13-96 (3)-073#14GND
6 TO CONTROL
EQUIPMENT
Q BS PULL BOX
s
a ,
Q #6GND
'�t4 TO FACP
CWP� TO TBB
6' MIN. #6GND
4 9
2 1
QROUNDINQ DETAIL
E4.1 N.T.S.
NOTE: ALL GROUNDING INSTALLATIONG SHALL
COMPLY WITH NEC ARTICLE 250.
t0 10 FT. LONG x 4" DIAMETER COPPER DRIVEN
GROUND ELECTRODE.
20 ADDITIONAL ELECTRODE AS REQUIRED BY NEC
250.56.
O CONNECTION TO METALIC COLD WATER PIPE.
O EXOTHERMIC CONNECTION (TYPICAL)
O 3/0 EXOTHERMIC CONNECTION. ELECTRICALLY
CONTINUOUS STEEL REINFORCING BAR IN BOTTOM
OF BUILDING FOUNDATION IN DIRECT CONTACT
WITH EARTH.
Q ATTACH GROUND BAR TO GROUNDING CONDUCTOR
USING SOLID CABLE TO FLAT BAR CONNECTOR.
O MAKE CONNECTION TO METALLIC COLD WATER
ENTRANCE PIPE BEFORE FIRST VALVE WITH HEAVY
DUTY BRONZE GROUND CLAMP.
O PROVIDE (1) #4/0 BONDING JUMPER AROUND
FIRST VALVE.
0 #3/0 GND IN 1 "C.
t0 CONNECTION TO NATURAL GAS PIPE.
t t NOT USED.
,z #1/0 GND IN 3/4 "C.
t3 #8 GND IN 1/2 "C. 6
t4 CONNECTION TO CONCRETE— ENCASED ELCTRODE
WITH DIRECT BURIAL LISTED CLAMP.
,s #4 GND IN 3/4 "C.
e#14 GND IN 1/2 "C.
PATIO
MAIN
O 5OF6
MAIN 1200A M.C.B.
SERVICE
6 OF 6 ENTRANCE RATED
400A M.C.B. TRYSTAR ROTARY
SERVICE GENERATOR DOCKING
TRYSTAENTRANCE RATED STATION 33R
R ROTARY
GENERATOR DOCKING
STATION
0
3ROUND
ELECTRICAL RISER (VOTES
1. CONTRACTOR TO PROVIDE A PERMANENT PLAQUE FOR
EACH NORMAL MAIN AND INDICATE LOCATION OF ALL OTHER
MAINS AS PER NEC 225.37.
2. CONTRACTOR SHALL PROVIDE FLASH HAZARD MARKING AS
PER NEC 110.16.
3. PROVIDE IDENTIFICATION OF DISCONNECTING MEANS PER
NEC 110.22.
FEEDER SCHEDULE
Ft (3) SETS OF 4 "C. EACH WITH (4) #600KCMIL
O 4 "C. WITH 4 #500KCMIL
O REFER TO ELECTRICAL RISER NOTES ABOVE.
F4 4 "C. WITH 4#500KCMIL AND (1) #3GND
O 3" EMPTY CONDUIT WITH PULLSTRINGS
Fa 1 1/40C. WITH (4) #3 AND (1) #8GND
O 2 "C. WITH (4) #3
O 2 "C. WITH (4) #1 AND (1) #6GND
Q 3 "C. WITH (4) #3/0 AND (1) #6GND
2 "C. WITH (4) #3 AND (1) #8GND
®i 1" EMPTY CONDUIT WITH PULLSTRINGS
2" EMPTY CONDUIT WITH PULLSTRINGS
3" EMPTY CONDUIT WITH PULLSTRINGS
E) NOT USED.
SEE PANEL SCHEDULE.
E) 3 "C. WITH (4) #3/0
t 1 1/4" RGS
(1) SETS G F 4 "C. EACH WITH (4) #600KCMIL &
2 SETS OF 3 "C. EACH WITH (4) 350KCMIL
2 "C. WITH (4) #1 AND (1) #1 GND
® #1/0 SECONDARY BONDING GND IN 2 "C. TO
NEAREST BUILDING STEEL AND CWP.
® 3/4 "C. FOR EPO SHUNT TRIP WIRES.
® PROVIDE STEP —UP TRANSFORMER ON CONCRETE
t I A A A A A A F_
HOUSEKEEPING PAD.
PARKING
CHILLER EQUIP
IOIL
777FU 1 1 r77iFM- ar
BACK EXTERIOR
1110
208V//480V
225KVA XFMR
0 0
REVISION
33R
4OF6
O O
3-*3R
OW As
#3/0 KCMIL
G G
FUTURE
VAULT
AREA
G
PNL
ICTI
IE
CT ROOM
EP01 EP03
LT ROOM VAULT CONTROL ROOM IT 128
MODULAR
' 48OV, 3P /90A
MCB PANEL
FURNISHED
BY VARIAN
mm
no
PU DUCT
BOX DUCT
'PD' VD1 CONTROL PNL
EQUIP. 'IT'
PULL BOX
G
G
G —
our 3P /200A
�t
3P /9OA
POWER
CONDITIONER
8BLX -50K-
70OA/VS
FURNISHED
BY VARIAN
G—
G
TO LIGHT
POLES
PNL PNL
'4A' '41 A'
" r.�
0
:J 60OW INVERTER
PHILIPS CHLORIDE
Z1600 -120
ELECTRICAL ROOM 122
Fa Fs SwW;c
Ll
•I •II'�,11• •�11•
LZAMJ L wj L = ''r' "' 1200A MLO,
PNL PNL PNL 120/208V,
'GE' '1E' '1 CE' , 0, 4W .
_G
G —
— G
G —
ELECTRICAL RISER DIAGRAM
_G
G —
SCALE: N.T.S.
PNL
'4E'
C
E4.1
MAIN
REVISION
AT MAINS #1. #2. AND
TRANSFORMER LET — THROUGH SHORT — CIRCUIT CURRENT 13.C.:
4OF6
VOLTAGE:
3-*3R
WIRE SIZE:
#3/0 KCMIL
NUMBER OF CONDUCTORS PER PHASE C:
1
CONDUCTOR LENGTH L:
75'
no n1'
13,1'23
CONDUCTORS PER PHASE x C = )
an
F�
_T
f — FACTOR
100A
1.73 x L x IS.C. _ 1.73 x 75 x 32,552
f
METER
1
= —_ 1
M 0.407
=
1 + f 1 + 1.46
IS.Ca►= IS.C. x M = 32,552 x 0.407 = 13,232 A RMS
0
8
ROOF
4TH FLOOR I
3RD FLOOR —
PARKING GARAGE
2ND FLOOR —
PARKING GARAGE
(FAULT CURRENT CALCULATIONS
REVISION
AT MAINS #1. #2. AND
TRANSFORMER LET — THROUGH SHORT — CIRCUIT CURRENT 13.C.:
32,552 AMPS
VOLTAGE:
120/208V, 30
WIRE SIZE:
#3/0 KCMIL
NUMBER OF CONDUCTORS PER PHASE C:
1
CONDUCTOR LENGTH L:
75'
(C NDUCTOR C VALUE:
13,1'23
CONDUCTORS PER PHASE x C = )
M — MULTIPLIER
f — FACTOR
1.73 x L x IS.C. _ 1.73 x 75 x 32,552
f
C x EL � _ 13923 x 208 = 1.46
1
= —_ 1
M 0.407
=
1 + f 1 + 1.46
IS.Ca►= IS.C. x M = 32,552 x 0.407 = 13,232 A RMS
RMS
MINIMUM BREAKER RATING - 18,000 A.I.C.
AT MAIN JA
TRANSFORMER LET — THROUGH SHORT — CIRCUIT CURRENT IS.C. :
32,552 AMPS
VOLTAGE:
120/208V, 30
WIRE SIZE:
#3
NUMBER OF CONDUCTORS PER PHASE C:
1
CONDUCTOR LENGTH L:
75'
NDUCTOR C VALUE:
4,811
CONDUCTORS PER PHASE x C = )
M — MULTIPLIER
f —FACTOR
f = 1.73 x L x Is_c_ 1.73 x 75 x 32,552
= = 4 22
C x EL_L 4811 x 208
__ 1 1
M =
'� 0.192
1 + f 1 + 4.22
IS.c n= IS.C. x M — 32,552 x 0.192 — 6,236 A RMS
RMS
MINIMUM BREAKER A.I.C. RATING = 10,000 A.I.C.
#5
AT MAIN
TRANSFORMER LET — THROUGH SHORT— CIRCUIT CURRENT IS.C. :
32,552 AMPS
VOLTAGE:
120/208V, 30
WIRE SIZE:
#600 KCMIL
NUMBER OF CONDUCTORS PER PHASE C:
3
CONDUCTOR LENGTH L:
150'
NDUCTOR C VALUE:
84,099
CONDUCTORS PER PHASE x C = )
M — MULTIPLIER
f —FACTOR
f m 1.73 x L x Is_�_ 1.73 x 150 x 32,552
= 0,483
C x EL—L 84,099 x 208
M = 0.674
1 + f 1 + 0.483
Is.C.A° IS.C, x M = 32,552 x 0.674 = 21,950 A RMS
RMS
MINIMUM BREAKER A.I.C. RATING - 22,000 A.I.C.
AT MAIN #6
TRANSFORMER LET- THROUGH SHORT- CIRCUIT CURRENT IS.C. :
32,552 AMPS
VOLTAGE:
120/208V, 30
WIRE SIZE:
#500 KCMIL
NUMBER OF CONDUCTORS PER PHASE C:
1
CONDUCTOR LENGTH L:
150'
(C NDUCTOR C VALUE:
26,706
CONDUCTORS PER PHASE x C = )
M - MULTIPLIER
f -FACTOR
f= 1.73 x L x Is.c. 1.73 x 150 x 32,552
mm = 1.52
C x EL-L 26,706 x 208
M= 1 _ 1 = 0.397
1 + f 1 + 1.52
IS.CA= IS.C. x M = 32,552 x 0.397 = 12,917 A RMS
RMS
MINIMUM BREAKER A.I.C. RATING a 14,000 A.I.C.
EXTERIOR WALL
MAIN MAIN MAIN
3OF6 2OF6 1 OF
33R 33R 33R 0
METER
0 0 0 400A CT
METER CAN
200A 200A 200A
' METER METER METER
NEW FP &L
120/208V, 30
TRANSFORMER
1, A r i".. i da.
0
a
C*?
N
G S & P
Design Services"
IMnr The Btilt
Environment
Atlanta Birmingham
Cincinnati
Columbus Qa_IIas
Fort Lauderdale
Koaxvil_Ie Jackson
Jacksonville LouisyiII
i4"M h is N ashviII .
Richmond Tampa
R: E S H A M
M I T H A I
P A R. T N E R. S
6030 Hollywood Blvd,
Suite 210
HOIMywood, Florida 33024
964.981.0100
FIRM'S FLORIDA
CERT, N0,
AAPO00034 /CA.3S06.
1026000797f!LC26000381
DELTA G CONSULTING
AILFORT INEERS, INC.
.E. 3rd AVE., SUITE 200
LAUDERDALE, FL. 33304
) 627 -1112
I00009181
PJT. M GR: MICHAEL H00
PROJECT #: 120717
= <
off` i� �
U_
0 3�::>::
N"
d A
I
04/22/13 ;'City Comments Response
10/04/13 VE Revisions
ELECTRICAL RISER
DIAGRAM
E4.1
FILE:
PROJECT: 29080.00
DATE: 1 1 /29/201 2
REVISION
��Ig?19Ii�:�a9d
(mate - Revision.
A�
1%"%
;
�y�� off_ °�,7 V j
02/01/13 Addendum #1
............ :......................... .... ......... .... .......
03/15/13 1City Comments Response
x �
,
04/22/13 ;'City Comments Response
10/04/13 VE Revisions
ELECTRICAL RISER
DIAGRAM
E4.1
FILE:
PROJECT: 29080.00
DATE: 1 1 /29/201 2
REVISION
No -
(mate - Revision.
02/01/13 Addendum #1
............ :......................... .... ......... .... .......
03/15/13 1City Comments Response
04/22/13 ;'City Comments Response
10/04/13 VE Revisions
ELECTRICAL RISER
DIAGRAM
E4.1
FILE:
PROJECT: 29080.00
DATE: 1 1 /29/201 2