13-96 (3)-059KEY NOTES Oi 4" STANDPIPE AND 2" DRAIN RISER UP. O2 SUPERVISED FLOOR CONTROL VALVE. SEE DETAIL ON SHEET FP1.1. O 2 -1/2" HOSE CONNECTION. O CONNECT NEW 2" DRAIN LINE TO STORM DRAIN LINE. PROVIDE S.O.V. AND CHECK VALVE. SEE SHEET P2.2 FOR CONTINUATION. Os 4" STANDPIPE UP. O SIDEWALL SPRINKLER AT ELEVATOR HOISTWAY NOT MORE THAN 2 FT ABOVE THE FLOOR OF THE PIT. 1-1/2* FIRE SPRINKLER LINE TO LANDSCAPE EQUIPMENT ROOM. PROVIDE FIRE SPRINKLERS AS REQUIRED PER NFPA 13 (ORDINARY HAZARD). PROVIDE SPRINKLER GUARDS. O FIRE SPRINKLER LINE ABOVE CEILING (TYPICAL) O GALVANIZED EXPOSED FIRE SPRINKLER LINE (TYPICAL). FIRST FLOOR PLAN - NEW CONSTRUCTION FIRE SPRINKLER SCALE: 1/8" = P -0" 10 RECESSED PENDENT SPRINKLERS INSTALLED ON RETURN BENDS (TYPICAL)PER NFPA 13 SECT. 7.3.2.5(3). 11 PREACTION SYSTEM BRANCH LINES SHALL BE PITCHED AT LEAST 1/2" PER 10 FT. AND MAINS SHALL BE PITCHED AT LEAST 1/4" PER 10 FT. TO DRAIN PER NFPA 13 SECT. 8.16.2.3.2. 12 DOUBLE INTERLOCK PREACTON SYSTEM VALVE CABINET VICTAULIC SERIES 745 FlRELOCK FIRE —PAC PART #SP0207457AB1B11 WITH PNEUMATIC/ELECTRICAL RELEASE. SIZE: 2 . ELECTRICAL CONTRACTOR SHALL CONNECT TAMPER do FLOW SWITCHES TO FIRE ALARM PANEL AND SMOKEMEAT DETECTORS TO PREACTION SYSTEM CABINET ELECTRIC RELEASE PANEL 13 DRAIN LINE TO DISCHARGE OVER FUNNEL TYPE FLOOR DRAIN. PROVIDE 2" AIR GAP. REFER TO PLUMBING DRAWINGS FOR MORE INFORMATION. 14 PREACTION SYSTEM SHALL BE PROVIDED WITH INTERNALLY GALVANIZED STEEL PIPE. NONGALVANIZED FITTINGS SHALL BE PERMITTED. 15 CONTRACTOR SHALL COORDINATE THE EXACT LOCATION OF THE RADIATION SHIELDING PENETRATION WITH THE EQUIPMENT VENDOR /ARCHITECT PRIOR TO INSTALLATION. 18 SECTIONAL VALVE ABOVE CEILING. 0 o c-) N ai C ....................... i G S K P Design Service For The Built Environment 0 Atlanta Birmingham C C i ne, irinati C o J u m bus Dallas Fort 'Lauderdale Knoxville Jackson Jacksonville Louisville Merrtph'is Na,s,h.viIIe Richrnond T: mpa N O R E S H A M 1 T H A N D R A R. T H E R. S 6030 Hollywood Bled'. Suite 210. Hollywood, Florida 33024 954,981.9100 FIRM'S FLORIDA CERT, NO AAP000034fCA380 IB26000797i`LC260003r31 DELTA G CONSULTING A2jF0RT INEERS, INC. .E. 3rd AVE., SUITE 200 LAUDERDALE, FL, 33304 ) 527 -1112 #00009181 PJT. M GR: IfICHAEL HOO PROJECT #: 120717 LLJ < Q ,. L vej C 4, ©� rP;'E. � RIDA LIk!ENSR 'j48100 REVISION No, - Date - Revision Q02/01/13 EAddendum #1 .._...3..._.- Q ......_.. ...... - .... :....................... 03/15/13 City Comments Response I■ KEY NOTES Oi 4" STANDPIPE AND 2" DRAIN RISER UP. O2 SUPERVISED FLOOR CONTROL VALVE. SEE DETAIL ON SHEET FP1.1. O 2 -1/2" HOSE CONNECTION. O CONNECT NEW 2" DRAIN LINE TO STORM DRAIN LINE. PROVIDE S.O.V. AND CHECK VALVE. SEE SHEET P2.2 FOR CONTINUATION. Os 4" STANDPIPE UP. O SIDEWALL SPRINKLER AT ELEVATOR HOISTWAY NOT MORE THAN 2 FT ABOVE THE FLOOR OF THE PIT. 1-1/2* FIRE SPRINKLER LINE TO LANDSCAPE EQUIPMENT ROOM. PROVIDE FIRE SPRINKLERS AS REQUIRED PER NFPA 13 (ORDINARY HAZARD). PROVIDE SPRINKLER GUARDS. O FIRE SPRINKLER LINE ABOVE CEILING (TYPICAL) O GALVANIZED EXPOSED FIRE SPRINKLER LINE (TYPICAL). FIRST FLOOR PLAN - NEW CONSTRUCTION FIRE SPRINKLER SCALE: 1/8" = P -0" 10 RECESSED PENDENT SPRINKLERS INSTALLED ON RETURN BENDS (TYPICAL)PER NFPA 13 SECT. 7.3.2.5(3). 11 PREACTION SYSTEM BRANCH LINES SHALL BE PITCHED AT LEAST 1/2" PER 10 FT. AND MAINS SHALL BE PITCHED AT LEAST 1/4" PER 10 FT. TO DRAIN PER NFPA 13 SECT. 8.16.2.3.2. 12 DOUBLE INTERLOCK PREACTON SYSTEM VALVE CABINET VICTAULIC SERIES 745 FlRELOCK FIRE —PAC PART #SP0207457AB1B11 WITH PNEUMATIC/ELECTRICAL RELEASE. SIZE: 2 . ELECTRICAL CONTRACTOR SHALL CONNECT TAMPER do FLOW SWITCHES TO FIRE ALARM PANEL AND SMOKEMEAT DETECTORS TO PREACTION SYSTEM CABINET ELECTRIC RELEASE PANEL 13 DRAIN LINE TO DISCHARGE OVER FUNNEL TYPE FLOOR DRAIN. PROVIDE 2" AIR GAP. REFER TO PLUMBING DRAWINGS FOR MORE INFORMATION. 14 PREACTION SYSTEM SHALL BE PROVIDED WITH INTERNALLY GALVANIZED STEEL PIPE. NONGALVANIZED FITTINGS SHALL BE PERMITTED. 15 CONTRACTOR SHALL COORDINATE THE EXACT LOCATION OF THE RADIATION SHIELDING PENETRATION WITH THE EQUIPMENT VENDOR /ARCHITECT PRIOR TO INSTALLATION. 18 SECTIONAL VALVE ABOVE CEILING. 0 o c-) N ai C ....................... i G S K P Design Service For The Built Environment 0 Atlanta Birmingham C C i ne, irinati C o J u m bus Dallas Fort 'Lauderdale Knoxville Jackson Jacksonville Louisville Merrtph'is Na,s,h.viIIe Richrnond T: mpa N O R E S H A M 1 T H A N D R A R. T H E R. S 6030 Hollywood Bled'. Suite 210. Hollywood, Florida 33024 954,981.9100 FIRM'S FLORIDA CERT, NO AAP000034fCA380 IB26000797i`LC260003r31 DELTA G CONSULTING A2jF0RT INEERS, INC. .E. 3rd AVE., SUITE 200 LAUDERDALE, FL, 33304 ) 527 -1112 #00009181 PJT. M GR: IfICHAEL HOO PROJECT #: 120717 LLJ < Q ,. L vej C 4, ©� rP;'E. � RIDA LIk!ENSR 'j48100 FIRST FLOOR PLAN NEW CONSTRUCTION FIRE SPRINKLER PLAN FP2ml FILE: PROJECT: 29080.00 DATE: 1 1/29/201 2 REVISION No, - Date - Revision Q02/01/13 EAddendum #1 .._...3..._.- Q ......_.. ...... - .... :....................... 03/15/13 City Comments Response FIRST FLOOR PLAN NEW CONSTRUCTION FIRE SPRINKLER PLAN FP2ml FILE: PROJECT: 29080.00 DATE: 1 1/29/201 2