Loading...
13-96 (2)-104FIRE ALARM SYSTEM (VOTES 1. THE MAIN FIRE ALARM CONTROL PANEL SHALL BE A MICROPROCESSOR BASE SYSTEM WITH ADDRESSABLE, INTELLIGENT DETECTORS. ADDRESSABLE CONTROL RELAY AND MONITOR MODULES, VISIBLE AND AUDIBLE SYSTEM ANNUCIATORS AND OTHER SYSTEM CONTROLLED DEVICES AS REQUIRED. 2. PROVIDE REMOTE POWER SUPPLY AS INDICATED FOR EACH FLOOR FOR FUTURE TENANT BUILDOUT. THE FIRE THE FIRE ALARM SHALL BE CAPABLE OF FUTURE EXPANSION AS REQUIRED IN THE TENANT TENANT SPACES. 3. ALL WIRING AND CONDUIT TO CONFORM TO N.F.P.A. 72 AND N.E.C. ARTICLE 760. WIRING SHALL BE SOLID COPPER OR STRANDED COPPER WITH A MAX. OF 7 STRANDS FOR 16 GA AND IS GA. STRANDED COPPER WITH A MAX. OF 19 STRANDS FOR SIZES 14 AND LARGER AS RQUIRED BY N.E.C. 760 AND N.F.P.A. 70. 4. ALL FIRE STOP PENETRATIONS SHALL BE MADE WITH APPROVED (NEC) METALLIC CONDUIT AND SHALL BE SEALED WITH A U.L' APPROVED FIRE STOP MATERIAL (SEE FIRE STOP DETAIL) 5. ROUTING OF THE FIRE ALARM SYSTEM CONDUIT IS DIAGRAMMATIC ONLY, VERIFY EXACT LOCATIONS PRIOR TO STARTING WORK. 6. ALL FIRE ALARM VISUAL SIGNAL (STROBES) SHALL ACTIVATE UPON INITIATION OF THE GENERAL ALARM. 7. ALL FIRE ALARM VISUAL SIGNALS IN OPEN AREA SHALL HAVE A THREE PLUS TEMPORAL PATTERN. 8. ALL FIRE ALARM AUDIBLE SIGNALS SHALL HAVE A SOUND LEVEL OF AT LEAST 15 dba ABOVE THE AVERAGE ABMBIENT SOUND LEVEL. 9. MANUAL STATIONS SHALL BE INSTALLED AT 48" INCHES A.F.F. 10. MOUNT FIRE ALARM SYSTEM HORN ORES SUCH THAT THE ENTIRE LENS IS SO" A.F.F. OR 6" BELOW CEILING, WHICH EVER IS LO 11. MOUNT FIRE ALARM SYSTEM STROBES SUCH THAT THE ENTIRE LENS IS 80" A.F.F. OR 6" BELOW CEILING, WHICH EVER IS LOWER. 12. SMOKE DETECTORS TO BE INSTALLED AS REQUIRED BY N.F.P.A. 72. 13. THE FIRE ALARM PANEL SHALL HAVE AN EARTH GROUND CONNECTION AS REQUIRED BY THE SYSTEM MANUFACTURER, AND N.E.C. ARTICLE 760. MINIMUM WIRE SIZE IS AWG FOR GROUND CONNECTION. (NOTE PANEL NEUTRAL OR CONDUIT GROUND IS NOT ACCEPTABLE 14. A GENERAL ALARM SHALL BE ANNUNCIATED UPON ACTIVATION OF ANY PULL STATION, FLOW SWATCH OR DETECTION DEVICE 15. A TROUBLE SIGNAL SHALL BE ANNUNCIATED UPON FAILURE OR REMOVAL OF ANY DETECTION OR MANUAL DEVICE 16. A SUPERVISORY SIGNAL SHALL BE ANNUNCIATED UPON ACTIVATION OF ANY FIRE SPRINKLER SYSTEM TAMPER SWITCH. 17. HVAC DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE FIRE ALARM CONTROL PANEL AND SHALL INITIATE A SUPERVISORY SIGNAL ONLY. 18. FIRE ALARM SYSTEM SHALL BE U.L CERTIFIED. 19. ALL FIRE ALARM INITIATING DEVICES SHALL BE ADDRESSABLE AND ALL FIRE ALARM CIRCUITS SHALL BE CLASS "B STYLE "4" SLC AND CLASS "B" STYLE "Y" NAC CIRCUITS. 20. PROVIDE CERTIFICATE OF COMPLETION AT THE FINAL INSPECTION OF THE FIRE ALARM SYSTEM. 21. PROVIDE THE OWNER WITH A COMPLETE FIRE ALARM SYSTEM AND INSTALLATION MANUAL COVERING MANUAL COVERING ALL SYSTEM EQUIPMENT INSTALLED FOR THIS PROJECT. KEEP AT THE MAIN FIRE ALARM CONTROL PANEL 22. ALL PULL STATIONS TO HAVE UL LISTED COVERS. 23. ALL STROBE LIGHTS SHALL COMPLY WITH NFPA 72 24. MINIMUM RADIO SIGNAL STRENGTH AS REQ'D BY AHJ SHALL BE MAINTAINED PER FFPC NFPA 1 11.3.1.3. RADIO SIGNAL STRENGTH MUST BE THE SAME FOR INSIDE AND OUTSIDE OF THE BUILDING. PROVIDE AN AMPLIFIED SYSTEM TO MEET MINIMUM RADIO STRENGTH AS REQUIRED BY AHJ. FIRE ALARM BAT'T'ERY CALCULATION ITEM DESCRIPTION STANDBY CURRENT PER UNIT (AMPS) QTY REQUIRED TOTAL STANDBY CURRENT ERIT) ALARM CURRENT PER UNIT (AMPS) MINIMUM QTY STANDBY TOTAL ALARM CURRENT (AMPS) ❑P MANUAL PULL STATION .0 X 11 - .0 .000230 X 11 = .00253 (2 p PHOTOELECTRIC SMOKE DETECTOR .000230 X 8 - .00184 .0065 X 8 = .052 (B,, ELEVATOR PHOTOELECTRIC SMOKE DETECTOR .000230 X 13 - .00299 .0065 X 13 = .08+5 GO) W DUCT DETECTOR .015 X 2 .03 .012 X 2 .024 1 t& HEAT DETECTOR .00015 X 3 .00045 .005 X 3 .015 rF-Aw-1 FIRE ALARM CONTROL PANEL .1 X 1 = .1 .15 X 1 .15 ® FIRE ALARM SYSTEM PONT ANNUNCIATOR .04 X 1 .04 .056 X 1 .056 FAANS ALARM COMMUNICATIONS ANNUNCIATOR .1 X 1 .1 .17 X 1 .17 75 STROBE (75 CANDELA) .0 X 44 0 .123 X 44 = 5.412 Otto STROBE (110 CANDELA) .0 X 1 0 .140 X 1 - .140 STANDBY CURRENT (AMPS) 0.3 ALARM CURRENT (AMPS) 6.1 REQUIRED OPERATING TIME OF SECONDARY POWER SOURCE FROM NFPA 72 1- 5.2.5: STANDBY. 24 HOURS ALARM: 5 MINUTES X 1/60 = 0.0833 HOURS FIRE ALARM RISER DIAGRAM, BATTERY CALCULATIONS, AND NOTES SCALE: N.T.S. REQUIRED TOTAL SYSTEM REQUIRED REQUIRED DERATING TOTAL SYSTEM MINIMUM REQUIRED STANDBY ALARM STANDBY AMPERE HOUR STANDBY ALARM ALARM CAPACITY ALARM TIME CURRENT CAPACITY TIME BATTERY CURRENT CAPACITY (HOURS) (AMPS) (AMP- HOURS) (HOURS) 7.2 (AMPS) 0.5081 (AMP- HOURS) 24 X 0.3 7.2 [I__6:0_W_3j X 6.1 1 0.5081 REQUIRED REQUIRED REQUIRED DERATING MINIMUM STANDBY ALARM AMPERE HOUR FACTOR O AMP -HOUR CAPACITY CAPACITY BATTERY 1.2 BATTERY (AMP - HOURS) (AMP - HOURS) REQUIRED 7.2 I + 0.5081 7.7051 I X 1.2 9.2497 El U i s Design Services For The Built Environment ■ Atlanta Birmingham Cincinnati Columbus Dallas Fort Lauderdale Knoxville Jackson Jacksonville Louisville Memphis Nashville Richmond Tampa ■ G R E S H A M S M I T A N D P A R T N E R S 6030 Hollywood Blvd. Suite 210 Hollywood, Florida 33024 954,981.9100 FIRM'S FLORIDA CERT. NO. AAP000034/CA3806 IB26000797/LC26000381 DELTA G CONSULTING ENGINEERS. INC. 707 N.B. 3rd AVE., SUITE 200 FORT LAUDERDALE, FL. 33304 954) 527 -1112 C PJT. YGR: 1QCHABL H00 PROJECT J: 120717 a`o100111111111 � 0 V/V O �v� ••d I ••0 00 9 OA, Mf.M M• REVISION I No. - Date - Revision FIRE ALARM RISER DIAGRAM AND BATTERY CALCULATIONS FA3n1 FILE: PROJECT: 29080.00 DATE: 11/29/2012