13-96 (2)-163Mv■ ■ 13111111111 tt FPP #14GND TO CONTROL —� EQUIPMENT O BS PULL BOX s e , Q #6GND CWVJ' t2 ------------- - - - - -- —S TO FACP ---5 TO TBB 6' MIN. #6GND 4 9 2 1 rT�QRQUNDINQ DETAIL E4,1 N.T.S. ROLE* ALL GROUNDING INSTALLATIONG SHALL COMPLY WITH NEC ARTICLE 250. O 10 FT. LONG x 34" DIAMETER COPPER DRIVEN GROUND ELECTRODE. O ADDITIONAL ELECTRODE AS REQUIRED BY NEC 250.56. O CONNECTION TO METALIC COLD WATER PIPE. O EXOTHERMIC CONNECTION (TYPICAL) 3/0 EXOTHERMIC CONNECTION. ELECTRICALLY CONTINUOUS STEEL REINFORCING BAR IN BOTTOM OF BUILDING FOUNDATION IN DIRECT CONTACT WITH EARTH. O ATTACH GROUND BAR TO GROUNDING CONDUCTOR USING SOLID CABLE TO FLAT BAR CONNECTOR. O MAKE CONNECTION TO METALLIC COLD WATER ENTRANCE PIPE BEFORE FIRST VALVE WITH HEAVY DUTY BRONZE GROUND CLAMP. O PROVIDE (1) #4/0 BONDING JUMPER AROUND FIRST VALVE. 0#3/0 GND IN 10C. to CONNECTION TO NATURAL GAS PIPE. tt CONNECTION TO FIRE PROTECTION PIPE. t2 #6 GND IN 3/4 "C. t3 #2/0 GND IN 1 "C. t2 CONNECTION TO CONCRETE— ENCASED ELCTRODE WITH DIRECT BURIAL LISTED CLAMP. PATIO MAIN MAIN 4OF4 @ 3OF4 800A SERVICE 800A SERVICE ENTRANCE RATED ENTRANCE RATED TRYSTAR ROTARY TRYSTAR ROTARY GENERATOR DOCKING GENERATOR DOCKING STATION STATION L...... O ELECTRICAL RISER (VOTES 1. CONTRACTOR TO PROVIDE A PERMANENT PLAQUE FOR EACH NORMAL MAIN AND INDICATE LOCATION OF ALL OTHER MAINS AS PER NEC 225.37. 2. CONTRACTOR SHALL PROVIDE FLASH HAZARD MARKING AS PER NEC 110.16. 3. PROVIDE IDENTIFICATION OF DISCONNECTING MEANS PER NEC 110.22. FEEDER SCHEDULE Ft (2) SETS OF 4 "C. EACH WITH 4#600KCMIL 0 4 "C. WITH 4#600KCMIL O REFER TO ELECTRICAL RISER NOTES ABOVE. F4 4 "C. WITH 4#600KCMIL AND (1) #3GND 0 3" EMPTY CONDUIT WITH PULLSTRINGS Q 1 1/4"C. WITH (4) #3 AND (1) #8GND O 2 "C. WITH (4) #1/0 AND (1) #6GND 0 2 0C. WITH (4) #1 AND (1) #6GND O 3 "C. WITH (4) #3/0 AND (1) #6GND E) 1 1/4 "C. WITH (4) #3 AND (1) #6GND (9 1" EMPTY CONDUIT WITH PULLSTRINGS E) 2" EMPTY CONDUIT WITH PULLSTRINGS 3" EMPTY CONDUIT WITH PULLSTRINGS Q 3 "C. WITH (4) #3/0 AND (1) #6GND SEE PANEL SCHEDULE. E) 3 "C. WITH (4) #3/0 Q 1 1/4" RGS PARKING ROOF CHILLER EQUIP 3*3R a m Nrs MM M711 FUTURE VAULT VAULT ROOM MODULAR o� ' L VAULT CONTROL ROOM 48OV, 3P /90A MCB PANEL FURNISHED BY VARIAN O MM 00 CONTROL EQUIP. PULL BOX _J PNL '4A' \ �l - - - -- IT 128 ELECTRICAL ROOM 122 of3P 200A t 3P /90A PNL 'IT' POWER CONDITIONER 8BLX -50K- 70OA/VS FURNISHED BY VARIAN ------ - - - - -- C ---- - ------------------------- ---- ---------- -- PNL 'GE' PNL i �M PNL PNL 1 E' '11 CE' ---- - - - - -- C -------------------- .............. r, ................ PNL '4E' ......................................... ..................................................................................... .............................. ............................... ... .................. .... I —..................... R 00 F PANEL "1 ED 120/208V, 30, 4W E4,1 *Soo*** -- -------------------------- ------------------------------------------------------- ........ - - - -- __ -------------- -- ELECTRICAL RISER DIAGRAM SCALE: N.T.S. .................. I ... ............................ l............................- ...................... ............................... 4TH FLOOR 3RD FLOOR - PARKING GARAGE 2ND FLOOR - PARKING GARAGE EXTERIOR WALL FAULT CURRENT CALCULATION -3 - - - --- AT MAIN #1 TRANSFORMER LET - THROUGH SHORT- CIRCUIT CURRENT IS .C.: 124,364 AMPS VOLTAGE: _ _ _ 120/208V,_ 30 WIRE SIZE: - - #3/4 KCMIL NUMBER OF CONDUCTORS PER PHASE C: - - 1 -, - CONDUCTOR LENGTH U 65' CONDUCTOR C VALUE: 13,923 ( #CONDUCTORS PER PHASE x C = ) M — MULTIPLIER PANEL "EDP" 120/208V, 30, 4W f —FACTOR ......................................... ..................................................................................... .............................. ............................... ... .................. .... I —..................... R 00 F PANEL "1 ED 120/208V, 30, 4W E4,1 *Soo*** -- -------------------------- ------------------------------------------------------- ........ - - - -- __ -------------- -- ELECTRICAL RISER DIAGRAM SCALE: N.T.S. .................. I ... ............................ l............................- ...................... ............................... 4TH FLOOR 3RD FLOOR - PARKING GARAGE 2ND FLOOR - PARKING GARAGE EXTERIOR WALL FAULT CURRENT CALCULATION -3 - - - --- AT MAIN #1 TRANSFORMER LET - THROUGH SHORT- CIRCUIT CURRENT IS .C.: 124,364 AMPS VOLTAGE: _ _ _ 120/208V,_ 30 WIRE SIZE: - - #3/4 KCMIL NUMBER OF CONDUCTORS PER PHASE C: - - 1 -, - CONDUCTOR LENGTH U 65' CONDUCTOR C VALUE: 13,923 ( #CONDUCTORS PER PHASE x C = ) M — MULTIPLIER f —FACTOR x L x IS.c_ 1.73 x 65 x 124364 f =1.73 = = 4.83 C x EL—L 13923 x 208 M — 1 __ 1 = 0.172 1 + f 1 + 4.83 Is.C.e IS.C. x M = 124364 x 0.172 = 21,331 A RMS RMS MINIMUM BREAKER RATING = 22,000 A.I.C. AT MAIN #2 TRANSFORMER LET - THROUGH SHORT- CIRCUIT CURRENT IS C.: 124,364 AMPS VOLTAGE: 120/208V, 30 WIRE SIZE: #600 KCMIL NUMBER OF CONDUCTORS PER PHASE C: 1 CONDUCTOR LENGTH U 65' NDUCTOR C VALUE: 28,033 CONDUCTORS PER PHASE x C = ) M - MULTIPLIER f - FACTOR f = 1.73 x L x IS -c_ 1.73 x 65 x 124364 = = 2,40 C x EL-L 28033 x 208 1 = 1 M __ =0.29 1 +f 1 +2.40 Is.C.e Is.C. x M = 124364 x 0.29 = 36,577 A RMS RMS MINIMUM BREAKER A.I.C. RATING = 42,000 A.I.C. AT MAIN #3 AND #4 TRANSFORMER LET — THROUGH SHORT— CIRCUIT CURRENT IS C.: 124,364 AMPS VOLTAGE: 120/208V, 30 WIRE SIZE: #600 KCMIL NUMBER OF CONDUCTORS PER PHASE C: 2 CONDUCTOR LENGTH L• 150' NDUCTOR C VALUE: 56,066 CONDUCTORS PER PHASE x C = ) M — MULTIPLIER f —FACTOR 1.73 x L x IS.c. 1.73 x 150 x 124364 f = = C x EL—L 56066 x 208 = 2'77 __ 1 1 M = =0.27 1 +f 1 +2.77 Is.0 A° Is.C. x M = 124364 x 0.27 = 32,987 A RMS RMS MINIMUM BREAKER A.I.C. RATING = 42,000 A.I.C. 33R 33R 33R BUILDING METER MAIN 1 OF 4 200A DISC. e MAIN a 120/208V, 2 OF 4 30, 4W t NEW FP &L 120/208V, 30 O O 120/208V, O 0A DISC. CT TRANSFORMER 12 30, 4W CAN 33R Fr7n 3993 e o WIREWAY F4 4W r ...--------- - -- --- - ------------- . e n : G RO U N D ' --------------------- --------------- - - - - -- - - - -- - - -- .. - -- - - - - -- - - - .................. . r "_ _________---...._._.______ '-------------------------- v-- - - v-- -- ----- ------- ------------- 1 � Design Services® For The Built Environment E Atlanta Birmingham Cincinnati Columbus Dallas Fort Lauderdale Knoxville Jackson Jacksonville Louisville Memphis Nashville Richmond Tampa G R E S H A M SMITH AND P A R `T H E R S 6030 Hollywood Blvd. Suite 210 Hollywood, Florida 33024 954.981.9100 FIRM'S FLORIDA CERT. NO. AAP000034 /CA3806 IB26000797/LC26000381 DELTA G CONSULTING ENGINEERS, INC. 707 N.B. 3rd AVE., 8UrrE 200 FORT LIUDBRDALE, FL 33304 (964) 627 -1112 CA/00009181 IT. MM MICHAEL HOO ROJEdf #: 120717 m tw ?� Q Cr c u 0 _ �U_ . 0 Q U-) W o U) �,itli}1tl ;FP,. .e �l\tJJI f �. OF • cu ti G$ORGB • ?3�i� ,v TES• o• ci,s�pa� REVISION No, - Date - Revision ELECTRICAL RISER DIAGRAM E4.1 FILE: PROJECT: 29080.00 DATE: 11/29/2012