13-96 (2)-169E Fd O O O O TYPE. SQ.D I-LINE Ill DISTRIBUTION PANEL '1EDP' MAIN BUS: 800 AMP SERVICE: 120/208V. 30, 4W A.I.C: 42.000 MOUNTING: SURFACE MAINS: MLO CKT. NO. NAMEPLATE DESIGNATION KVA AMP PROTECTION WIRE AND CONDUIT POLES FRAME C.B. I ACCELERATOR OBI 50.0 138.9 3 200 200 SEE RISER DIAGRAM. 2 FUTURE ACCELERATOR/OBI 50.0 138.9 3 200 200 SEE RISER DIAGRAM. 3 TRUEBEAM CHILLER 13.0 1 36.0 3 60 45 (4) #8 AND (1) #10 GND IN 1 1/2-C. 4 FUTURE TRUEBEAM CHILLER- 13.0 1 36.0 3 80 45 SEE RISER DIAGRAM. 5 FUTURE CRT SCAN 90.0 250.0 3 400 350 - 6 CHILLER BOOSTER PUMP 4.0 11.0 3 30 20 (4) #10 AND (1) #10 GND IN 11-C. 7 FUTURE CH BOOSTER PUMP- 4.0 11.0 3 30 20 SEE RISER DIAGRAM. 8 TVSS 12 12 3 30 1 30 (4) #10 AND (1) #10 GND IN 3/eC. 9 ISPACE 20 12 U 3 20 25- 8 TOTAL LOAD 1224.0 r ILOCATION: SEE FLOOR PLAN PANEL "CAE" SQUARE D. ITE , G.E. [3 E)OSTING WNEW E0 SCHEDULE �� M I& r_9 _ - I CKT.1 LOAD DESCRIPTION WIRE GRD. ICOND. POLE/ TRIP KVA I A PHASE KVA B PHASE KVA C PHASE POLE/ TRIP COND. GRD. WIRE AAZ-1 LOAD DESCRIPTION CKT CKT. 2 GEF CONTROL COMP RECS 12 12 1/2 3/15 0.411.2 1 2� 20 20 1/2 12 12 12 GARAGE GATE 2 12 12 10 6 0.411.2 CONTROL PRINTER REC 777� 20 1 2 12 12 0.2 10.6 GARAGE GATE 4 20 • 12 12 0.4 10.4 20 1 2 12 12 CONTROL 117 RECS CONTROL 117 RECS FACP DOOR ACCESS VAULT DOOR INTERLOCKS SAGITTAL WALL RECS IN -ROOM MONITORS EXTERIOR RECS 6 7 1 GARAGE RAMP 1ST FL LTS 20 20 20 20 20 20 20 12 12 1 2 20 0.7 1 0.1 12 12 12 12 12 12 12 12 12 12 1 2 12 12 7 CO CONTROLLER a 9 GARAGE 1ST Full LTS 20 12 U 12 20 25- 8 28 197-TAeLc_- 20 - - - _27 _ 29. TVSS SPARE 10 11 GARAGE 2ND Full LTS 3/30 -76- -10 1 2 20 1/2 1/2 3/20 20 _M_ 0.7 11.0 20 1 1*2 12 12 ­ GARAGE FLR LTS 12 73- 7 T' 17 VAV-1-1/1-2/1-3/1-4 1/2 1 2 1 2 1 2 12 12 1/2 3/20 28 36 38 40 42' ALL FEEDER CALCULATIONS ARE BASED ON:NW" CU. 1.0 0 2 1-2 ELEC JAN RECS GARAGE 1ST FUR LTS 14 KVA IS 1.3 10.5 ALL FEEDER CALCULATIONS ARE BASED ON:DW/fflWN CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY -ffT-A-L SUBTUA-L KVA IS 2 _12_ 1-2 TOTAL AMPERES IS 528 Wpr-- GARAGE 2ND FUR LTS 16' SPECIAL OUTLET AUTO SINK 1.3 11.0 3/20 1/2 12 12 F_ TYPE VAV-1-8 18 20 22 21 23 VAV-1-3 MAINS: 12 12 1/2 3/20 1*3 11.0 BRANCH POLES: 42 0BUSWAY BRANCH I BRANCH POLES: 30 1.3 11.0 777777, 7,77, " MOUNTING: MSURFACE 0 FLUSH 1.4 11.0 3/20 1/2 12 1 2 NEUTRAL BUS IS- E3 HALF SIZE W FULL SIZE VAV-1-9 24 26 28 V7 VAV-1-4 1 12 162 1/2 3/20 1.0 11.0 N CB BOLT IN ,­7777 FED FROM: MNORMAL [3 EMERGENCY [3 UNINTERRUPTABLE NOTE 22 20 1.0 1 1.0. 3/2 0 1/2 12 12 20' 20 VAV-1-10 32 34 31 MALE 104 HAND DRYER -WA-LE 12 10 -10 10 10 3/4 20 1.4 1 1.0 1/2 12 73- 103 HAND DRYER STAFF AC REC 22. 10 3 20 1.4 1111.0 12 35 -3-7-0-112 Ill HAND DRYER 1 1-0 10 3 20 • 12 11.0 3/2 01 1/2 12 1 12 VAULT/BRACHY In !SPACE VAV-1-11 38 40 42 _S9_ HAND DRYER 0.410.5 10 1 3 20 1.0 12 199, T1 T STAFF TLT 124 HAND DRYER SPACE 26 1-0 - 1-0 - 3 -10-- 7, 777-777 77 11.0 1 20 ALL FEEDER CALCULATIONS ARE BASED ON:11411l CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY TOTAL KVA T6T)r 28 10.2 CIRCUIT TYPE iFARC FAULT TIME SWITCH CONTROL SHUNT TRIP 0 GROUND FAULT DEDICATED @ ISOLATED GIRD. TOTAL AMPERES IS 94.2 AMPS 12 8 25.6 K LCP FIRST FLOOR CIRCUIT rPE ARC FAULT @ TIE SWATCH CONTROL SHUNT TRIP GROUND FAULT @ DEDICATED @ ISOLATED GIRD. 28 I RMS 122-126 LTS 12 POLE TRIP TYPE RATED VOLTAGE- 120/208 VOLTS 3PHASE TOTAL AMPERES IS 74 AMPS 4 WIRE M EQPT. GRD. ll ISOL GIRD. MAINS: Ill 13 BREAKER: I - - I FEEDER SIZE IS' N CABLE - SEE RISER POLE 0BUSWAY BRANCH POLES: BRANCH BREAKERS- 22 KAIC 12 MOUNTING: N SURFACE C-3 FLUSH I__3 FREE STANDING 110 KEYED DOOR BUS RATING- 200A I BRACING - 22 KAIC 20 NEUTRAL BUS IS. E3 HALF SIZE M FULL SIZE 6 K RATED (1.5) Ill K RATED (10) GROUND BAR: M EQUIPMENT 13 ISOLATED EJ BOTH M FULL SIZE ENCLOSURE MNEMA 1 ll NEMA 3R C3 NEMA 4X CLASS DIV FEED LOCATION: OTOP 0 BOTTOM Il FEED THRU 1/2 PANEL TYPE 0FUSED Ill CB PLUG IN M C8 BOLT IN GROUND BAR: N EQUIPMENT 13 ISOLATED IM BOTH FED FROM: MNORMAL E3 EMERGENCY Ill UNINTERRUPTABLE NOTE. 12 a-AM DIV CORRIDOR LTS 13 FLUSH 34 35 PENDANT LIGHTS CONF. RM ­565-5-77VA-TRNG LOCATION: SEE FLOOR PLAN SPEC: SQUARE D. ITE . G.E. 0 EXISTING M NEW PANEL "ICE" SCHEDULE I CKT. I .3 LOAD DESCRIPTION \1%1 WAITING COMP RECS BRACHY COMP RECS WIRE 2 2 GRD. 12 2 1COND. 1 1/2 1 1/2 POLE'll 20 20 KVA A PHASE 0.8 1 1.2 KVA B PHASE 0.6 1 0.8 KVA C PHASE POLE/ TRIP 2 20 COND. /2 /2 GRD. 12 12- WIRE 12 12 4411V LOAD DESCRIPTION EXAM ROOMS COMP RECS WORK ROOM RECS Al CKT. 2 5 CONTROL COMP RECS 11 2 12 1/2 20 1 2� 20 0.8 10.8 20 1/2 12 12 12 co NIF ROOM RECS 12 12 10 6 7 CONTROL PRINTER REC 777� 12 2 1/2 20 0.2 10.6 1.0 ­.' � ',�` *, : � 20 1/2 12 12 19, CONF ROOM RECS 'R� WvX�`,, 1.7 1.0 8 9 71- _13 _ 75- 17 19 1 CONTROL 117 RECS CONTROL 117 RECS FACP DOOR ACCESS VAULT DOOR INTERLOCKS SAGITTAL WALL RECS IN -ROOM MONITORS 12 10 10 12 12 -12 12 -Ty- 12 12 12 12 _71- 1/2 1/2 1 2 20 20 20 20 20 20 20 0.2 0.8 1...., 11.1. 1 * 0.5 1 1.0 0.8 1.2 1 "1 1.0 11.2 -- �111-_,, 0.1 1.0 1 * 1,11 0.8 11.2 0.1 1 � 20 20 20 20 20 20 1/2 1 2 1 _�2 2 1 2 12 12 12 12 12 12 12 12 12 12 CORRIDOR COMP RECS OFFICE 125 PRINTER OFFICE 125 COMP RECS OFFICE 125 COMP RECS SPACE SPARE SPARE 7 101 12 14 Is' is 20 22 7 SPACE 12 3.3 10.3 20 20 12 12 1.0 25- 8 28 197-TAeLc_- 20 SPARE 3/35 1 _27 _ 29. TVSS 12 10 10 3/4 3/30 1.0 X; 12 12 12 12 0 1/2 1/2 3/20 20 _M_ 1.0 13.3 1 ARE 1 1 26 ­ 1 1.0 z =0 - 20 1/2 1 2 1 2 1 2 12 - 12 12 1'2' 1 12 1 ISPARE ELEVATOR CAB LIGHTS ELEVATOR C AB LIGHTS OFFICE LIGHTS NIGHT UGHT/LCP 28 36 38 40 42' ALL FEEDER CALCULATIONS ARE BASED ON:NW" CU. 1.0 0 2 .20 CIRCUIT TYPE ARC FAULT TIME SWITCH CONTROL ELEC JAN RECS ISPARE 12 KVA IS 30 ALL FEEDER CALCULATIONS ARE BASED ON:DW/fflWN CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY -ffT-A-L SUBTUA-L KVA IS 5. 7.6 5.6 CIRCUIT TYPE ARC FAULT TOE SWITCH CONTROL @ SHUNT TRIP GROUND FAULT DEDICATED @ ISOLATED GRD. TOTAL AMPERES IS 528 Wpr-- 12 12 SPECIAL OUTLET AUTO SINK 20 POLE I TRIP P OLE I TRIP F_ TYPE RATED VOLTAGE- 120/208 VOLTS 3 PHASE MAINS: 4 WIRE 0 EQPT. GRD. E3 ISOL GRD. MAINS: Mll C3 BREAKER: 17 I - I FEEDER SIZE IS.- N CABLE - SEE RISER BRANCH POLES: 42 0BUSWAY BRANCH I BRANCH POLES: 30 BRANCH BREAKERS- 22 KAIC C3 FLUSH MOUNTING: MSURFACE 0 FLUSH Il FREE STANDING Ill KEYED DOOR RATING: 125A BRACING - 22 KAIC M FULL SIZE NEUTRAL BUS IS- E3 HALF SIZE W FULL SIZE E3 K RATED (11.5) C3 K RATED (ZO) GROUND BAR: N EQUIPMENT M ISOLATED Ill BOTH ENCLOSURE MNEMA 1 ENCLOSURE WNEMA 1 0 NEMA 3R C3 NEMA 4X a-AM DIV FEED LOCATION: ATOP [3 BOTTOM [3 FEED THRU PANEL TYPE 0FUSED PANEL TYPE EJFUSED 13 CEI PWG IN N CB BOLT IN FED FROM: FED FROM: MNORMAL [3 EMERGENCY [3 UNINTERRUPTABLE NOTE 22 20 1 /2 12 12 I LOCATION: SEE FLOOR PLAN SPEC: SQUARE D. ITE . G.E. CODOSTING M NEW PANEL 74Ew SCHEDULE CKT-1 1 3 5 7 9 LOAD DESCRIPTION \-�'j 1 ELEV LOBBY RECS BALCONY EXTERIOR RECS EXTERIOR J-BOX OFFICE 407 COMP RECS RECEPTION LIGHTS / LCP WIRE WIRE 12 12 12 12 GIRD. 12 12 12 12 12 COND. 1/2 /2 142 1 2 1 2 POLE TRIP 20 20 20 20 20 KVA A PHASE 0.8 1 1.0 0.8 10.4 1, ­ � .. ;' & KVA B PHASE 1 1 .0 0.8 0.2 1 9 2. I KVA C PHASE 1,e 0.8 1 1.2 POLE/ TRIP 20 =0 20 3/40 1COND. 2 !2 1 GRD. 1-2 7_2 10 WIRE 12 12 12 12 8 Al LOAD DESCRIPTION RECEPT OFFICE RECS CONSULT RECS STORAGE REC TUTS-R-RECS Ill 1 CKT 2 4 6 8 10 12 14 11 RECEPT/ OFFICE COMP RECS 12 11- 12_ 1 2� 20 ,..29:. 20 1.4_F2_.9 13 151 17 19 2 _F3 VAV-4-1/VAV-4-4 VAV-4-2/VAV-4-3 ELEVATOR 1 12 12 12 a 12 12 10 1/2 1/2 3/20 .3/20 3/35 1.7 1 777� 77. 77*7777-7-77-, 12 1.7 1 - 20 . . . . . . . . 1.0 12 20_ /2 SPACE 12 _ 12 19, 1.7 10.7 'R� WvX�`,, 1.7 1.0 1.8 1 0.6 20 20 20 1/2 12 10 10 12 10 10 12 GARAGE 4TH FUR LTS GARAGE 3RD FLR LTS GARAGE 3RD FLR LTS 20 18 20. 22 2 151 2 7 29 . . ... .. 3.3 10.3 20 1.6 1 0.5 20 1 /2 12 12 12 12 7 GARAGE 3RD FUR LTS STAIR LTS 7 24 26 12 3.3 10.3 20 20 12 12 CONF 401 COFFEE MAKER 1 STAIR LTS 8 28 197-TAeLc_- 20 3.3 3.3 3/35 1 10 8 12 ELEVATOR 2 20 30 32 31 33 35 37 1 39 1 41 1 VAV-4--6 LOBBY PERIMETER LTS. CORRIDOR LIGHTS BALCONY LIGHTS 20 13. 3 12 12 12 12 12 12 1 1 1 1/2 1/2 3/20 20 _M_ 1.0 13.3 1 *,,-;.`.-,-,`,,`.,,, 1 1 1.0 13.3 ­ 0.7 0.4 z 1.0 10.4 - 20 1/2 1 2 1 2 1 2 12 - 12 12 1'2' 1 12 1 1 ELEVATOR CAB LIGHTS ELEVATOR C AB LIGHTS OFFICE LIGHTS NIGHT UGHT/LCP 1 2 36 38 40 42' ALL FEEDER CALCULATIONS ARE BASED ON:NW" CU. st TOTAL 10 2 .20 CIRCUIT TYPE ARC FAULT TIME SWITCH CONTROL ELEC JAN RECS NOT MORE THAN 4 CONDUCTORS IN A RACEWAY 12 KVA IS /2 20 qP SHUNT TRIP GROUND FAULT DEDICATED @ ISOLATED GRD. TOTAL AMPERES IS 158.8 AMPS I 20 1/2 12 12 SPECIAL OUTLET AUTO SINK 20 POLE I TRIP TYPE RATED VOLTAGE- 120/208 VOLTS 3 PHASE 2.0 4 WIRE M EQPT. GRD. 13 ISOL GRID. MAINS: EM.LO. 13 Ell : I - I - 17 FEEDER SIZE IS. M CABLE - SEE RISER ISPARE C3BUSWAY BRANCH POLES: 42 BRANCH BREAKERS- 22 KAIC SPACE MOUNTING: WSURFACE C3 FLUSH 0 FREE STANDING Ill KEYED DOOR BUS RATING: 200A I BRACING - 22 KAIC 1/2 NEUTRAL BUS IS- 0 HALF SIZE M FULL SIZE [3 K RATED (1Z) 0 K RATED (ZO) GROUND BAR: N EQUIPMENT 13 ISOLATED 13 BOTH 1 /2 ENCLOSURE MNEMA 1 Ill 3R C3 NEMA 4X MASS DIV FEED LOCATION: ATOP ll BOTTOM Ill FEED THRU 19 PANEL TYPE 0FUSED C-3 CB PWG IN 0 CB BOLT IN 12 FED FROM: MNORMAL 0 EMERGENCY C3 UNINTERRUPTABLE NOTE: 11. 22 20 1 /2 12 12 LOCATION: SEE FLOOR PLAN I__3EX1STING ANEW PANEL 0112" SCHEDULE SPEC:. -=iiRE D, If . G.L '_ 0111fVM0M_01r� r_1 allufAlit-) IN10 CKT. LOAD DESCRIPTION WIRE GRD. COND. POLE/ TRIP KVA A PHASE KVA B PHASE KVA C PHASE POLE/ TRIP COND. GIRD. WIRE LOAD DESCRIPTION CKT 1 LOBBY RECS 2 12 1 2 20 1.0 1 1.0 1 0.1 20 1/2 12 12 12 IT 128 REC 120/24V TRANS. 2 3 EWC 12 12 1 /2 20 . . . . . . . . 1.0 12 20_ /2 12 12 _ 12 5 IBATHROOM Ill 4 6 5 EWC 12 12 12 /2 20 n, "0.6-11 0.6 1 0.6 20 /2 12 12 1 EXAM. 106 TABLE IT 128 REC 7 EXAM ROOMS RECS 7 12 12 1/2 20 0.6 1 0.6 30 20 13.3 9 CONF 401 COFFEE MAKER 2/40 8 1 197-TAeLc_- 20 AHU-5 CU-5 9 CORRIDOR RECS 9 12 12 1 /2 20 3 4 3 0 7. 77 20 13. 3 77777777"',-r 12 12 10 EXAM 108 TABLE 1 10 1 1 CONSULT RECS ­ 2.0 11.0 20 /2 20 - I 0.8 1 0.2 12 _fF_ 12 1 2 12 1 HOTLAB REC 10 2 13 ELEC JAN RECS 1 1.0 12 12 /2 20 0.410.2 k*,---:` I 20 1/2 12 12 SPECIAL OUTLET AUTO SINK 20 14 15 DOCTOR STAFF RECS 12 T_1F_ T� 2.0 /2 20 20 0.6 1 1.0 is 17 SPACE ISPARE 12 16 S REF SPACE 19 17 RECIRCULATION PUMP - 12 12 1/2 20 - I - - 0.2 1 0.8 20 1 /2 12 12 - STAFF DISHWASHER/bISPOSAL 18 19 MOTORIZED DAMPERS 12 12 1 /2 20 0.2 1 1.2 11. 22 20 1 /2 12 12 SPACE STAFF COFFEE MACHINE 20' 20 21 ELEVATOR PIT RECS & LTS 1 12 12 1/2 20 ­ 1.0 10.2 20 1/2 12 1 12 SPACE STAFF AC REC 22. 22' 23 ELEVATOR PIT SUMP PUMP 12 12 1 /2 20 SPACE 1.0 1 0.3 20 1/2 2 12 SPACE LOBBY DO M LTS 24 24 .25 VAULT/BRACHY In 10 12 1� /2 20 0.410.5 SPACE SPACE 26 28 1 12 199, LOBBY PERIMETER LTS 26 26 27 OTOSCOPE DEVICES 12 1/2 1 20 SPACE 0.6 1 0.1 28 20 /2 12 12 8 25.6 K LCP FIRST FLOOR CIRCUIT rPE ARC FAULT @ TIE SWATCH CONTROL SHUNT TRIP GROUND FAULT @ DEDICATED @ ISOLATED GIRD. 28 I RMS 122-126 LTS 12 12 /2 1 20 6.0 CIRCUIT TYPE ARC FAULT @ TIME SWTCH CONTROL 0 SHUNT TRIP GROUND FAULT @ DEDICATED (@) ISOLATED GIRD. TOTAL AMPERES IS 74 AMPS TYPE RATED VOLTAGE- 120/208 VOLTS 3 PHASE 4 WIRE M EQPT. GIRD. 0 ISOL GRID. MS 115 -117 LTS Ill 0BREAKER POLE 31 RMS 119-121,129 & 130 LTS RATED VOLTAGE- 120/208 VOLTS 12 12 1 /2 1 20 0.7 1 0.6 I _ I 20 1 /2 12 12 BRANCH POLES: 30 NIGHT LTS M FULL SIZE 32 33 RMS 110-113 LTS BUS RATING: 12 12 1/2 1 20 W FULL SIZE 0.5 10.6 GROUND BAR: N EQUIPMENT 13 ISOLATED IM BOTH 20 1/2 12 12 a-AM DIV CORRIDOR LTS 13 FLUSH 34 35 PENDANT LIGHTS CONF. RM ­565-5-77VA-TRNG ' 200A 12 12 1 2 20 C3 K RATED (11.5) Ill K RATED (10) GROUND BAR: N EQUIPMENT 0 ISOLATED C3 BOTH 0.6 20 I 12 12 DIV RIMS 103-109 LTS 36 IT AREA DO WhI LTS -T 12 12 11 0 0.4� �u 20 t12 1 2 12 1 12 SF- II/Ell 36 39 COFFEE MAKER 12 12 �32 1 2 2 _11 20 0 =4"",77777 1.1 1 IM 1511_��,�!_ 20 1 2 BRACHY EXAM TABLE REC 1 40' 41 WAITING PERIMETER LTS _30- �r .777. 77! 7-7 7. 1 - I SPACE 1 42 ALL FEEDER CAILCULATI011 ARE BASED MIMAM CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY TOTAL KVA IS 7.8 CIRCUIT TYPE ARC FAULT TRHU LIGHTING CONTROL PANEL SHUNT TRIP GROUND FAULT DEDICATED @ ISOLATED GRD. TOTAL AMPERES IS 65.3 AMP I POLE TRIP I TYPE RATED VOLTAGE- 120/208 VOLTS 3 PHASE 4 WIRE M EQPT. GIRD. 1:3 ISOL GRD. MAINS: WM.LO. 13 BREAKER: I - FEEDER SIZE IS: M CABLE - SEE RISER IZIBUSWAY BRANCH POLES: 42= =RANCH BREAKERS- 22 KAIC MOUNTING: NSURFACE [3 FLUSH 0 FREE STANDING ll KEYED DOOR BUS RATING: 125A I BRACING - 22 KAIC NEUTRAL BUS IS. Ill HALF SIZE N FULL SIZE E3 K RATED (1.5) ll K RATED (10) GROUND BAR: 0 EQUIPMENT E3 ISOLATED C3BOTH ENCLOSURE MNEMA 1 Ill NEMA 311 M NEMA 4X MASS DIV FEED LOCATION: WTOP 0 BOTTOM Il FEED THRU PANEL TYPE EIFUSED C3 CS PLUG IN 0 C8 BOLT IN FED FROM: MNORMAL 1-3 EMERGENCY C3 UNINTERRUPTABLE NOTE: LOCATION: SEE FLOOR PLAN SPEC: SQUARE D, ITE MEXISMIll WIN Ill PANEL "IT" SCHEDULE �� � n­ r" CKT. LOAD DESCRIPTION IWIRE GIRD. COND. POLE/ TRIP KVA A PHASE KVA B PHASE KVA C PHASE POLE/ TRIP COND. GRD. WIRE � LOAD DESCRIPTION CKT 1 TB B REC 12 12 1 2 20 1.0 1 1.0 1 0.1 20 1/2 12 12 12 IT 128 REC 120/24V TRANS. 2 3 TBB REC 12, 12 1 2 20 1/2 1.0 1 1.0 12 20 1 2 7_2 1-2 5 IT 128 REC 4 5 SPECIAL OUTLET 12 10 10 3/4 30 • 7 0 1.0 20 �2 1 2 12 12 20 IT 128 REC 6 7 SPECIAL OUTLET 12 12 20 1/2 30 20 13.3 9 CONF 401 COFFEE MAKER 2/40 8 1 8 20 AHU-5 CU-5 1.2 1 0.1 8 10 9 1 SPECIAL OUTLET 1 1.2 10 10 3 4 3 0 7. 77 20 13. 3 77777777"',-r 11 SPECIAL OUTLET 10 10 1 4 30 . . . . . . . . . . . . . . . ­ 2.0 11.0 20 12 12 - I SPARE 12 _fF_ 12 13 SPECIAL OUTLET 0.6 1.4 10 10 3 4 30 2.0 1 1.0 Ill 413 HAND DRYER 20 14 15 - I -SPARE RAIN BIRD CONTROLLER 14 15 SPECIAL OUTLET 1.0 1 1.7 20 3/20 3 4 30 12 2.0 1 1.0 16 is 20 20 SPACE is 17 SPACE ISPARE - 16 17 SPACE 19 BALCONY LIGHTS - - 1/2 20 0.3 1 - I - - 21 SPARE SPACE - SPACE - 18 19 SPACE SPACE PACE SPACE 22 23 SPARE SPACE SPACE 20' 21 SPACE 1.0 1 SPACE 24 25 1 SP SPACE 22. _F5_ SPACE -3-/4- SPACE SPACE 241 29' 27 1 SPARE SPACE 24 27 TVSS 10 10 3 30 : - SPACE SPACE 26 28 29 1 SPACE SPACE 26 SPACE SPACE 28 29 . . . . . . . . . . . . . . . . . . . . . .... ALL FEEDER CALCULATIONS ARE BASED O"MAM CU- NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SUBTOTAL _ffT_A_L KVA IS 8 25.6 K CIRCUIT rPE ARC FAULT @ TIE SWATCH CONTROL SHUNT TRIP GROUND FAULT @ DEDICATED @ ISOLATED GIRD. TOTAL AMPERES IS 71.1 AMPS I ISPACE 30 ALL FEEDER CAUMATIONS ARE BASED Olt NIN" CI). NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SUE OTALI To TOTAL KVA IS 10.3 6.0 CIRCUIT TYPE ARC FAULT @ TIME SWTCH CONTROL 0 SHUNT TRIP GROUND FAULT @ DEDICATED (@) ISOLATED GIRD. TOTAL AMPERES IS 74 AMPS TYPE RATED VOLTAGE- 120/208 VOLTS 3 PHASE 4 WIRE M EQPT. GIRD. 0 ISOL GRID. MAINS: Ill 0BREAKER POLE I TYPE RATED VOLTAGE- 120/208 VOLTS 3 PHASE 0BUSWAY 4 WIRE M EQPT. GIRD. D ISOL GIRD. MAINS: Mll C3 BREAKER : I _ I EI FREE STANDING Q KEYED DOOR FEEDER SIZE IS. M CABLE - SEE RISER 125A 0BUSWAY BRANCH POLES: 30 1BRANCH BREAKERS- 22 KAIC M FULL SIZE MOUNTING: III SURFACE 0 FLUSH 0 FREE STANDING C3 KEYED DOOR BUS RATING: 125A I BRACING - 22 KAIC CLASS( DIV NEUTRAL BUS IS- C-3 HALF S! ' ZE W FULL SIZE C3 K RATED (1.5) C-3 K RATED (ZO) GROUND BAR: N EQUIPMENT 13 ISOLATED IM BOTH W CB BOLT IN ENCLOSURE MNEMA 1 Ill NEMA 3R [3 NEMA 4X a-AM DIV FEED LOCATION: WTOP E3 BOTTOM Ill FEED THRU 13 FLUSH PANEL TYPE 0FUSED C3 CO PLUG IN N CB BOLT IN ' 200A FED FROM: MNMAAL I__3 EMERGENCY EJ UNINTERRUPTABLE NOTE- I 0 FULL SIZE C3 K RATED (11.5) Ill K RATED (10) GROUND BAR: N EQUIPMENT 0 ISOLATED C3 BOTH ENCLOSURE: - MNEMA 1 I ILOCATION: SEE FLOOR PLAN SPEC. SQUARE D. ITE , G.E. Ill rXISTINQ =NEW PANEL w4Aw SCHEDULE ­ I CKT. LOAD DESCRIPTION )' \ i WIRE GIRD. COND. POLE/ TRIP KVA A PHASE KVA B PHASE KVA C PHASE POLE / TRIP COND. GRD. WIRE AX LOAD DESCRIPTION CKT. 1 CORRIDOR RECS 12 12 11 20 0.6 1 1.6 1 0.1 20 1/2 1/2 12 12 CONF 401 RECS 120/24V TRANS. 2 3 S 411-414 LTS 8.8 1 0.2 _Y2 - 20 1/2 0.7 12 POWER SUPPLIES 12 5 CONE 401 PROJECTOR 4 5 CU-6/AHU-6A.8B 12 12 12 _T21T2_ 2 17_ - 2720 6 7 1.2 1 1.0 20 1/2 12 12 20 401 MOTORIZED SCREEN 6 7 1.2 11.0 12 12 20 1/2 12 12 9 CONF 401 COFFEE MAKER 8 9 9 M CU-7/AHU-7A,7B - 20 12 1.2 1 0.1 1, ; I" 2/20 . . . . . . . . . . . 1 1.2 12 20 3/4 10 10 1 BUILDING SIGNAGE 101 10 3 4 1.2 . . . . . . . . . Z,,'<, 1.2 0. 1 20 1 2 DRYE1.2 R 12 12 13 ROOFTOP RECEPTACLES 12 12 _fF_ 12 1 2 20 0.6 1.4 :? 20 0.6 1 1.0 _, - - .,o 1'31`.,-11�, 10 10 Ill 413 HAND DRYER 14 15 SHELL SPACE LTS 415 & 41-73 15 RAIN BIRD CONTROLLER 20 12 1.0 1 1.7 20 3/20 1/2 12 12 VAV -4-5 16 is 20 17 SPACE is 17 SPACE - 151.6 1 1.7 19 BALCONY LIGHTS 12 12 1/2 20 0.3 1 SPACE 21 SPARE SPACE - - - 20 1.0 1 SPACE PACE SPACE 22 23 SPARE SPACE 20 1.0 1 SPACE 24 25 1 SP 20 1.0 SPACE SPACE 241 29' 27 1 SPARE 20 1.0 - SPACE SPACE 26 28 29 1 SPACE SPACE SPACE 28 30 ALL FEEDER CALCULATIONS ARE BASED O"MAM CU- NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SUBTOTAL _ffT_A_L KVA IS 8 25.6 K CIRCUIT rPE ARC FAULT @ TIE SWATCH CONTROL SHUNT TRIP GROUND FAULT @ DEDICATED @ ISOLATED GIRD. TOTAL AMPERES IS 71.1 AMPS I I POLE TRIP TYPE RATED VOLTAGE- 120/208 VOLTS 3 PHASE 4 WIRE M EQPT. GIRD. 0 ISOL GRID. MAINS: Ill 0BREAKER NOT MORE THAN 4 CONDUCTORS IN A RACEWAY FEEDER SIZE IS. M CAM - SEE RISER 0BUSWAY BRANCH POLES: 30 _BRANCH BREAKERS- 22 KAIC MOUNTING: M SURFACE C3 FLUSH EI FREE STANDING Q KEYED DOOR BUS RATING: 125A I BRACING - 22 KAIC NEUTRAL BUS IS- - E3 HALF SIZE M FULL SIZE E3 K RATED (1.5) Ill K RATED (ZO) GROUND BAR: N EQUIPMENT E:3 ISOLATED Ill BOTH 3 PHASE ENCLOSURE M NEMA 1 0 NEMA 311 IM NEMA 4X CLASS( DIV LOCATION: WTOP C3 BOTTOM EZI FEED THRU PANEL TYPE OFUSED C3 CB PWG IN W CB BOLT IN C38USWAY -FEED FED FROM: MNORMAL 0 EMERGENCY C3 UNINTERRUPTABLE' NOTE- MOUNTING% MSURFACE 13 FLUSH 13 FREE STANDING M KEYED DOOR BUS RATING: ' 200A LOCATION: SEE FLOOR PLAN SPEC: D, ITE , GF_ IlNQ ANEW PANEL 0SL7 SCHEDULE __ ­.- CKT. LOAD DESCRIPTION WIRE GRD. COND. JPOLE / TRIP KVA A PHASE KVA B PHASE KVA C PHASE Poll TRIP COND. GIRD. WIRE 4V LOAD DESCRIPTION CKT. I ' PANEL '4A* 3 8 1 1/4 3/100 9.3 1 0.1 �t, 20 1/2 2 12 120/24V TRANS. 2 3 8.8 1 0.2 1 011, :, 26- 1/2 12 12 POWER SUPPLIES 4 5 7.5 10.9 20 1/2 12 12 SITE LIGHTING 6 7 WATER FEATURE 12 1/2 20 1.2 10.6 20 12 12 LANDSCAPE LIGHTS 8 9 SIGNAGE 10 10 3 20 1.2 1 0.1 1, ; I" 20 -1/2 ill 12 12 1 EXT. ENTRY LTS 101 11 SIGNAGE 10 10 3 4 20 . . . . . . . . . Z,,'<, 1.2 0. 1 20 1 2 12 12 IRRIGATION CONTROL VALVE TI VE 12 13 BLDG. EXTERIOR LIGHTS 10 10 3 20 0.6 1 1.0 _, - - .,o 1'31`.,-11�, 20 - - 15 RAIN BIRD CONTROLLER 12 12 1 2 20 0.1 1 1.0 20 ISPARE is 17 SPACE SPACE 18 _rl SPACE PACE SPACE 20 SPACE SPACE 22 23_ SPACE SPACE 241 25 SPACE SPACE 26 27 SPACE SPACE 28 29 SPACE I ISPACE 30 ALL FEEDER CALCULATIONS ARE BASED ""I'M" 'U' SUBTOTAL _fflTAL KVA IS CIRCUIT TYPE ARC FAULT TIME CLOCK & UMMG CONTACTOR NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SHUNT TRIP GROUND FAULT DEDICATED @ ISOLATED GRD. TOTAL AMPERES IS 104 AMPS POLE TRIP TYPE RATED VOLTAGE- 120/208 VOLTS 3 PHASE 4 WIRE M EQPT. GIRD. E3 ISOL GIRD. MAINS: Ill C3 BREAKER : I - FEEDER SIZE IS. MCABLE - SEE RISER C38USWAY BRANCH POLES. 30 BRANCH BREAKERS- 22 KAIC MOUNTING% MSURFACE 13 FLUSH 13 FREE STANDING M KEYED DOOR BUS RATING: ' 200A I BRACING - 22 KAIC NEUTRAL BUS 1& 110 HALF SIZE 0 FULL SIZE C3 K RATED (11.5) Ill K RATED (10) GROUND BAR: N EQUIPMENT 0 ISOLATED C3 BOTH ENCLOSURE: - MNEMA 1 C3 NEMA 3111 C3 NEMA 4X CLASS( DIV FEED LOCATION: ATOP Ill BOTTOM E3 FEED THRU PANEL TYPE 0FUSED C3 CS PWG IN N CB BOLT IN FED FROM: NNORMAL C3 EMERGENCY C3 UNINTERRUPTABLE NOTE- AW i &.P � ---------- Design Services For The BUilt Environment ■ Atlanta Birmingham Cincinnati Columbus Dallas Fort Lauderdale Knoxville Jackson Jacksonville Louisville Memphis N a s h v i l l e Richmond Tampa N G R E S H A M S M I T H A N D P A R T N E R S 6030 Hollywood Blvd. Suite 210 Hollywood, Florida 33024 9 54.9 81.9100 FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381 A56MIDELTA G CONSULTING ENGINEERS. INC. 707 N.E. 3rd AVE., SUITE 200 FORT 1AUDEMUZ, FL 33304 954) M-1112 CAODOOMM PTT. XGR. iaCELAM HOO PROJECT 111: 120717 go INN, tw 0 a I_ CY) Ljj MINN < "or -0 a ert U) Fr 0 0 C: IN- C/) RCS 0_ X Lij 0 U) S A N i tj Cr LIJ Of .,0 044 FDO 46100 L ) V.611 e N REVISION I No. - Date - Revision I ELECTRICAL FANELS E4.2 FILE: PROJECT: 29080.00 DATE: 11/29/2012