13-96 (3)-073#14GND 6 TO CONTROL EQUIPMENT Q BS PULL BOX s a , Q #6GND '�t4 TO FACP CWP� TO TBB 6' MIN. #6GND 4 9 2 1 QROUNDINQ DETAIL E4.1 N.T.S. NOTE: ALL GROUNDING INSTALLATIONG SHALL COMPLY WITH NEC ARTICLE 250. t0 10 FT. LONG x 4" DIAMETER COPPER DRIVEN GROUND ELECTRODE. 20 ADDITIONAL ELECTRODE AS REQUIRED BY NEC 250.56. O CONNECTION TO METALIC COLD WATER PIPE. O EXOTHERMIC CONNECTION (TYPICAL) O 3/0 EXOTHERMIC CONNECTION. ELECTRICALLY CONTINUOUS STEEL REINFORCING BAR IN BOTTOM OF BUILDING FOUNDATION IN DIRECT CONTACT WITH EARTH. Q ATTACH GROUND BAR TO GROUNDING CONDUCTOR USING SOLID CABLE TO FLAT BAR CONNECTOR. O MAKE CONNECTION TO METALLIC COLD WATER ENTRANCE PIPE BEFORE FIRST VALVE WITH HEAVY DUTY BRONZE GROUND CLAMP. O PROVIDE (1) #4/0 BONDING JUMPER AROUND FIRST VALVE. 0 #3/0 GND IN 1 "C. t0 CONNECTION TO NATURAL GAS PIPE. t t NOT USED. ,z #1/0 GND IN 3/4 "C. t3 #8 GND IN 1/2 "C. 6 t4 CONNECTION TO CONCRETE— ENCASED ELCTRODE WITH DIRECT BURIAL LISTED CLAMP. ,s #4 GND IN 3/4 "C. e#14 GND IN 1/2 "C. PATIO MAIN O 5OF6 MAIN 1200A M.C.B. SERVICE 6 OF 6 ENTRANCE RATED 400A M.C.B. TRYSTAR ROTARY SERVICE GENERATOR DOCKING TRYSTAENTRANCE RATED STATION 33R R ROTARY GENERATOR DOCKING STATION 0 3ROUND ELECTRICAL RISER (VOTES 1. CONTRACTOR TO PROVIDE A PERMANENT PLAQUE FOR EACH NORMAL MAIN AND INDICATE LOCATION OF ALL OTHER MAINS AS PER NEC 225.37. 2. CONTRACTOR SHALL PROVIDE FLASH HAZARD MARKING AS PER NEC 110.16. 3. PROVIDE IDENTIFICATION OF DISCONNECTING MEANS PER NEC 110.22. FEEDER SCHEDULE Ft (3) SETS OF 4 "C. EACH WITH (4) #600KCMIL O 4 "C. WITH 4 #500KCMIL O REFER TO ELECTRICAL RISER NOTES ABOVE. F4 4 "C. WITH 4#500KCMIL AND (1) #3GND O 3" EMPTY CONDUIT WITH PULLSTRINGS Fa 1 1/40C. WITH (4) #3 AND (1) #8GND O 2 "C. WITH (4) #3 O 2 "C. WITH (4) #1 AND (1) #6GND Q 3 "C. WITH (4) #3/0 AND (1) #6GND 2 "C. WITH (4) #3 AND (1) #8GND ®i 1" EMPTY CONDUIT WITH PULLSTRINGS 2" EMPTY CONDUIT WITH PULLSTRINGS 3" EMPTY CONDUIT WITH PULLSTRINGS E) NOT USED. SEE PANEL SCHEDULE. E) 3 "C. WITH (4) #3/0 t 1 1/4" RGS (1) SETS G F 4 "C. EACH WITH (4) #600KCMIL & 2 SETS OF 3 "C. EACH WITH (4) 350KCMIL 2 "C. WITH (4) #1 AND (1) #1 GND ® #1/0 SECONDARY BONDING GND IN 2 "C. TO NEAREST BUILDING STEEL AND CWP. ® 3/4 "C. FOR EPO SHUNT TRIP WIRES. ® PROVIDE STEP —UP TRANSFORMER ON CONCRETE t I A A A A A A F_ HOUSEKEEPING PAD. PARKING CHILLER EQUIP IOIL 777FU 1 1 r77iFM- ar BACK EXTERIOR 1110 208V//480V 225KVA XFMR 0 0 REVISION 33R 4OF6 O O 3-*3R OW As #3/0 KCMIL G G FUTURE VAULT AREA G PNL ICTI IE CT ROOM EP01 EP03 LT ROOM VAULT CONTROL ROOM IT 128 MODULAR ' 48OV, 3P /90A MCB PANEL FURNISHED BY VARIAN mm no PU DUCT BOX DUCT 'PD' VD1 CONTROL PNL EQUIP. 'IT' PULL BOX G G G — our 3P /200A �t 3P /9OA POWER CONDITIONER 8BLX -50K- 70OA/VS FURNISHED BY VARIAN G— G TO LIGHT POLES PNL PNL '4A' '41 A' " r.� 0 :J 60OW INVERTER PHILIPS CHLORIDE Z1600 -120 ELECTRICAL ROOM 122 Fa Fs SwW;c Ll •I •II'�,11• •�11• LZAMJ L wj L = ''r' "' 1200A MLO, PNL PNL PNL 120/208V, 'GE' '1E' '1 CE' , 0, 4W . _G G — — G G — ELECTRICAL RISER DIAGRAM _G G — SCALE: N.T.S. PNL '4E' C E4.1 MAIN REVISION AT MAINS #1. #2. AND TRANSFORMER LET — THROUGH SHORT — CIRCUIT CURRENT 13.C.: 4OF6 VOLTAGE: 3-*3R WIRE SIZE: #3/0 KCMIL NUMBER OF CONDUCTORS PER PHASE C: 1 CONDUCTOR LENGTH L: 75' no n1' 13,1'23 CONDUCTORS PER PHASE x C = ) an F� _T f — FACTOR 100A 1.73 x L x IS.C. _ 1.73 x 75 x 32,552 f METER 1 = —_ 1 M 0.407 = 1 + f 1 + 1.46 IS.Ca►= IS.C. x M = 32,552 x 0.407 = 13,232 A RMS 0 8 ROOF 4TH FLOOR I 3RD FLOOR — PARKING GARAGE 2ND FLOOR — PARKING GARAGE (FAULT CURRENT CALCULATIONS REVISION AT MAINS #1. #2. AND TRANSFORMER LET — THROUGH SHORT — CIRCUIT CURRENT 13.C.: 32,552 AMPS VOLTAGE: 120/208V, 30 WIRE SIZE: #3/0 KCMIL NUMBER OF CONDUCTORS PER PHASE C: 1 CONDUCTOR LENGTH L: 75' (C NDUCTOR C VALUE: 13,1'23 CONDUCTORS PER PHASE x C = ) M — MULTIPLIER f — FACTOR 1.73 x L x IS.C. _ 1.73 x 75 x 32,552 f C x EL � _ 13923 x 208 = 1.46 1 = —_ 1 M 0.407 = 1 + f 1 + 1.46 IS.Ca►= IS.C. x M = 32,552 x 0.407 = 13,232 A RMS RMS MINIMUM BREAKER RATING - 18,000 A.I.C. AT MAIN JA TRANSFORMER LET — THROUGH SHORT — CIRCUIT CURRENT IS.C. : 32,552 AMPS VOLTAGE: 120/208V, 30 WIRE SIZE: #3 NUMBER OF CONDUCTORS PER PHASE C: 1 CONDUCTOR LENGTH L: 75' NDUCTOR C VALUE: 4,811 CONDUCTORS PER PHASE x C = ) M — MULTIPLIER f —FACTOR f = 1.73 x L x Is_c_ 1.73 x 75 x 32,552 = = 4 22 C x EL_L 4811 x 208 __ 1 1 M = '� 0.192 1 + f 1 + 4.22 IS.c n= IS.C. x M — 32,552 x 0.192 — 6,236 A RMS RMS MINIMUM BREAKER A.I.C. RATING = 10,000 A.I.C. #5 AT MAIN TRANSFORMER LET — THROUGH SHORT— CIRCUIT CURRENT IS.C. : 32,552 AMPS VOLTAGE: 120/208V, 30 WIRE SIZE: #600 KCMIL NUMBER OF CONDUCTORS PER PHASE C: 3 CONDUCTOR LENGTH L: 150' NDUCTOR C VALUE: 84,099 CONDUCTORS PER PHASE x C = ) M — MULTIPLIER f —FACTOR f m 1.73 x L x Is_�_ 1.73 x 150 x 32,552 = 0,483 C x EL—L 84,099 x 208 M = 0.674 1 + f 1 + 0.483 Is.C.A° IS.C, x M = 32,552 x 0.674 = 21,950 A RMS RMS MINIMUM BREAKER A.I.C. RATING - 22,000 A.I.C. AT MAIN #6 TRANSFORMER LET- THROUGH SHORT- CIRCUIT CURRENT IS.C. : 32,552 AMPS VOLTAGE: 120/208V, 30 WIRE SIZE: #500 KCMIL NUMBER OF CONDUCTORS PER PHASE C: 1 CONDUCTOR LENGTH L: 150' (C NDUCTOR C VALUE: 26,706 CONDUCTORS PER PHASE x C = ) M - MULTIPLIER f -FACTOR f= 1.73 x L x Is.c. 1.73 x 150 x 32,552 mm = 1.52 C x EL-L 26,706 x 208 M= 1 _ 1 = 0.397 1 + f 1 + 1.52 IS.CA= IS.C. x M = 32,552 x 0.397 = 12,917 A RMS RMS MINIMUM BREAKER A.I.C. RATING a 14,000 A.I.C. EXTERIOR WALL MAIN MAIN MAIN 3OF6 2OF6 1 OF 33R 33R 33R 0 METER 0 0 0 400A CT METER CAN 200A 200A 200A ' METER METER METER NEW FP &L 120/208V, 30 TRANSFORMER 1, A r i".. i da. 0 a C*? N G S & P Design Services" IMnr The Btilt Environment Atlanta Birmingham Cincinnati Columbus Qa_IIas Fort Lauderdale Koaxvil_Ie Jackson Jacksonville LouisyiII i4"M h is N ashviII . Richmond Tampa R: E S H A M M I T H A I P A R. T N E R. S 6030 Hollywood Blvd, Suite 210 HOIMywood, Florida 33024 964.981.0100 FIRM'S FLORIDA CERT, N0, AAPO00034 /CA.3S06. 1026000797f!LC26000381 DELTA G CONSULTING AILFORT INEERS, INC. .E. 3rd AVE., SUITE 200 LAUDERDALE, FL. 33304 ) 627 -1112 I00009181 PJT. M GR: MICHAEL H00 PROJECT #: 120717 = < off` i� � U_ 0 3�::>:: N" d A I 04/22/13 ;'City Comments Response 10/04/13 VE Revisions ELECTRICAL RISER DIAGRAM E4.1 FILE: PROJECT: 29080.00 DATE: 1 1 /29/201 2 REVISION ��Ig?19Ii�:�a9d (mate - Revision. A� 1%"% ; �y�� off_ °�,7 V j 02/01/13 Addendum #1 ............ :......................... .... ......... .... ....... 03/15/13 1City Comments Response x � , 04/22/13 ;'City Comments Response 10/04/13 VE Revisions ELECTRICAL RISER DIAGRAM E4.1 FILE: PROJECT: 29080.00 DATE: 1 1 /29/201 2 REVISION No - (mate - Revision. 02/01/13 Addendum #1 ............ :......................... .... ......... .... ....... 03/15/13 1City Comments Response 04/22/13 ;'City Comments Response 10/04/13 VE Revisions ELECTRICAL RISER DIAGRAM E4.1 FILE: PROJECT: 29080.00 DATE: 1 1 /29/201 2