6' MIN
#14GND
TO CONTROL
—� EQUIPMENT
PULL BOX
- #6GND
' —S TO FACP
5 TO TBB
#6GND
z GROUNDING DETAIL
E4.1 N.T.S.
NOTE: ALL GROUNDING INSTALLATIONG SHALL
COMPLY WITH NEC ARTICLE 250.
O 10 FT. LONG x 3/a" DIAMETER COPPER DRIVEN
GROUND ELECTRODE.
0 ADDITIONAL ELECTRODE AS REQUIRED BY NEC
250.56.
O CONNECTION TO METALIC COLD WATER PIPE.
O EXOTHERMIC CONNECTION (TYPICAL)
3/0 EXOTHERMIC CONNECTION. ELECTRICALLY
I CONTINUOUS STEEL REINFORCING BAR IN BOTTOM
j OF BUILDING FOUNDATION IN DIRECT CONTACT
WITH EARTH.
O ATTACH GROUND BAR TO GROUNDING CONDUCTOR
USING SOLID CABLE TO FLAT BAR CONNECTOR.
O MAKE CONNECTION TO METALLIC COLD WATER
ENTRANCE PIPE BEFORE FIRST VALVE WITH HEAVY
DUTY BRONZE GROUND CLAMP.
O PROVIDE (1) #4/0 BONDING JUMPER AROUND
FIRST VALVE.
(D#3/0 GND IN 1 "C.
�o CONNECTION TO NATURAL GAS PIPE.
>> CONNECTION TO FIRE PROTECTION PIPE.
(D#1/0 GND IN 3/4 "C.
13 #8 GND IN 1/2"C.
to CONNECTION TO CONCRETE— ENCASED ELCTRODE
WITH DIRECT BURIAL LISTED CLAMP.
is #4 GND IN 3/4 "C.
is #14 GND IN 1/2 "C.
F3
MAIN 0
6OF6
400A M.C.B.
SERVICE
ENTRANCE RATED
TRYSTAR ROTARY
GENERATOR DOCKING
STATION
a
PATIO
MAIN
5OF6
1200A M.C.B.
SERVICE
ENTRANCE RATED
TRYSTAR ROTARY
GENERATOR DOCKING
STATION
ELECTRICAL RISER MOTES
1. CONTRACTOR TO PROVIDE A PERMANENT PLAQUE FOR
EACH NORMAL MAIN AND INDICATE LOCATION OF ALL OTHER
MAINS AS PER NEC 225.37.
2. CONTRACTOR SHALL PROVIDE FLASH HAZARD MARKING AS
PER NEC 110.16.
3. PROVIDE IDENTIFICATION OF DISCONNECTING MEANS PER
NEC 110.22.
u9
�o
PARKING ROOF
TO LIGHT
POLES
PNL PNL
'4A' '41 A'
�.
2
11
60OW INVERTER
PHILIPS CHLORIDE
Z1600 -120
PNL
0
CHILLER EQUIP
3*3 R
3*3R
Q
30 AIDS G
or b AMf
FUTURE VAULT
o�I
VAULT ROOM
MODULAR
ROOF
4TH FLOOR-,
3RD FLOOR -
PARKING GARAGE
i
2ND FLOOR -
-- - -
VAULT CONTROL ROOM IT 128 ELECTRICAL ROOM 122 EXTERIOR WALL
1
I
FAULT CURRENT CALCULATIONS
AT MAINS #1. #2. AND #3
FEEDER SCHEDULE
Ft
(3) SETS
OF 4 "C. EACH WITH (4) #600KCMIL
F2
4 "C. WITH
4 #500KCMIL
F3
REFER TO
ELECTRICAL RISER NOTES ABOVE.
F4
4 "C. WITH
4 #500KCMIL AND (1) #3GND
Fs
3" EMPTY
CONDUIT WITH PULLSTRINGS
Fs
1 1/4 "C.
WITH (4) #3 AND (1) #8GND
O
2 "C. WITH
(4) #3
F6
2 "C. WITH
(4) #1 AND (1) #6GND
Fs
3 "C. WITH
(4) #3/0 AND (1) #6GND
to
2 "C. WITH
(4) #3 AND (1) #8GND
Ft t
1 " EMPTY
CONDUIT WITH PULLSTRINGS
t®
2" EMPTY
CONDUIT WITH PULLSTRINGS
VOLTAGE:
3" EMPTY
CONDUIT WITH PULLSTRINGS
1a
NOT USED.
1
is
SEE PANEL SCHEDULE.
is
3 "C. WITH
(4) #3/0
• -9 r`
1 1/4" RGS
o
o1
(3) SETS
OF 4 "C. EACH WITH (4) #600KCMIL &
1.73 x L x IS.C. 1.73 x 75 x 32,552
f
(1) #3/0 GND
u9
�o
PARKING ROOF
TO LIGHT
POLES
PNL PNL
'4A' '41 A'
�.
2
11
60OW INVERTER
PHILIPS CHLORIDE
Z1600 -120
PNL
0
CHILLER EQUIP
3*3 R
3*3R
Q
30 AIDS G
or b AMf
FUTURE VAULT
o�I
VAULT ROOM
MODULAR
ROOF
4TH FLOOR-,
3RD FLOOR -
PARKING GARAGE
i
2ND FLOOR -
-- - -
VAULT CONTROL ROOM IT 128 ELECTRICAL ROOM 122 EXTERIOR WALL
1
I
FAULT CURRENT CALCULATIONS
AT MAINS #1. #2. AND #3
DELTA G CONSULTING
TRANSFORMER LET— THROUGH SHORT— CIRCUIT CURRENT IS C
32,552 AMPS
VOLTAGE:
120/208V, 30
WIRE SIZE:
#3/0 KCMIL
NUMBER OF CONDUCTORS PER PHASE C:
1
CONDUCTOR LENGTH L:
75'
CONDUCTOR C VALUE:
13,923
( #CONDUCTORS PER PHASE x C = )
M — MULTIPLIER
0)
f — FACTOR
1.73 x L x IS.C. 1.73 x 75 x 32,552
f
__ =
C x EL —L 13923 x 208 = 1.46
•�
M = 1 — 1 = 0.407
1 + f 1 + 1.46
IS.C.A= IS.C. x M = 32,552 x 0.407 = 13,232 A RIMS
m
RMS
MINIMUM BREAKER RATING = 18,000 A.I.C.
•0
AT MAIN #4
TRANSFORMER LET— THROUGH SHORT— CIRCUIT CURRENT IS.C.:
32,552 AMPS
VOLTAGE:
120/208V, 30
WIRE SIZE:
#3
NUMBER OF CONDUCTORS PER PHASE C:
1
CONDUCTOR LENGTH L:
75'
CONDUCTOR C VALUE:
4,811
( #CONDUCTORS PER PHASE x C = )
• -9 r`
M — MULTIPLIER
o
o1
f — FACTOR
0
1.73 x L x IS.C. 1.73 x 75 x 32,552
f
�w
= = = 4.22
C x EL—L 4811 x 208
.. -0 '• t A-� O • (V
o �• C • b
1 __ 1
M __ =0.192
1 +f 1 +4.22
s
Is.C.a— IS.C. x M = 32,552 x 0.192 = 6,236 A RMS
RMS
FLOItTDA I E� 46100
MINIMUM BREAKER A.I.C. RATING = 10,000 A.I.C.
DATE: 05/08/13
AT MAIN #5
TRANSFORMER LET— THROUGH SHORT— CIRCUIT CURRENT IS
32,552 AMPS
C
VOLTAGE:
120/208V, 30
WIRE SIZE:
#600 KCMIL
NUMBER OF CONDUCTORS PER PHASE C:
3
CONDUCTOR LENGTH L:
150'
CONDUCTOR C VALUE:
84,099
( #CONDUCTORS PER PHASE x C = )
M — MULTIPLIER
f —FACTOR
1.73 x L x IS.C. 1.73 x 150 x 32,552
f
= = = 0.483
C x EL—L 84,099 x 208
M = 1 — 1 = 0.674
1 + f 1 + 0.483
Is.C.A IS.C. x M = 32,552 x 0.674 = 21,950 A RMS
RMS
MINIMUM BREAKER A.I.C. RATING = 22,000 A.I.C.
AT MAIN #6
TRANSFORMER LET— THROUGH SHORT— CIRCUIT CURRENT IS.C.
32,552 AMPS
VOLTAGE:
120/208V, 30
WIRE SIZE:
#500 KCMIL
NUMBER OF CONDUCTORS PER PHASE C:
1
CONDUCTOR LENGTH L:
150'
CONDUCTOR C VALUE:
26,706
( #CONDUCTORS PER PHASE x C = )
M — MULTIPLIER
f — FACTOR
1.73 x L x IS.C_ 1.73 x 150 x 32,552
f
= = = 1.52
C x EL_L 26,706 x 208
M = 1 = 1 = 0.397
1 + f 1 + 1.52
IS.C.A= IS.C. x M = 32,552 x 0.397 = 12,917 A RMS
RMS
MINIMUM BREAKER A.I.C. RATING = 14,000 A.I.C.
MAIN MAIN MAIN
10 480V, 3P /90A 3 OF 6 2 OF 6 1 OF 6
3 3R 3 3R 3 3R 0
FUR PANEL BUILDING
FURNISHED � PNL MAIN
BY VARIAN ! FS t F8 Fs 'SL' 4 OF 6
O j 31,800-3R
O
ID ID •
00 l IrJ - t NEW FP &L
3P /200A : • • 120/208V, 30 400A CT
3P/9a
TRANSFORMER
P /90 4 ,00 AAM O O O METER CAN
PANEL "EDP"
1200A MLO, 200A 200A 200A
CONTROL PNL PNL PNL PNL 120/208V, METER METER METER
EQUL P BOX 'IT' POWER 'GE' F1 E' '11 CE' �0, 4W
CONDITIONER 100A
8BLX -50K- 2 13
70OA /VS I L - ----- i \IT S�
ri FURNISHED 16
- BY VARIAN -- - _ -
- - - - - -- - - - - - - - •••••••• - - - - -- - - - -- - -- - - ; GROUND
ro 1
ELECTRICAL RISER DIAGRAM
SCALE: N.T.S.
I
I
G S & P
Design Services
For The Built
Environment
N
Atlanta Birmingham
Cincinnati
Columbus Dallas
Fort Lauderdale
Knoxville Jackson
Jacksonville Louisville
Memphis Nashville
Richmond Tampa
0
G R E S H A M
SMITH AND
P A R T N E R S
6030 Hollywood Blvd.
Suite 210
Hollywood, Florida 33024
954.981.9100
FIRM'S FLORIDA
CERT. NO.
AAP000034 /CA3806
1B26000797/LC26000381
REVISION
No. - Date - Revision
DELTA G CONSULTING
ENGINEERS, INC.
Addendum #1
707 N.E. 3rd AVE., SUITE 200
FORT LAUDERDALE, FL. 33304
(954) 527 -1112
CA #00009181
Q04/22/13
PJT. MGR: MICHAEL HOO
City Comments Response
PROJECT #: 120717
0)
•�
w
w
Q
0
Of
m
O
•0
Q
LC)
Q
2
® X
CY)
`�
L!
:D
o
A /V r0�i
• -9 r`
o
o1
0
�w
.. -0 '• t A-� O • (V
o �• C • b
s
FLOItTDA I E� 46100
DATE: 05/08/13
REVISION
No. - Date - Revision
Q02/01/13
Addendum #1
Q04/22/13
City Comments Response
ELECTRICAL RISER
DIAGRAM
E4.1
FILE:
PROJECT: 29080.00
DATE: 11129/2012