13-96 (2)-165La k� F �3 Fj I i� i•I ff� is e: 4; �y i7 r i TYPE: SQ.D I -LINE HCP MSTMBUTI©N PANEL 'EDP' MAIN BUS: 1200 AMP SERVICE: 120/208V, 30, 4W A.I.C: 42,000 MOUNTING: SURFACE MAINS: MLO CKT. NO. NAMEPLATE DESIGNATION KVA AMP PROTECTION WIRE AND CONDUIT POLES IFRAME C.B. 1 AHU -1 (6.3) (17.5) 3 30 20 (3) #10 AND (1) #10 GND IN 3/4 "C. 2 CU -1 23.0 64.0 3 100 100 (3) #3 AND (1) #8 GND IN 1 1/4 "C. 3 EWH -1 4.5 21.6 2 30 30 (3) #10 AND (1) #10 GND IN 3/4 "C. 4 VAV -1 -8 /VAV -1 -9 4.0 11.1 3 30 20 (4) #12 AND (1) #12 GND IN 3/4" 5 VAV -1 -7 5.0 13.9 3 30 20 (4) #12 AND (1) #12 GND IN 3/4" 6 VAV -1 -5 4.0 11.1 3 30 20 (4) #12 AND (1) #12 GND IN 3/4" 7 VAV- 1- 1/1- 2/1 -3/1 -4 5.0 13.9 3 30 20 (4) #12 AND (1) #12 GND IN 3/4" 8 VAV -1 -6 3.0 8.3 3 30 20 (4) #12 AND (1) #12 GND IN 3/4" 9 VAV -1 -10 3.0 8.3 3 30 20 (4) #12 AND (1) #12 GND IN 3/4" 10 AHU- 3 /CU -3 4.3 20.7 2 60 40 (3) #8 AND (1) #10 GND IN 1 "C. 11 AHU- 4A /CU -4B 3.8 18.2 2 60 35 (3) #8 AND (1) #10 GND IN 1 "C. 12 AHU- 4B /CU -4B 3.8 18.2 2 60 35 (3) #8 AND (1) #10 GND IN 1 "C. 13 VAV -1 -13 3.0 8.3 3 30 20 (4) #12 AND (1) #12 GND IN 3/4" 14 VAV -1 -11 3.0 8.3 3 30 20 (4) #12 AND (1) #12 GND IN 3/4" 15 VAV -1 -12 3.0 8.3 3 30 20 (4) #12 AND (1) #12 GND IN 3/4" 16 VAV -1 -14 5.0 13.9 3 30 20 (4) #12 AND (1) #12 GND IN 3/4" 17 PANEL '1E' 28.5 79.2 3 200 125 SEE RISER DIAGRAM. 18 PANEL '10E' 19.0 52.8 3 100 100 SEE RISER DIAGRAM. 19 PANEL 'IT' 26.6 73.8 3 100 125 SEE RISER DIAGRAM. 20 TVSS - - 3 30 30 (4) #10 AND (1) #10 GND IN 3/4 "C. 21 ACCELERATOR /OBI 50.0 138.9 3 200 200 SEE RISER DIAGRAM. 22 FUTURE ACCELERATOR /OBI 50.0 138.9 3 200 200 SEE RISER DIAGRAM. 23 TRUEBEAM CHILLER 13.0 36.0 3 60 45 (4) #8 AND (1) #10 GND IN 1 1/2 "C. 24 FUTURE TRUEBEAM CHILLER 13.0 36.0 1 3 60 45 1 SEE RISER DIAGRAM. 25 FUTURE CRT SCAN 90.0 250.0 3 400 350 - 26 CHILLER BOOSTER PUMP 4.0 11.0 3 30 20 (4) #10 AND (1) #10 GND IN 1 "C. 27 FUTURE CH BOOSTER PUMP 4.0 11.0 3 30 20 SEE RISER DIAGRAM. TOTAL LOAD 371.5 1031.9 LOCATION: SEE FLOOR PLAN w w SPEC: SQUARED, ITE , G.E. ❑EXISTING MNEW PANES GE SCHEDULE =rnDDCD DI IC "Al II+11A11111 DI IC CKT. LOAD DESCRIPTION F WIRE GRID. COND. __172__,3_/1_5 POLE/ TRIP KVA A PHASE KVA B PHASE KVA C PHASE POLE/ TRIP COND. GIRD. WIRE A/ LOAD DESCRIPTION F LOAD DESCRIPTION CKT 1 GEF WAITING COMP RECS 12 12 12 0.4 1.2 20 0.8 1.2 20 1 2 12 12 12 GARAGE GATE 3 2 3 2 0.4 1.2 BRACHY COMP RECS 20 1 2 12 12 1/2 GARAGE GATE 20 4 5 20 1/2 0.4 0.4 20 1 2 12 12 4 EXTERIOR RECS CONTROL COMP RECS 6 7 GARAGE RAMP 1ST FL LTS 12 12 12 1/2 20 0.7 1 0.1 20 1/2 20 1 2 12 12 12 CO CONTROLLER 7 8 9 GARAGE 1ST FUR LTS 12 1 12 1 12 1/2 20 12 0.6 1 - 20 1 20 - I - - ICONF ROOM RECS 12 SPARE 9 10 11 GARAGE 2ND FUR LTS 12 10 10 1/2 20 0.8 1 1.2 RTU -2 0.7 1 1.0 20 1/2 1 12 12 ICORRIDOR COMP RECS GARAGE 2ND FUR LTS 10 12 13 LOBBY RECS 1.4 3.3 12 12 142 20 0.8 1 0.6 - 0.8 1 1.2 20 1/2 1 12 12 15 GARAGE 1ST FUR LTS 13 14 15 EWC - 12 12 1/2 20 20 0.6 1 0.5 - 20 1/2 12 12 1 GARAGE 2ND FUR LTS OFFICE 125 COMP RECS 16 17 EWC DOOR ACCESS 12 12 1/2 20 1/2 20 0.6 1.0 20 1/2 12 12 1 TELECOM RECS 17 18 19 DOOR ACCESS 17 12 12 1/2 20 0.1 1 1.0 1 20 20 1/2 12 12 - TELECOM RECS - 20 21 ELEVATOR PIT RECS & LTS 18 12 12 1/2 20 12 1.0 1 0.4 1 2 20 142 12 12 20 _EL EC GARAGE RECS - 22 23 ELEVATOR PIT SUMP PUMP - 12 12 1/2 20 - 12 1.0 1 0.1 20 1/2 12 12 25 1 FACP - 24 25 AUTOMATIC TOILETS SPARE 12 12 1/2 20 0.2 1 0.1 - - - 20 1/2 12 12 27 MOTORIZED DAMPER 20 26 27 HAND FREE SINK - 12 12 1/2 20 TVSS 0.1 1 0.3 - 20 1/2 12 12 - 1.0 C LOBBY DOWN LIGHTS 20 28 29 BATHROOM RECS ISPARE 12 12 1/2 20 - ---T1.0 0.6 1 0.5 20 1 2 - - SPACE C LOBBY PERIMETER LIGHTS 28 30 31 MALE 104 HAND DRYER 20 10 10 3/4 20 1.4 0.2 BRANH BREAKERS= 14 KAIC 30 20 1 2 5.8 7.6 19.0 KVA 5.6 CIRCUIT TYPE : ® ARC FAULT Q TIME SWATCH CONTROL ® SHUNT TRIP ® GROUND FAULT ® DEDICATED © ISOLATED GIRD. TOTAL AMPERES IS 52.8 AMPS BATHROOM LIGHTS - 32 33 MALE 103 HAND DRYER 0.4 - 10 10 3/4 20 RATED VOLTAGE= 120 /208 VOLTS 3 PHASE 1.4 0.2 MAINS: 20 1/2 - FEEDER SIZE IS: 0CABLE = FEEDER SIZE IS: NCABLE= SEE RISER NIGHT LIGHTS ❑BUSWAY 34 35 SPACE MOUNTING: 0 SURFACE - - - - 113RACING = 22 KAIC NEUTRAL BUS IS: ❑ HALF SIZE 1.0 20 - GROUND BAR: M EQUIPMENT ❑ ISOLATED ❑ BOTH M21 ENCLOSURE MNEMA 1 SPARE CLASS( ) DIV ( ) 36 37 SPACE ❑ CB PLUG IN - - - - - 10 38 39 20 - - - - SPARE --1 1.0 1 38 39 SPACE 12 - - - - 40 - 1.0 BALCONY LIGHTS 20 - 12 1/2 20 SPARE 0.4 - 40 41 SPACE - - - - - ALL FEEDER CALCULATIONS ARE BASED ON:THHN/THWN CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SUBTOTAL TOTAL KVA IS - - - - TOTAL AMPERES IS 71.3 AMPS ❑BUSWAY SPACE 1 42 ALL FEEDER CALCULATIONS ARE BASED ON- THHN/THWN CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SUBTOTAL TOTAL KVA IS 8.6 8.6 4. _KVA 7.3 CIRCUIT TYPE : Q ARC FAULT Q TIME SWITCH CONTROL SHUNT TRIP ® GROUND FAULT ® DEDICATED © ISOLATED GRID. TOTAL AMPERES IS 68.0 AMPS MAINS: MM.L.O. ❑ BREAKER : I - I - GROUND BAR: N EQUIPIENT ❑ ISOLATED ❑ BOTH FEEDER SIZE IS: 0CABLE= SEE RISER ENCLOSURE: MNEMA 1 ❑BUSWAY BRANCH POLES: 42 BRANCH BREAKERS= 10 KAIC POLE TRIP TYPE RATED VOLTAGE= 120 /208 VOLTS 3 PHASE 4 WARE M EQPT. GRID. ❑ ISOL. GRID. MAINS: MM.L.O. E3 BREAKER : - - ❑ K RATED (1.5) ❑ K RATED (2.0) FEEDER SIZE IS: N CABLE = SEE RISER ENCLOSURE : MNEMA 1 ❑ BUSWAY BRANCH POLES: 42 BRANCH BREAKERS- 14 KAIC FEED LOCATION: 0 TOP p BOTTOM ❑ FEED THRU MOUNTING: N SURFACE ❑ FLUSH ❑ CB PLUG IN ❑ FREE STANDING ❑ KEYED DOOR BUS RATING: 100A I BRACING = 1 4 KAIC NEUTRAL BUS IS: ❑ HALF SIZE 0 FULL SIZE ❑ K RATED (1.5) ❑ K RATED (2.0) GROUND BAR: =EQUIPMENT ❑ ISOLATED ❑ BOTH ENCLOSURE : O NEMA 1 ❑ NEMA 3R ❑ NEMA 4X CLASS( ) DIV ( ) FEED LOCATION: 0 TOP p BOTTOM ❑ FEED THRU PANEL TYPE : ❑FUSED ❑ CB PLUG IN M CB BOLT IN FED FROM: ONORMAL ❑ EMERGENCY ❑ UNINTERRUPTA13LE NOTE: ❑ EXSTING SEE FLOOR WAN PANEL "ICE" SCHEDULE SPEC: A00170 011C r_1 r1 A I 1 I.lI.II I,. D1 IC CKT. LOAD DESCRIPTION F WIRE GIRD. COND. POLE/ TRIP KVA A PHASE KVA B PHASE KVA C PHASE POLE/ TRIP COND. GIRD. WIRE F LOAD DESCRIPTION CKT CKT 1 WAITING COMP RECS 12 12 12 12 1/2 20 0.8 1.2 20 1/2 20 1/2 12 12 3 IEXAM ROOMS COMP RECS 3 2 3 BRACHY COMP RECS 12 1/2 12 12 1/2 20 20 0.6 1 0.8 12 20 1/2 12 12 4 IWORK ROOM RECS EXTERIOR J -BOX 4 5 CONTROL COMP RECS 1 2 20 12 12 1/2 20 12 12 0.8 1 0.8 20 1/2 12 12 7 ICONF ROOM RECS 12 6 7 PRINTER HMI SCREEN REC 20 0.6 0.4 12 12 1/2 20 0.2 1 0.6 12 7 20 1/2 12 12 RECEPTION LIGHTS ICONF ROOM RECS 12 8 9 CONTROL 117 RECS 1 0.2 3.3 12 12 1/2 20 8 0.8 1 1.2 RTU -2 20 1 2 12 12 SPACE ICORRIDOR COMP RECS 12 10 11 CONTROL 117 RECS - 1.4 3.3 12 1 12 1/2 20 - - 0.8 1 1.2 20 1 2 12 12 15 1 OFFICE 125 PRINTER 13 12 13 WORK ROOM 120 RECS - 10 12 12 1/2 20 0.2 1 0.8 - - 20 1Z2 12 12 SPACE OFFICE 125 COMP RECS - 14 15 DOOR ACCESS 10 3 4 12 12 1/2 20 - 1.0 1 1.2 SPARE 20 1 2 12 12 17 OFFICE 125 COMP RECS - 16 17 VAULT DOOR INTERLOCKS - MOUNTING: M SURFACE ❑ FLUSH 12 12 1/2 20 - SPARE 0.1 1 - - - - - CLASS( ) DIV ( ) SPACE 1 12 18 19 SAGITTAL WALL RECS FED FROM: 20 12 12 1 2 20 0.6 1 1.0 - 22 20 - - - - SPARE - 20 21 IN -ROOM MONITORS 20 - 12 12 1 2 20 - 0.1 1.0 25 1 20 - - - - SPARE - 1.0 22 23 SPACE - - - - - - - 26 27 - 1 1.0 20 - - - - SPARE - 1.0 24 25 TVSS SPACE - 10 10 3/4 3/30 - 1.0 SPACE 27 N 20 - - - ISPARE - - - 26 27 29 - ---T1.0 20 - - - SPACE SPARE - 28 - - - 1.0 20 - - - - SPARE BRANH BREAKERS= 14 KAIC 30 ALL FEEDER CALCULATIONS ARE BASED ON:THHN/THWN CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY TOT AL KVA IS SUBTOTAL 5.8 7.6 19.0 KVA 5.6 CIRCUIT TYPE : ® ARC FAULT Q TIME SWATCH CONTROL ® SHUNT TRIP ® GROUND FAULT ® DEDICATED © ISOLATED GIRD. TOTAL AMPERES IS 52.8 AMPS - - - ❑ K RATED (1.5) ❑ K RATED (2.0) - - 0.4 - - POLE I TRIP TYPE RATED VOLTAGE= 120 /208 VOLTS 3 PHASE 4 WIRE 0 EQPT. GIRD. ❑ ISOL. GIRD. MAINS: MM.L.O. ❑ BREAKER: I - - FEEDER SIZE IS: 0CABLE = FEEDER SIZE IS: NCABLE= SEE RISER - ❑BUSWAY BRANCH POLES: 30 BRANCH BREAKERS= 22 KAIC - - MOUNTING: 0 SURFACE ❑ FLUSH ❑ FREE STANDING ❑ KEYED DOOR BUS RATING: 125A 113RACING = 22 KAIC NEUTRAL BUS IS: ❑ HALF SIZE NEUTRAL BUS IS: ❑ HALF SIZE M FULL SIZE ❑ K RATED (1.5) ❑ K RATED (2.0) GROUND BAR: M EQUIPMENT ❑ ISOLATED ❑ BOTH - ENCLOSURE MNEMA 1 ❑ NEMA 3R ❑ NEMA 4X CLASS( ) DIV ( ) FEED LOCATION: STOP p BOTTOM 13 FEED THRU PANEL TYPE : ❑FUSED PANEL TYPE : =FUSED ❑ CB PLUG IN M CB BOLT IN - FED FROM: NNORMAL ❑ EMERGENCY ❑ UNINTERRUPTABLE NOTE: 38 39 SPACE 0.3 3.0 - - LOCATION: SEE FLOOR PLAN PANEL np2� w��w �a��2 ®��2 SPEC: SQUARE D, ITE , G.E. DEXISTING M NFW ANE SCHEDULE E �„ ,--, CKT. LOAD DESCRIPTION F WIRE GIRD. COND. POLE/ TRIP KVA A PHASE KVA B PHASE KVA C PHASE POLE/ TRIP COND. GIRD. WIRE Al LOAD DESCRIPTION CKT CKT 1 ELEV LOBBY RECS 8 12 12 1/2 20 0.8 1 1.0 B PHASE 3/35 20 1/2 12 12 ELEVATOR 2 1 RECEPT OFFICE RECS 3 2 3 BALCONY EXTERIOR RECS 4 12 12 1/2 20 6 1.0 0.8 SHUNT TRIP 20 - 12 12 - CONSULT RECS 3 4 5 EXTERIOR J -BOX - 12 12 1 2 20 9 ELEVATOR CAB LIGHTS 0.8 12 20 12 12 12 4 STORAGE REC SPECIAL OUTLET 6 7 OFFICE 407 COMP RECS 12 12 12 1 2 20 0.6 0.4 1/2 - 20 Et 12 12 7 TLT HSK RECS - 8 9 RECEPTION LIGHTS 30 12 12 1 2 20 1 0.2 3.3 - 3/35 1 10 8 SPECIAL OUTLET RTU -2 - 10 11 RECEPT OFFICE COMP RECS SPACE 12 12 1 2 20 - - 1.4 3.3 12 14 13 SPACE 10 - - - - - 3.3 SPACE 16 15 SPACE 13 - - - - 10 - - - - - - - - - SPACE 18 16 17 SPACE 6.6 - - PANEL 'GE 10 10 3 4 __-__F1.0 20 - - - RATED VOLTAGE= 120 /208 VOLTS 3 PHASE SPARE MAINS: 18 19 SPACE 17 - - - - - 1.0 - MOUNTING: M SURFACE ❑ FLUSH 20 - - - - SPARE ❑ K RATED (1.5) ❑ K RATED (2.0) 20 21 SPACE ❑ NEMA 4X CLASS( ) DIV ( ) FEED LOCATION: W TOP ❑ BOTTOM ❑ FEED THRU 1 12 PANEL TYPE : ❑FUSED ❑ CB PLUG IN ■ CB BOLT IN I - 1.0 FED FROM: 20 - - - - SPARE - 22 23 SPACE 21 - - - - - - - 1.0 20 - - - - SPARE - 24 25 1 SPACE 23 - - - - - 1.0 1 2.2 1.0 20 - - - - ISPARE - - 26 27 SPACE 25 - - - - 10 - 1.0 3/30- 20 RTU -3 SPACE - ISPARE - - 1 28 29 SPACE 27 N - - - - - - - - - - - - 29 SPACE 4TH FLR LHT POLES INVERTER 30 31 SPACE - - - - - - - ALL FEEDER CALCULATIONS ARE BASED ON:THHN /THWN CU. SUBTOTAL TOTAL KVA - - - - BRANH BREAKERS= 14 KAIC SPACE IS 32 33 SPACE TOTAL AMPERES IS 74 AMPS - - - - ❑ K RATED (1.5) ❑ K RATED (2.0) - - 0.4 - - - - - 4 WIRE M EQPT. GIRD. ❑ ISOL. GIRD. SPACE ■M.L.O. ❑ BREAKER : 34 35 SPACE FEEDER SIZE IS: 0CABLE = - - - - BRANCH BREAKERS= 22 KAIC ' ' - - - - - - BRACING = 22 KAIC SPACE NEUTRAL BUS IS: ❑ HALF SIZE 36 37 SPACE - - - - - - 0.5 3.0 PANEL TYPE : ❑FUSED - - - - WNORMAL ❑ EMERGENCY ❑ UNINTERRUPTABLE SPACE 1 38 39 SPACE 0.3 3.0 - - - - 21.6 --1 1.0 1 CIRCUIT TYPE 20 12 1 OFFICE LIGHTS 61.6 KVA 40 41 BALCONY LIGHTS 12 12 1/2 20 0.4 - - _!Z2 - - - RATED VOLTAGE= 120/208 VOLTS SPACE 4 WIRE N EQPT. GIRD. ❑ ISOL. GIRD. 42 ALL FEEDER CALCULATIONS ARE BASED ON:THHN/THWN CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SUBTOTAL TOTAL KVA IS 8.3 8.3 25.7 KVA 9.1 CIRCUIT TYPE : © ARC FAULT Q 11ME SWITCH CONTROL ® SHUNT TRIP ® GROUND FAULT ® DEDICATED (@) ISOLATED GIRD. TOTAL AMPERES IS 71.3 AMPS ❑BUSWAY BRANCH POLES: 42 ANCH BREAKERS= 14 KAIC MOUNTING: 0 SURFACE 1:1 FLUSH POLE TRIP TYPE RATED VOLTAGE= 120 /208 VOLTS 3 PHASE 4 WIRE 0 EQPT. GIRD. ❑ ISOL. GIRD. MAINS: MM.L.O. ❑ BREAKER : I - I - GROUND BAR: N EQUIPIENT ❑ ISOLATED ❑ BOTH FEEDER SIZE IS: 0CABLE= SEE RISER ENCLOSURE: MNEMA 1 ❑BUSWAY BRANCH POLES: 42 BRANCH BREAKERS= 10 KAIC ) DIV ( ) MOUNTING: 0 SURFACE ❑ FLUSH ❑ FREE STANDING ❑ KEYED DOOR BUS RATING: 100A BRACING = 1 O KAIC NEUTRAL BUS IS: ❑ HALF SIZE M FULL SIZE ❑ K RATED (1.5) ❑ K RATED (2.0) GROUND BAR: N EQUIPMENT ❑ ISOLATED ❑ BOTH ENCLOSURE : MNEMA 1 ❑ NEMA 3R ❑ NEMA 4X CLASS( ) DIV ( ) FEED LOCATION: 0 TOP p BOTTOM ❑ FEED THRU PANEL TYPE : ❑FUSED ❑ CB PLUG IN M CB BOLT IN FED FROM: MNORMAL ❑ EMERGENCY ❑ UNINTERRUPTABLE NOTE: LOCATION: SEE FLOOR PLAN SPEC: SQUARE D, ITE , G.E. OEXISTING NFW ®AN EL 41A SCME®ULE -„ CKT. LOAD DESCRIPTION a WARE GRID. COND. POLE TRIP KVA A PHASE KVA B PHASE KVA C PHASE POLE TRIP COND. GRID. WIRE LOAD DESCRIPTION CKT 1 ELEVATOR 1 a 8 10 1 3/35 3.3 3.3 A B PHASE 3/35 1 10 8 WIRE ELEVATOR 2 2 3 1 3.3 3.3 12 4 5 - 20 3.3 3.3 6 7 SHUNT TRIP 1/2 - - - - 2 3 SPARE 12 - - - 20 SHUNT TRIP 8 9 ELEVATOR CAB LIGHTS 1/2 12 12 1/2 20 4 0.4 1 0.4 SPECIAL OUTLET 20 1/2 12 12 30 ELEVATOR CAB LIGHTS 10 11 SPACE 1/2 - - - - 6 7 - - - - - - 30 SPACE 12 13 SPACE 1 - - - - - - 9 SPECIAL OUTLET - - - - 30 SPACE 14 15 SPACE 1 SPECIAL OUTLET - - - - 3/4 - - 10 - - - - 12 SPACE 16 17 SPACE 13 - - - - 10 344 - - - - - - - SPACE 18 ALL FEEDER CALCULATIONS ARE BASED ON:THHN/TMVM CU. NOT MORE THAN 4 CONDUCTORS IN A RACEWAY SUBTOTAL TOTAL KVA IS 6.6 7.4 20.6 KVA 6.6 CIRCUIT TYPE : Q ARC FAULT © 11ME SWATCH CONTROL SHUNT TRIP ® ® GROUND FAULT ® DEDICATED © ISOLATED GIRD. TOTAL AMPERES IS 57.2 AMPS PANEL 'GE 10 10 3 4 30 8 POLE TRIP TYPE RATED VOLTAGE= 120 /208 VOLTS 3 PHASE 4 WIRE M EQPT. GRID. ❑ ISOL. GRID. MAINS: MM.L.O. ❑ BREAKER : I - - 17 FEEDER SIZE IS: MCABLE = SEE RISER 1 20 ❑BUSWAY BRANCH POLES: 18 BRANCH BREAKERS= 14 KAIC - MOUNTING: M SURFACE ❑ FLUSH ❑ FREE STANDING ❑ KEYED DOOR BUS RATING: 1 ODA I BRACING = 14 KAIC - NEUTRAL BUS IS: ❑ HALF SIZE N FULL SIZE ❑ K RATED (1.5) ❑ K RATED (2.0) GROUND BAR: N EQUIPMENT ❑ ISOLATED ❑ BOTH 22 ENCLOSURE : MNEMA 1 ❑ NEMA 3R ❑ NEMA 4X CLASS( ) DIV ( ) FEED LOCATION: W TOP ❑ BOTTOM ❑ FEED THRU 1 12 PANEL TYPE : ❑FUSED ❑ CB PLUG IN ■ CB BOLT IN - FED FROM: NNORMAL ❑ EMERGENCY ❑ UNINTERRUPTABLE NOTE: 20 - - - - LOCATION: SEE FLOOR PLAN ❑EXISTING M NEW Oil NAA I I UM �C2-iG 1 SPEC: SQUARE D, ITE , G.E. CKT. LOAD DESCRIPTION F WIRE GRD. COND. POLE/I TRIP KVA PHASE KVA KVA POLE/ Ljj Ld M City Comments Response �vv � uvJ V nLV MII \Vm t+, nLUMMUm F DUJ LOAD DESCRIPTION a WIRE GRID. COND. TRI A PHASE A B PHASE C PHASE TRIP COND. GIRD. WIRE � LOAD DESCRIPTION CKT CKT 1 SPARE 12 - - - 20 1 1.0 1 1.0 20 20 1/2 1 12 12 IT 128 REC 2 2 3 SPARE 12 - - - 20 0.7 1.0 1.0 1 1.0 20 20 1/2 1 12 12 IT 128 REC 4 4 5 SPECIAL OUTLET 12 10 10 3/4 30 12 1.2 T 1.0 2.0 1 1.0 20 1/2 1 12 12 IT 128 REC 6 6 7 SPECIAL OUTLET 10 10 3 4 30 2.0 3.3 CONF 401 COFFEE MAKER 3 4 2/40 1 10 8 AHU -5 CU -5 12 8 10 9 SPECIAL OUTLET 1.2 1.2 10 10 3 4 30 10 2.0 1 3.3 BUILDING SIGNAGE 11 1 SPECIAL OUTLET 11 1.2 0.1 10 10 3/4 30 10 10 2.0 1.0 20 BLDG. EXTERIOR LIGHTS 12 13 SPARE 3 4 12 13 SPECIAL OUTLET 20 0.6 1.4 10 10 344 30 2.0 1 1.0 10 E 20 - - - SPARE 20 14 15 SPECIAL OUTLET 1 20 PANEL 'GE 10 10 3 4 30 8 2.0 1 1.0 20 - - - SPARE SPACE 16 17 SPACE 1 20 " - - - - ROOFTOP MOTORIZED DAMPER CU -2 - - - - - - SPACE 22 18 19 SPACE - 1 12 - - - - - - - 20 - - - - SPACE 25 1 20 21 SPACE - 12 - - - - - - - 20 - - - - SPACE SPACE 22 23 SPACE - 10 10 3 4 20 2.2 1.0 - - - - - - - - SPACE 24 25 TVSS 2.3 2.2 -- 10 10 3/4 3/30- - - RTU -3 SPACE - - - - 1 ISPACE - - 26 27 N NOT MORE THAN 4 CONDUCTORS IN A RACEWAY - - - 2.3 - - - - SPACE 3/4 28 29 4TH FLR LHT POLES INVERTER - - - - - I ISPACE - MM.L.O. ❑ BREAKER : 30 ALL FEEDER CALCULATIONS ARE BASED ON:THHN /THWN CU. SUBTOTAL TOTAL KVA 10.3 10.3 6.0 CIRCUIT TYPE : I@ ARC FAULT © TIME SWITCH CONTROL BRANH BREAKERS= 14 KAIC NOT MORE THAN 4 CONDUCTORS IN A RACEWAY IS 26.6 KVA 35 ® SHUNT TRIP IG0 F GROUND FAULT ® DEDICATED © ISOLATED GIRD. TOTAL AMPERES IS 74 AMPS 12 12 1/2 20 ❑ K RATED (1.5) ❑ K RATED (2.0) GROUND BAR: M EQUIPMENT ] ISOLATED ❑ BOTH 0.4 - POLE TRIP TYPE RATED VOLTAGE= 120/208 VOLTS 3 PHASE 4 WIRE M EQPT. GIRD. ❑ ISOL. GIRD. MAINS: ■M.L.O. ❑ BREAKER : I - - LOBBY PERIMETER LTS. FEEDER SIZE IS: 0CABLE = SEE RISER 12 ❑BUSWAY BRANCH POLES: 30 BRANCH BREAKERS= 22 KAIC ' ' MOUNTING: MSURFACE ❑ FLUSH ❑ FREE STANDING ❑ KEYED DOOR BUS RATING: 125A I BRACING = 22 KAIC RTU -1 NEUTRAL BUS IS: ❑ HALF SIZE M FULL SIZE ❑ K RATED (1.5) ❑ K RATED (2.0) GROUND BAR: N EQUIPMENT ❑ ISOLATED ❑ BOTH ENCLOSURE: MNEMA 1 ❑ NEMA 3R ❑ NEMA 4X CLASS( ) DIV ( ) FEED LOCATION: STOP p BOTTOM C3 FEED THRU 0.5 3.0 PANEL TYPE : ❑FUSED ❑ CB PLUG IN 0 CB BOLT IN NIGHT LIGHTS LCP FED FROM: WNORMAL ❑ EMERGENCY ❑ UNINTERRUPTABLE NOTE: 1/2 20 0.3 3.0 42 LOCATION: SEE FLOOR PLAN P p np�p wn q w �ypoM2 ®��2 SPEC: SQUARE D, ITE , G.E. LOCATION: M NEW PANEL L� '�?PU SCHEDULE �n CKT. LOAD DESCRIPTION a WIRE GIRD. COND. POLE/ TRIP KVA KVA KVA POLE/ 4Q Ljj Ld M City Comments Response �vv � uvJ V nLV MII \Vm t+, OUJ CKT. LOAD DESCRIPTION a WIRE GRID. COND. TRI A PHASE B PHASE C PHASE TRIP COND. GIRD. WIRE LOAD DESCRIPTION ® CKT 1 CORRIDOR RECS LLi 12 12 1 2 20 0.6 1.6 20 1/2 12 12 CONF 401 RECS 2 3 RMS 411 LTS 2 1.61 0.2 12 12 1 2 20 12 0.7 1.0 20 1/2 12 12 CONF 401 PROJECTOR 20 4 5 CU -6 AHU -6A,6B SITE LIGHTING 12 12 1/2 -172--2/20 2/20 12 1.2 T 1.0 20 1/2 12 12 CONF 401 MOTORIZED SCREEN 20 6 7 1.2 1.0 JC LANDSCAPE LIGHTS 20 1/2 12 12 10 CONF 401 COFFEE MAKER 3 4 8 M 9 CU -7 AHU -7A,7B 12 12 12 - 1.2 1.2 10 20 3 4 10 10 10 BUILDING SIGNAGE 20 10 11 1.2 0.1 20 1.2 1 17 20 3/4 10 10 12 TLT 414 HAND DRYER BLDG. EXTERIOR LIGHTS 12 13 ROOFTOP RECEPTACLES 3 4 12 12 1 2 20 0.6 1.4 3/4 10 20 3 4 10 10 E TLT 413 HAND DRYER 14 15 SHELL SPACE LTS 415 & 417 20 1 12 12 1/2 1 20 PANEL 'GE 1.0 1 6.6 _0__4F7_4 3/80 1 1/4 8 4 PANEL 41A 16 17 CONF FLOOR RECEPTS. SPACE 1 12 12 1/2 1 20 " 3/35 18 19 ROOFTOP MOTORIZED DAMPER CU -2 1 12 12 1/2 20 1 0.1 1 6.6 22 20 21 STAIR LIGHTS - 1 12 12 1 2 20 0.3 0.6 - 20 3 4 10 10 GARAGE 4TH FLR LIGHTS 25 1 22 23 STAIR LIGHTS - 12 12 1 2 20 - 0.3 0.7 20 3 4 10 10 26 GARAGE 3RD FLR LIGHTS SPACE 24 25 EWH -2 - 10 10 3 4 20 2.2 1.0 - - 20 3 4 10 10 29 1 GARAGE 3RD FUR LIGHTS 26 27 - 2.3 2.2 -- 2/20 3 4 10 10 - RTU -3 SPACE 28 29 SPACE SPACE SUBTOTAL TOTAL KVA I - - - - - - - - NOT MORE THAN 4 CONDUCTORS IN A RACEWAY - 2.3 31 - 1 0.4 TOTAL AMPERE IS 266.3 AMPS 20 3/4 10 10 4TH FLR LHT POLES INVERTER 32 33 1 SPACE RATED VOLTAGE= 120/208 VOLTS - - - MM.L.O. ❑ BREAKER : I - _ 1,p FEEDER SIZE IS: MCABLE - SEE RISER ❑BUSWAY BRANCH POLES: 30 BRANH BREAKERS= 14 KAIC MOUNTING: WSURFACE ❑ FLUSH 35 TOILET LIGHTS 400A 12 12 1/2 20 ❑ K RATED (1.5) ❑ K RATED (2.0) GROUND BAR: M EQUIPMENT ] ISOLATED ❑ BOTH 0.4 - - - - - FEED LOCATION: MTOP ] BOTTOM ❑ FEED THRU SPACE PANEL TYPE : ❑FUSED 36 37 LOBBY PERIMETER LTS. FED FROM: 12 12 1 2 20 0.7 3.0 ' ' 3/35 1 10 b RTU -1 38 39 CORRIDOR LIGHTS 12 12 1 2 20 0.5 3.0 40 41 NIGHT LIGHTS LCP 12 12 1/2 20 0.3 3.0 42 ALL FEEDER CALCULATIONS ARE BASED ON:THHN/THWN CU. SUBTOTAL TOTAL KVA IS 20.4 21.6 19.6 CIRCUIT TYPE : Q ARC FAULT © TIME SWITCH CONTROL NOT MORE THAN 4 CONDUCTORS IN A RACEWAY 61.6 KVA SHUNT TRIP ® GROUND FAULT ® DEDICATED ©ISOLATED GIRD. TOTAL AMPERES IS 171.1 AMPS POLE TRIP TYPE RATED VOLTAGE= 120/208 VOLTS 3 PHASE 4 WIRE N EQPT. GIRD. ❑ ISOL. GIRD. MAINS: M .L.. ❑ BREAKER: I - - FEEDER SIZE IS: NCABLE = SEE RISER ❑BUSWAY BRANCH POLES: 42 ANCH BREAKERS= 14 KAIC MOUNTING: 0 SURFACE 1:1 FLUSH ❑FREE STANDING ❑ KEYED DOOR BUS RATING: 22.)A RRACING - 14 KAIC NEUTRAL BUS IS: ❑ HALF SIZE N FULL SIZE ❑ K RATED (1.5) ❑ K RATED (2.0) GROUND BAR: N EQUIPIENT ❑ ISOLATED ❑ BOTH ENCLOSURE: MNEMA 1 ❑ NEMA 3R ❑ NEMA 4X CLASS( ) DIV ( ) FEED LOCATION: MTOP p BOTTOM ❑ FEED THRU PANEL TYPE : ❑FUSED ❑ CB PLUG IN N CB BOLT IN FED FROM: NNORMA ❑ EMERGENCY ❑ UNINTERRUPTABLE NOTE: F OCATION: SEE FLOOR PLAN PAWL �p�p w�p w ��M� ®��� SPEC: SQUARE D, ITE , G.E. EXISTING M NEW PYUx'1'L�L� L W „ ........... .. -.- G S Design Services For The Built Environment Atlanta Birmingham Cincinnati Columbus Dallas Fort Lauderdale Knoxville Jackson Jacksonville Louisville Memphis Nashville RiChmo ampa G R E S H A M SMITH AND P A R T N E R S 6030 Hollywood Blvd. Suite 210 Hollywood, Florida 33024 954.981.9100 FIRM'S FLORIDA CERT. NO. AAP000034 /CA3806 1B26000797/LC26000381 DELTA G CONSULTING ENGINEERS. INC. 707 N.E. 3rd AVE., SUITE 200 ///---- --7��� FORT LAUDERDALE, FL. 33304 (954) 527 -1112 CA #00009181 PJT. UGR: HICHAEL H00 PROJECT #: 120717 No. - Date - Revision r� City Comments Response POLE VA KVA KVA POLE 4Q Ljj Ld M City Comments Response vv. . ♦ vvJ u nLV mll \UM UVJ CKT. LOAD DESCRIPTION a WIRE GRID. COND. TRI ASE B PHASE C PHASE TRIP COND. GIRD. WIRE LOAD DESCRIPTION ® CKT 1 PANEL 4A LLi 250 4 3 3/225120.31 0.1 20 1/2 12 12 120/24V TRANS. 2 3 2 1.61 0.2 20 1/2 12 12 POWER SUPPLIES 4 5 19.2 09 20 1 2 12 12 SITE LIGHTING 6 7 WATER FEATURE 12 12 1 2 20 1.2 0.6 20 1 2 12 12 JC LANDSCAPE LIGHTS 8 9 SIGNAGE C 10 10 3 4 20 1.2 0.1 20 1 2 12 12 EXT. ENTRY LTS 10 11 SIGNAGE 10 10 3/4 20 1.2 0.1 20 1 2 12 12 IRRIGATION CONTROL VALVE 12 13 BLDG. EXTERIOR LIGHTS C 10 10 3 4 20 0.6 1 2.0 2/30 3/4 10 10 AHU -2 14 16 15 RAIN BIRD CONTROLLER 12 12 1/2 20 0.1 2.0 17 PANEL 'GE 3 8 2 3/100 8.6 1 SPACE 18 19 8.6 1.0 " 3/35 1 10 8 CU -2 20 21 7.3 1.0 22 23 1 SPACE - - - - - - - - - - SPACE 24 25 1 SPACE - - - - - - - - - - SPACE 26 27 1 SPACE - - - - - - - - - - SPACE 28 29 1 SPACE - - - - -- - - - - - - SPACE 30 ALL FEEDER CALCULATIONS ARE BASED ON:THHN/THWN CU. SUBTOTAL TOTAL KVA I 33.4 32.5 30.0 CIRCUIT TYPE : © ARC FAULT Q TIME CLOCK & LIGHTING CONTACTOR NOT MORE THAN 4 CONDUCTORS IN A RACEWAY KVA SHUNT TRIP ® GROUND FALT ® DEDICATED © ISOLATED GRD. TOTAL AMPERE IS 266.3 AMPS POLE I TRIP TYPE RATED VOLTAGE= 120/208 VOLTS 3 PHASE 4 WIRE 0 EQPT. GIRD. ❑ ISOL. GRID. MAINS: MM.L.O. ❑ BREAKER : I - - FEEDER SIZE IS: MCABLE - SEE RISER ❑BUSWAY BRANCH POLES: 30 BRANH BREAKERS= 14 KAIC MOUNTING: WSURFACE ❑ FLUSH ❑ FREE STANDING ❑ KEYED DOOR BUS RATING: 400A I BRACLG = 1 4 KAIC NEUTRAL BUS IS: ❑ HALF SIZE 0 FULL SIZE ❑ K RATED (1.5) ❑ K RATED (2.0) GROUND BAR: M EQUIPMENT ] ISOLATED ❑ BOTH ENCLOSURE : MNEMA 1 ❑ NEMA 3R ❑ NEMA 4X CLASS( ) DIV ( ) FEED LOCATION: MTOP ] BOTTOM ❑ FEED THRU PANEL TYPE : ❑FUSED ❑ CB PLUG IN N CB BOLT IN FED FROM: ONORMAL ❑ EMERGENCY ❑ UNINTERRUPTABLE NOTE: G S Design Services For The Built Environment Atlanta Birmingham Cincinnati Columbus Dallas Fort Lauderdale Knoxville Jackson Jacksonville Louisville Memphis Nashville RiChmo ampa G R E S H A M SMITH AND P A R T N E R S 6030 Hollywood Blvd. Suite 210 Hollywood, Florida 33024 954.981.9100 FIRM'S FLORIDA CERT. NO. AAP000034 /CA3806 1B26000797/LC26000381 DELTA G CONSULTING ENGINEERS. INC. 707 N.E. 3rd AVE., SUITE 200 ///---- --7��� FORT LAUDERDALE, FL. 33304 (954) 527 -1112 CA #00009181 PJT. UGR: HICHAEL H00 PROJECT #: 120717 flOR&A., If3ENSE' #46100 DATE: 05/08/13 REVISION No. - Date - Revision r� City Comments Response m r 3Q CY: City Comments Response 4Q Ljj Ld M City Comments Response m C/) )O � ♦ c3+$ A � t-, LL. O Q QOl ® x 2 L0 rz LLi 0 fts C/) flOR&A., If3ENSE' #46100 DATE: 05/08/13 REVISION No. - Date - Revision SANjU''�; City Comments Response w r 3Q CY: City Comments Response 4Q 04/22/13 City Comments Response O. flOR&A., If3ENSE' #46100 DATE: 05/08/13 REVISION No. - Date - Revision City Comments Response Q03/15/13 3Q 03/29/13 City Comments Response 4Q 04/22/13 City Comments Response ELECTRICAL PANELS E4m2 FILE: PROJECT: 29080.00 DATE: 11/29/2012