13-96 (2)-103P11 P10
IJp--Cp
S11 S10 S9
2p 0, 2E
P9 P8
Dp D-p
S8
P7 P8
D'p p
S7
Vp
P5 P4 P3 P2 P1
S01 S8 S5 S4 S3 S2 S1
2pp 2p 2p 2CO 2p 2E 2E
CONTROL
MODULE
SE7
ZE-
SE5
E
SE3
a
SE1
20-E
ELEVATOR SHAFT
SE9 SE10
2 E J E
SES
OE
SE8
OE '
SE4
\WE €
SE2
OE :
A59 A80 A81 A62
A54 AN AN A87 AM
75M 75M 7300 73CD 75CD 750 75M 75CD 73M 7800 11OCD
A63 A54 A65 ASO A67 ASS A89 A70 A71 A72 A73
A43 A48 A47 AM A49
75CD 73CD 75CD 75M
A50 A51 A52 A53
AM A37 AM A39 A40
75CD 75CD 75CD 75CD
A41 A42 A43 A44
M21Si o
Al A2 A3 A4 AS AS A7 AS A9
75M 7500 75CD 75M 75M 75M 75M 75CO 75M 75CD 75CD 75CD 75CD
A10 All Al2 A13 A14 A15 A18 A17 A18 A19 A20 A21 A22
75M 75CD 75CD 75M 75CD 75CD 75CD 75CD 75CD 75CD 75CO 75CD 75CD
A23 A24 AM A28 A27 AM M AM A31 A32 AM AM AM
FIRE ALARM SYSTEM WIRE SCHEDULEo MAIN FIRE ALARM RIPS
FIRE ALARM SYSTEM SHALL BE POWER LIMITED CONTROL PANEL
• INITIATING CIRCUITS: 4 CONDUCTOR, #18 AWG (FRCP)
SOLID, SHIELDED TWISTED PAIR 2
• INDICATING CIRCUITS: 2 CONDUCTOR, #14 AWG
SOLID, SHIELDED CABLE
NOTES:
1. PROVIDE PLENUM RATED FIRE ALARM CABLE
WHERE REQUIRED. 3
2. VERIFY IF EXISTING FA SYSTEM CAN INTERFACE
WITH THIS NEW BUILDING'S FA SYSTEM. -
3. ALL CONTROLS FOR ALARM SYSTEM SHALL BE
AT MAIN PANEL
KEY NOTES:
FLOW O D AS INDICAT
THE FIRESPR NKLER SYSTEMDRAWIN S. ON O CO MM CA R TO MAIN BUILDING GROU
TOR TRAN MITTER TO MAIN TELE HONE O
BACKBOARD.
2
FIRE ALArm"M SYSTEM NOTES
1. THE MAIN FIRE ALARM CONTROL PANEL SHALL BE A MICROPROCESSOR BASE SYSTEM WITH
ADDRESSABLE, INTELLIGENT DETECTORS. ADDRESSABLE CONTROL RELAY AND MONITOR MODULES,
VISIBLE AND AUDIBLE SYSTEM ANNUCIATORS AND OTHER SYSTEM CONTROLLED DEVICES AS REQUIRED.
2. PROVIDE REMOTE POWER SUPPLY AS INDICATED FOR EACH FLOOR FOR FUTURE TENANT BUILDOUT.
THE FIRE THE FIRE ALARM SHALL BE CAPABLE OF FUTURE EXPANSION AS REQUIRED IN THE TENANT
TENANT SPACES.
3. ALL WIRING AND CONDUIT TO CONFORM TO N.F.P.A. 72 AND N.E.C. ARTICLE 760. WIRING SHALL BE
SOLID COPPER OR STRANDED COPPER WITH A MAX. OF 7 STRANDS FOR 16 GA AND 18 GA, STRANDED
COPPER WITH A MAX. OF 19 STRANDS FOR SIZES 14 AND LARGER AS RQUIRED BY N.E.C. 760
AND N.F.P.A. 70.
4, ALL FIRE STOP PENETRATIONS SHALL BE MADE WITH APPROVED (NEC) METALLIC CONDUIT AND SHALL
BE SEALED WITH A U.L APPROVED FIRE STOP MATERIAL (SEE FIRE STOP DETAIL)
5. ROUTING OF THE FIRE ALARM SYSTEM CONDUIT IS DIAGRAMMATIC ONLY, VERIFY EXACT LOCATIONS
PRIOR TO STARTING WORK.
6. ALL FIRE ALARM VISUAL SIGNAL (STROBES) SHALL ACTIVATE UPON INITIATION OF THE GENERAL ALARM.
7. ALL FIRE ALARM VISUAL SIGNALS IN OPEN AREA SHALL HAVE A THREE PLUS TEMPORAL PATTERN.
8. ALL FIRE ALARM AUDIBLE SIGNALS SHALL HAVE A SOUND LEVEL OF AT LEAST 15 dba ABOVE THE
AVERAGE ABMBIENT SOUND LEVEL.
9. MANUAL STATIONS SHALL BE INSTALLED AT 48' INCHES A.F.F.
10. MOUNT FIRE ALARM SYSTEM HORN /STROBES SUCH THAT THE ENTIRE LENS IS 80" A.F.F. OR 6-
BELOW CEILING, WHICH EVER IS LOWER.
11. MOUNT FIRE ALARM SYSTEM STROBES SUCH THAT THE ENTIRE LENS IS 80' A.F.F. CAR 6"
BELOW CEILING, WHICH EVER IS LOWER.
12. SMOKE DETECTORS TO BE INSTALLED AS REQUIRED BY N.F.P.A. 72.
13. THE FIRE ALARM PANEL SHALL HAVE AN EARTH GROUND CONNECTION AS REQUIRED BY THE SYSTEM
MANUFACTURER, AND N.E.C. ARTICLE 760. MINIMUM WIRE SIZE IS AWG FOR GROUND CONNECTION.
(NOTE PANEL NEUTRAL OR CONDUIT GROUND IS NOT ACCEPTABLE
14. A GENERAL ALARM SHALL BE ANNUNCIATED UPON ACTIVATION OF ANY PULL STATION, FLOW SWITCH
OR DETECTION DEVICE.
15. A TROUBLE SIGNAL SHALL BE ANNUNCIATED UPON FAILURE OR REMOVAL OF ANY DETECTION OR
MANUAL DEVICE.
16. A SUPERVISORY SIGNAL SHALL BE ANNUNCIATED UPON ACTIVATION OF ANY FIRE SPRINKLER
SYSTEM TAMPER SWITCH.
17. HVAC DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE FIRE ALARM CONTROL PANEL AND
SHALL INITIATE A SUPERVISORY SIGNAL ONLY.
18. FIRE ALARM SYSTEM SHALL BE U.L CERTIFIED.
19. ALL FIRE ALARM INITIATING DEVICES SHALL BE ADDRESSABLE AND ALL FIRE ALARM CIRCUITS SHALL
BE CLASS "B', STYLE W SLC AND CLASS "B" STYLE "Y" NAC CIRCUITS.
20. PROVIDE CERTIFICATE OF COMPLETION AT THE FINAL INSPECTION OF THE FIRE ALARM SYSTEM.
21. PROVIDE THE OWNER WITH A COMPLETE FIRE ALARM SYSTEM AND INSTALLATION MANUAL COVERING
MANUAL COVERING ALL SYSTEM EQUIPMENT INSTALLED FOR THIS PROJECT. KEEP AT THE MAIN FIRE
ALARM CONTROL PANEL
22. ALL PULL STATIONS TO HAVE UL LISTED COVERS.
23. ALL STROBE LIGHTS SHALL COMPLY WITH NFPA 72
24. MINIMUM RADIO SIGNAL STRENGTH AS REQ'D BY AHJ SHALL BE MAINTAINED PER FFPC NFPA 1 11.3.1.3.
RADIO SIGNAL STRENGTH MUST BE THE SAME FOR INSIDE AND OUTSIDE OF THE BUILDING.
PROVIDE AN AMPLIFIED SYSTEM TO MEET MINIMUM RADIO STRENGTH AS REQUIRED BY AHJ.
DO NOT INSTALL EIRE ALARM
PER 7MS Di,F,W.1T TG!
FEEQ- E TNiFjTA r T ATTON
FireAlarrr: contra CiQt`a 'W:Ci'iF:- pl Ii i S'? ?1I
be subin'ted forrRrmit 2uyr�val to hli.mi-
Dade County Piro D::parlm. jjt.
Approved for Buildh -,,r Permit oriy!
Date gy
ITEM
FRE ALARM
BATTERY
CALCULATION
QTY
REQUIRED
TOTAL
STANDBY
CURRENT
PER ITEM
(AMPS)
ALARM
CURRENT
PER UNIT
(AMPS)
MINIMUM
QTY
STANDBY
TOTAL
ALARM
CURRENT
(AMPS)
�p
MANUAL PULL STATION
.0
X
11
=
.0
.000230
X
11
=
.00253
(BP
PHOTOELECTRIC SMOKE DETECTOR
.000230
X
8
=
.00184
.0065
X
8
=
.052
0E
ELEVATOR PHOTOELECTRIC SMOKE DETECTOR
.000230
X
13
=
.00299
.0065
X
13
X
.0845
Opp
DUCT DETECTOR
.015
X
2
=
.03
.012
X
2
=
.024
@"I
HEAT DETECTOR
.00015
X
3
.00045
.005
X
3
=
.015
FACP
FIRE ALARM CONTROL PANEL
.1
X
1
=
.1
.15
X
1
=
.15
Q
FIRE ALARM SYSTEM POINT ANNUNCIATOR
.04
X
1
=
.04
.056
X
1
=
.056
FAANS
ALARM COMMUNICATIONS ANNUNCIATOR
.1
X
1
=
.1
.17
X
1
=
.17
�Q�7e
STROBE (75 CANDELA)
.0
X
44
s
0
.123
X
44
=
5.412
% %tto
STROBE (110 CANDELA)
.0
X
1
=
0
.140
X
1
=
.140
STANDBY CURRENT (AMPS)_ �
0'3
ALARM CURRENT (AMPS)
6.1
REQUIRED
OPERATING TIME OF SECONDARY POWER SOURCE FROM NFPA 72 1- 5.2.5:
STANDBY 24 HOURS
ALARM: 5
MINUTES X 1/60 = 0.0833 HOURS
ITEM
I DESCRIPTION
',
STANDBY
CURRENT
PER UNIT
(AMPS)
QTY
REQUIRED
TOTAL
STANDBY
CURRENT
PER ITEM
(AMPS)
ALARM
CURRENT
PER UNIT
(AMPS)
MINIMUM
QTY
STANDBY
TOTAL
ALARM
CURRENT
(AMPS)
�p
MANUAL PULL STATION
.0
X
11
=
.0
.000230
X
11
=
.00253
(BP
PHOTOELECTRIC SMOKE DETECTOR
.000230
X
8
=
.00184
.0065
X
8
=
.052
0E
ELEVATOR PHOTOELECTRIC SMOKE DETECTOR
.000230
X
13
=
.00299
.0065
X
13
X
.0845
Opp
DUCT DETECTOR
.015
X
2
=
.03
.012
X
2
=
.024
@"I
HEAT DETECTOR
.00015
X
3
.00045
.005
X
3
=
.015
FACP
FIRE ALARM CONTROL PANEL
.1
X
1
=
.1
.15
X
1
=
.15
Q
FIRE ALARM SYSTEM POINT ANNUNCIATOR
.04
X
1
=
.04
.056
X
1
=
.056
FAANS
ALARM COMMUNICATIONS ANNUNCIATOR
.1
X
1
=
.1
.17
X
1
=
.17
�Q�7e
STROBE (75 CANDELA)
.0
X
44
s
0
.123
X
44
=
5.412
% %tto
STROBE (110 CANDELA)
.0
X
1
=
0
.140
X
1
=
.140
STANDBY CURRENT (AMPS)_ �
0'3
ALARM CURRENT (AMPS)
6.1
FIRE ALARM RISER DIAGRAM, BATTERY CALCULATIONS, AND NOTES
SCALE: N.T.S.
REQUIRED
TOTAL SYSTEM
REQUIRED
REQUIRED
DEBATING
TOTAL SYSTEM
MINIMUM
REQUIRED
STANDBY
ALARM
STANDBY
AMPERE HOUR
STANDBY
ALARM
ALARM
CAPACITY
ALARM
TIME
CURRENT
CAPACITY
TIME
BATTERY
CURRENT
CAPACITY
(HOURS)
(AMPS)
(AMP - HOURS)
(HOURS)
7.2
(AMPS)
0.5081
(AMP - HOURS)
24
X
0.3
7.2
0.0833
X
6.1
0.5081
REQUIRED
REQUIRED
REQUIRED
DEBATING
MINIMUM
STANDBY
ALARM
AMPERE HOUR
FACTOR O
AMP -HOUR
CAPACITY
CAPACITY
BATTERY
1.2
BATTERY
(AMP - HOURS)
(AMP - HOURS)
REQUIRED
7.2
+
0.5081
=
7.7081
X
1.2
9.2497
Design Services
For The Built
Environment
■
Atlanta Birmingham
Cincinnati
Columbus Dallas
Fort Lauderdale
Knoxville Jackson
Jacksonville Louisville
Memphis Nashville
Richmond Tampa
■
G R E S H A M
SMITH AND
P A R T N E R S
8030 Hollywood Blvd.
Suite 210
Hollywood, Florida 33024
954,981.9100
FIRM'S FLORIDA
CERT. N0,
AAP000034/CA3806
I@26000797/LC26000381
DELTA G CONSULTING
ENGINEERS. INC.
707 N.B. 3rd AVE., 3UT1'B 200
FORT LAUDF.IiDAI$, PZ.. 33304
964) 627 -1112
CA#00009181
PIT. YaR: 1QCHAIL
RA
U01 W
LL
Lo
T*-
LO F-
LJJ
IT H00
PROJECT j: 120717
w to
Q�
Lt..i o
G,
\G �Nt
� a'L
N
46
p
ST
•
48100
?fill � 19
REVISION
a. - e is'o
1 02/01/13 I Addendum #1
FIRE ALARM RISER DIAGRAM
AND BATTERY CALCULATIONS
FA3ml
FILE:
PROJECT: 29080.00
DATE: 11/29/2012