13-96 (2)-206INNOVATIVE CANCER INSTITUTE
6141 SW 72ND STREET
MIAMI, FL 33176
TO MAIN POWER FEED
OPTIONAL
SINGLE VOLTAGE INPUT
SINGLE VOLTAGE OUTPUT
POWER CONDITIONER
....................................... ...............................
GENERAL CLINAC POWER SPEC;
480V, 80A9 3PH + N & G, 48KVA
FOR COMPLETE POWER SPEC SEE
SECTION 4.2, TrueBeam DDR
(l)-1 /2" C
WARNING LIGHTS
DOOR INTERLOCKS
CE MAIN CIRCUIT
BREAKER PANEL
TO ORDER:
PEA.# 800 -200 --9760
CONDUIT
DER CODE
1) -2## C
(:) -2" C
C)NTROL EQUIPMENT BULL BOX
(30" x 12" x 6 ")
DATA
(1) -111 C
IEC 603099
30A, 250V
(1) -3" C
(2) -2" C
N
(1) -1" C
........... I ........... .... 1 0 ........
(4)-4" C L M, __rl k.:�
TYPICAL Truebeam CONDUIT DIAGRAM
.................................................................................................................................................. ...............................
Provide adequate clearance for typical conduit radius of six times the diameter.
Conduit bends shall not exceed 270 degrees per cable run. Control cable conduit
shall not exceed 75 ° -0* in total length.
IN—ROOM ACCESSORY BOX
(24 "x18 "x6 ")
(1) —r C
(2) -1 1/4" C
(1) -1" C
RELAY JUNCTION BOX
(Varian Supplied)
(1)_1" C
(2) -2$$ C
MODULATOR
CABINET
MODULATOR
PALL BOAC
(18" x 24" x 10 ")
(3) ---4" C
BASE FRAME
PULL BOX
(12" x 24" x 10")
TrueBeam Conduit Schedule
From
To
Qty.
Size ('in)
Base Frame Pull Box
Control Equipment Pull Box
4
4.0
Modulator Pull Box
3
4.0
Relay Junction Box
2
2.0
Modulator Pull Box
Main Circuit Breaker Panel
2
2.0
Relay Junction Box
--Ray Warning Lights
1
0.5
Door Interlocks (24VDC & 120VAC)
1
0.5
IN—ROOM
ACCESSORY BOX
Control Equipment Pull Box
.2
2.0
r_1_j
3.0
In —Room Monitors
1
2.0
Optical Imaging Camera
P g
1
3.0
PAVS Systems
1
1.0
CCTV Cameras
2
1.0
Live View Camera, Microphone hone
2
1.25
Speakers
2
1.0
Main Circuit rcul � t Breaker Panel
Control Equipment Pull Box
1
2.0
IEC 603099 30Ap 250V Receptacle
1
Code
Network (Data) Signal Conduit
1.0
Experimental Access Conduit
1
3.0
SCALE: 1/8" 0 V-0"
REFERENCE NOTES DIMENSIONS: ft — in [rim] PCD ALE NO.
A. THIS DRAWING IS QED ON INFORMATION PROVIDED BY THE CUSTOMER.
T FOR CONSTRUCTION 13 -0017
VERIFY ALL EXISTING CONDITIONS IN THE FIELD. COPYRIGHT (,0 VARIAN MEDICAL SYSTEMS 2011
W DRAB DATE lt�R9 DATE APPROVED Dt�"�
B. THESE DRAWINGS ARE NOT COMPLETE. THE APPROPRIATE CUNAC 00 � JWD 01 NOV12
DESIGNERS DESK REFERENCE (DDR) IS TO BE USED FOR N OR z
REMODELED THERAPY ROOD PLANNING. ALL DRAWINGS AND RAD a! I TrueBeam PROPOSAL FOR Paw_
SHEETS REQUIRED ARE INCWDED IN THAT PACKAGE. U � INNOVATIVE CANCER INSTITUTE
C. INFORMATION SHOWN ON SECTION IS TYPICAL. LAYOUT ONLY. MIAMI, FL CHK
D. VERIFY ALL SHIELDING AND PENS RAMONS WIM THE PHYSICIST OF DATE 1 JWD � 4�JWD �'�"+ i c a I '� �' �� �'� � '�
RECORD. N � i,`-d, e M S
RED' O 1 SIB - - - - -- DR &WING NO. .R_