RECOMMENDATIONS. 401 ELEVATOR LOBBY MANUFACTURER'S RECOMMENDATIONS. B. INSULATION: REFRIGERANT SUCTION PIPING AND CONDENSATE PIPES SHALL BE 4. INSTALL CHEMICAL DRYER AND STRAINER IN REFRIGERANT LIQUID LINES. INSULATED WITH 3/4" THICK FOAMED PLASTIC INSULATION, FIRE RETARDANT TYPE. 5. PROVIDE BUILT -IN DISCONNECT WITH ALL AIR HANDLING UNITS. INSULATION SHALL BE INSTALLED IN PIPING BEFORE ASSEMBLY. NO SPLIT 6. CONDENSING UNITS TO BE PROVIDED WITH TIME DELAY AND PHASE LOSS PROTECTIN INSULATION WILL BE ACCEPTABLE. SEAL JOINTS WITH MANUFACTURER'S APPROVED ADHESIVE AND GREY TAPE. 410 HLI< X1 13 TLT 1190 VOR FRIEDRICH EQUIPMENT ALL INDOOR UNITS RECEIVE POWER FROM OUTDOOR UNIT, VALUES LISTED ARE TOTAL, 990 AIR BALANCE SCHEDULE AREA SUPPLY AIR OUTSIDE AIR RETURN AIR VIA EXHAUST AIR VIA BLDG. PRESS. [CFM] [mi] [CFM] [CFM] [CFM] 101 LOBBY 103 FEMALE 800 200 600 AHU -2 100 EF -1 +100 104 MALE 102 WAITING CORRIDOR 106 EXAM 107 EXAM 108 EXAM 109 CONSULT 110 MALE GOWNED WAITING 111 TOILET /CHANGING 112 TOILET /CHANGING 113 FEMALE GOWNED WAITING 115 CONTROL EF -2 & EF -3 116 HOT LAB 6225 900 5325 AHU -1 200 +700 117 CONTROL EF -4 & ff -5 119 STORAGE 120 WORK ROOM 121 CONFERENCE 122 ELECTRICAL ROOM 123 JANITOR 124 STAFF TOILET 125 OFFICE 126 STAFF LOUNGE 127 DOCTOR OFFICE 130 TELECOM. 114 BRANCHY 1050 70 980 AHU -3 - - +70 118 VAULT 2100 180 1920 AHU -4A _ _ +180 AHU -48 401 ELEVATOR LOBBY 409 CORRIDOR 410 HLI< X1 13 TLT 1190 200 990 RTU -1 150 EF_7 +50 414 Ti .F EF -8 & EF -9 416 CORRIDOR 402 RECEPTION 403 CONSULT. 404 STORAGE 405 OFFICE 406 OFFICE 1400 150 1315 RTU -2 50 EF -6 +100 407 OFFICE 4OB TOILET 411 CONFERENCE 800 125 675 RTU -3 - - +125 0 z C n z 1P Q d' 0 k `v C 3 0i N 0 0 0 o! F- U 1v (0 N x Irrk 0 Design Services For The Built Environment L-1 A t I a n t a Birmingham Cincinnati Columbus IDaIIas Fort Lauderdale Knoxville Jackson Jacksc nviIIe Louisville Memphis Nashville Rich1TIOI7d Tampa 0 R. E S H A M SMITH AND P A R. T N E R, 6030 Hollywood Blvd, Suite 210 Hollywood, Florida 33024 954981,0100 FIr11A'S FLORIDA CERT. NQ. AAP000034/CA3806 IB2 6000797/LC26000381 ,& DELTA G CONSULTING 707 N.E. 3rd AVE., SUITE 200 FORT LAUDERDALE, FL. 33304 (954) 527 -1112 IL CA #00009181 P]T. MGR: MICHAEL H00 PROJECT #: 120717 ��A,1 @11191117 sY 7 {0 .� �1IG Oj2 E FsojuMNv k uiG*Nai #46100 1819 I No, - Oats RQ.Vi *ibn 02/01/13 :Addendum #1 ................................:...... ............................... 05/17/13 City Comments Response 10/04/13 VE Revisions 10/04/13 I.T. Revisions MECHANICAL SCHEDULES Mlm2 FILE: PHOJECT: 29080.00 DATE: 1 1/29/2012