13-96 (2)-079PREACTION SYSTEM VALVE AND CABINET VICTAULIC FIRELOCKO FME -PAC: Provide a pre- assembled Preaction fire protection valve mounted completely within a 12 gauge steel cabinet. Cabinet shall be coated with red ASA -61 electrostatically applied polyester powder coating. Unit shall be UL Listed and FM- Global Approved with all materials and wiring conforming to NFPA requirements. Unit shall be provided with all necessary valves, switches, gauges, and air supply system for proper operation and shall be pre -wired to a control panel. All external electrical connections shall be accessible through an enclosure on the outside of the cabinet. Water inlet, system supply, and drain connections shall be grooved for ease of installation. Victaulic Style 745 FireLock® Fire -Pac PREACTION VALVE: Low differential, latched clapper design, black enamel coated ductile iron body conforming to ASTM A -536, grade 65- 45 -12, aluminum bronze clapper, stainless steel spring and shaft, peroxide cured EPDM diaphragm, EPDM seal, brass seat, and Nitrile seat 0-rings. Valve internal parts shall be replaceable without removing the valve from the installed position. Valve shall be externally resettable. Water working pressure is 300 psi. Does not require a separate check valve downstream of preaction valve. Valve shall be, in a Victaulic Style 745 FireLock® Fire -Pac utilizing Victaulic FireLock® NXT Series 769. The preaction valve will be an equipped with an additional Victaulic Series 705 FireLockO downstream of preaction valve for use on annual trip test and 3 -year full flow trip test. DOUBLE INTERLOCK PREACTION SYSTEM CABINET: Contractor shall provide Double Interlock Preaction System Cabinet Victaulic Series 745 FireLock Fire -Pac Part # SP0207457AB1Bl 1, which includes Victaulic FireLock NXT Series 769 Actuated Valve with Preaction Trim with Pneumatic /electrical release, a 1/6 HP compressor, PDRP -2001 release panel, and additional supervised control valve. Size: 2 ". 4' DOUBLE DETECTOR CHECK VALVE WITH TAMPER SWITCHES. 4' 9' -1 J� 4• 10' -1 4' 50' -0' R NEW 12' MAIN LINE NOTE: FOR HYDRAULIC CALCULATION REFERENCE ONLY. REFER TO CIVIL ENGINEER DRAWINGS FOR DDCV AND FDC EXACT LOCATIONS. 4' FIRE SPRINKLER RISER TO SYSTEM. SEE FLOOR PLANS FOR CONTINUATION. FIRE SPRINKLER WATER SERVICE ISOMETRIC SCALE: N.T.S. ADJUSTIBLE CLEVIS HANGER EXPANSION SHIELD (HORIZONTAL) SIDE BEAM ATTACHMENT CONCRETE ALL THREADED BEAM HANGER ROD SIDE BEAM ATTACHMENT NOTE: ADJUSTIBLE SWIVEL RING HANGER ALL THREADED HANGER ROD CONCRETE SLAB NUT ALL THREADED IN. MM HANGER ROD I 9.5 NUT SWIVEL RING 12.7 CLEVIS HANGER HANGER s ALL THREADED , HANGER ROD PIPE (4' AND 15 15 LARGER) : \ \ ^: USED IN LIEU OF LISTED CONC. 12 INSERTS WHERE APPROVED BY 12 STRUCTURAL ENGINEER 12 12 - - ADJUSTIBLE CLEVIS HANGER EXPANSION SHIELD (HORIZONTAL) SIDE BEAM ATTACHMENT CONCRETE ALL THREADED BEAM HANGER ROD SIDE BEAM ATTACHMENT NOTE: ADJUSTIBLE SWIVEL RING HANGER ALL THREADED HANGER ROD CONCRETE SLAB NUT DIAMETER OF ROD IN. MM UP TO 4' ADJUSTABLE 9.5 WEDGE SWIVEL RING 12.7 ANCHOR HANGER 1 15.9 ALL THREADED PIPE (1' TO 3') HANGER ROD 15 15 15 POWDER DRIVEN STUDS MAY BE 15 USED IN LIEU OF LISTED CONC. 12 INSERTS WHERE APPROVED BY 12 STRUCTURAL ENGINEER CENTER I -BEAM CLAMP Fl ALL THREADED HANGER ROD SELF DRILLING CONCRETE WEDGE ANCHOR STEEL I BEAM OR BAR JOIST ElTOP BEAM CLAMP W/ LOCK NUT R-ALL THREADED HANGERROD CENTER I -BEAM CLAMP TOP BEAM CLAMP HANGERS DETAILS HANGER ROD SIZES THE COMPONENTS OF HANGER ASSEMBLIES THAT DIRECTLY ATTACH TO THE PIPE OR M THE BUILDING STRUCTURE SHALL BE LISTED FOR THEIR INTENDED SERVICE PIPE SIZE DIAMETER OF ROD IN. MM UP TO 4' 3/8 9.5 5', 6' do 8' 1 1/2 12.7 10' do 12' 1 5/8 1 15.9 MAXIMUM DISTANCE BETWEEN HANGERS (Fib NOMINAL PIPE SIZE (IN) 1 1 -y4 1 -11 2 2 -1i 3 4 6 8 STEEL PIPE EXCEPT THEADED LIGHTWALL 12 12 15 15 15 15 15 15 15 THREADED LIGHTWALL STEEL PIPE 12 12 12 12 12 12 - - - CPVC 6 6.5 7 8 9 10 - - - NOTES: 1. ALL PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH NFPA -13. EACH SECTION OF PIPE SHALL HAVE NO LESS THAN ONE HANGER. 2. THE DISTANCE BETWEEN A HANGER AND THE CENTERLINE OF AN UPRIGHT SPRINKLER SHALL NOT BE LESS THAN 3 IN. 3. THE UNSUPPROTED LENGTH BETWEEN THE END SPRINKLER AND THE LAST HANGER ON BRANCH LINES SHALL NOT BE GREATER THAN 36' FOR 1' PIPE, 48' FOR 1 -1/4' PIPE AND 60' FOR 1 -1/2' OR LARGER PIPE. EXTEND BRANCH LINE AND PROVIDE ADDITIONAL HANGER WHERE REQUIRED. 4. MAXIMUM HORIZONTAL LENGTH OF AN UNSUPPORTED ARMOVER TO A SPRINKLER, SPRINKLER DROP, OR SPRING -UP SHALL NOT EXCEED 24 IN. FOR STEEL PIPE 5. WALL- MOUNTED SIDEWALL SPRINKLERS SHALL BE RESTRAINED TO PREVENT MOVEMENT PER NFPA 13. 6• HANGERS FOR MAINS SHALL BE IN ACCORDANCE WITH TABLE SHOWN ABOVE (MAXIMUM DISTANCE BETWEEN HANGERS) OR BETWEEN EACH BRANCH LINE, WHICHEVER IS THE LESSER DIMENSION. 7. RISERS SHALL BE SUPPORTED BY PIPE CLAMPS OR BY HANGERS LOCATED ON THE HORIZONTAL CONNECTIONS WITHIN 24 IN. OF THE CENTERLINE OF THE RISER. DISTANCE BETWEEN SUPPORTS FOR RISER SHALL NOT EXCEED 25 FT. 8. RISERS SUPPORTS IN MULTISTORY BUILDINGS SHALL BE PROVIDED AT THE LOWEST LEVEL, AT EACH ALTERNATE LEVEL ABOVE, ABOVE AND BELOW OFFSETS, AND AT THE TOP OF THE RISER. SUPPORTS ABOVE THE LOWEST LEVEL SHALL ALSO RESTRAIN THE PIPE TO PREVENT MOVEMENT BY AN UPWARD THRUST WHERE FLEXIBLE FITTINGS ARE USED. 9• PROVIDE SUPPLEMENTARY STEEL TRAPEZE SUPPORTS BETWEEN BUILDING STRUCTURAL MEMBERS (BAR JOISTS) AS REQUIRED TO SUPPORT PIPE HANGERS. SIZE TRAPEZE PER NFPA -13. PIPE HANGER DETAIL SCALE N.T.S. u SIGHT GLASS ORIFICE UNION 2' TEST DRAIN TO EXTERIOR SPRINKLER RISER INDICATING FLOOR CONTROL VALVE PRESSURE GAGE WATER FLOW ALARM SWITCH SPRINKLER MAIN INSPECTORS TEST VALVE AUXILIARY DRAIN VALVE 6' -8' AFF MINIMUM FLOOR CONTROL VALVE ASSEMBLY SCALE N.T.S. FIRE PROTECTION GENERAL NOTES 1. THE FIRE PROTECTION SYSTEM INSTALLATION AND MATERIALS SHALL BE IN COMPLIANCE WITH THE FLORIDA BUILDING CODE, NFPA 13, 14, 25, 101 AND ALL LOCAL FIRE CODES AND ORDINANCES. 2. SPRINKLER SYSTEM TO BE INSTALLED BY A STATE CERTIFIED FIRE PROTECTION CONTRACTOR. 3. THE WORK THAT IS TO BE DONE UNDER THIS CONTRACT INCLUDES THE FURNISHING OF ALL LABOR, MATERIALS AND EQUIPMENT, PERMITS, FEES, INSPECTIONS, TESTS, INSURANCE, ETC. REQUIRED FOR THE COMPLETION OF THE FIRE PROTECTION SYSTEM SHOWN ON THE DRAWINGS AND LISTED HEREIN. 4. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC. THEY DO NOT SHOW EVERY BEND, OFFSET OR OTHER FITTINGS WHICH MAY BE REQUIRED FOR THE INSTALLATION IN THE SPACE ALLOCATED, OR FOR COORDINATION WITH OTHER TRADES. CONTRACTOR SHALL COORDINATE WITH STRUCTURE, CEILING GRID AND ELEVATION, AND OTHER MECHANICAL, ELECTRICAL AND PLUMBING SERVICES BEFORE FABRICATING AND INSTALLING SPRINKLER PIPING. MAKE OFFSETS IN PIPING AS REQUIRED PER FIELD CONDITIONS. MAINTAIN 6' CLEARANCE BETWEEN PIPING AND 1 AND 2 HOUR RATED WALLS INCLUDING CORRIDOR WALLS. 5• ALL FIRE PROTECTION EQUIPMENT AND DEVICES SHALL BE U.L LISTED AND /OR FM APPROVED. ALL PIPING, HANGERS, SUPPORT METHOD AND SPRINKLER HEADS TO BE INSTALLED IN STRICT ACCORDANCE WITH NFPA 13 AND ALL LOCAL CODES AND ORDINANCES. 6. SPRINKLER HEADS SHALL BE U.L LISTED AND FM APPROVED AS INDICATED IN SCHEDULE RATED FOR 175 PSI WORKING PRESSURE, AND PROVIDED IN ACCORDANCE WITH SCHEDULE SHOWN ON THIS SHEET. PROVIDE HEAD GUARDS ON SPRINKLERS LOCATED IN MECHANICAL AND ELECTRICAL ROOMS. CONTRACTOR SHALL PROVIDE A WALL- MOUNTED SPRINKLER HEAD CABINET CONTAINING SPARE SPRINKLER HEADS AND WRENCHES FOR REPLACING THE HEADS IN ACCORDANCE WITH NFPA 13 (MINIMUM 2 SPRINKLER OF EACH TYPE AND TEMPERATURE RATING). 7. PROVIDE AUXILIARY DRAIN CONNECTION FOR ALL TRAPPED SECTION OF PIPING. PROVIDE CONCRETE SPLASHBLOCKS AT TEST/1DRAINS EXTERIOR DISCHARGES AS REQUIRED. CONTRACTOR SHALL PROVIDE FLUSHING CONNECTIONS AS REQUIRED. READILY REMOVABLE FITTINGS SHALL BE PROVIDED AT THE END OF ALL CROSSMAINS. ALL CROSSMAINS SHALL TERMINATE IN 1 -1/4' OR LARGER PIPE. ALL BRANCH LINES ON GRIDDED SYSTEMS SHALL BE ARRANGED TO FACILITATE FLUSHING. 8. ARE PROTECTION PIPING: STEEL PIPE (ABOVE GRADE): ASTM A53, ASTM A135 OR ASTM A795, UL LISTED, 175 PSIG WP, FM APPROVED FOR FIRE PROTECTION BLACK STEEL PIPE PIPE TO HAVE MINIMUM WALL THICKNESS IN ACCORDANCE WITH SCHEDULE 10 BLACK STEEL, THIN WALL PIPE FOR PIPE SIZES UNDER 6 INCHES, 0.134 INCHES FOR 6 INCH PIPE AND 0.188 INCHES FOR PIPE SIZES 8 AND 10 INCHES. SCREWED PIPE SHALL BE SCHEDULE 40 FOR SIZES UNDER 8 INCHES AND SCHEDULE 30 FOR SIZES 8 INCHES AND LARGER. BRANCH PIPING UP TO 2 INCHES IN SIZE SHALL BE XL, ASTM A135 THREADABLE LIGHT WALL GALVANIZED STEEL PIPING WITH SCREWED ENDS. EXTERIOR INSTALLED PIPING EXPOSED TO WEATHER SHALL BE GALVANIZED. FITTING: - WELDED: ANSI /ASME B16.25, STANDARD WEIGHT BLACK STEEL - THREADED: ANSI /ASME B16.3, CLASS 150 MALLEABLE IRON. - FLANGED: ANSI /ASME 816.1 OR B16.4, CAST IRON, 175 PSI COLD WATER PRESSURE - GROOVED: ASTM A536, DUCTILE IRON OR ASTM A47, MALLEABLE IRON APPROVED FOR USE BY THE COUPLING MANUFACTURER WITH LOW FLOW CHARACTERISTICS EQUAL TO OR BETTER THAN STANDARD FITTINGS. GROOVED FITTINGS TO BE MCTAULIC TYPE OR APPROVED EQUAL - MECHANICAL GROOVED COUPLING: UL LISTED, FM APPROVED FOR FIRE PROTECTION SERVICE, DUCTILE OR MALLEABLE IRON HOUSING, RUST INHIBITED NO -LEAD COATING, ZINC ELECTROPLATED HEAT TREATED BOLTS AND HEAVY HEX CARBON STEEL NUTS MEETING ASTM A183 STANDARDS. MECHANICAL GROOVED COUPLING FOR PIPING ONLY IS APPROVED. MECHANICAL GROOVED TEE FITTINGS ARE NOT APPROVED. JOINTS: SCREWED, WELDED, ROLL GROOVED OR FLANGED. - WELDED: AWS D10.9. - THREADED: ANSI /ASME 81.20.1 FOR 2' AND SMALLER. - FLANGED: ASTM D2000, 1/16' THICK RED RUBBER SHEET GASKETS. - GROOVED: FOR 2 -1/2' AND LARGER. GROOVE DIMENSIONS TO BE COMPATIBLE WITH LISTING OF COUPLING/FITTINGS USED AND OF THE SAME MANUFACTURER. 9• SPRINKLER HEADS SHALL BE A MINIMUM OF 18' ABOVE ANY FLOOR OBSTRUCTION, SHELVES OR CABINETS. 10. CONTRACTOR SHALL INSTALL SPRINKLERS UNDER DUCTS do OTHER OBSTRUCTIONS OVER 4 FEET IN WIDTH. 11. ALL FIRE RATED FLOOR AND WALL PENETRATIONS SHALL BE PROPERLY PROTECTED FROM FIRE, SMOKE AND WATER PENETRATION BY FILLING VOIDS BETWEEN PIPE AND WALL/FLOOR SLEEVES WITH FIRE RATED FOAM, CHASE TECHNOLOGY CORP.- CTC PR -855 OR 3M, CP -25 CAULKING OR 303 PUTTY, TO ACHIEVE SAME RATING AS WALLS OR FLOORS. 12. PRESSURE TEST ABOVE GROUND AND UNDERGROUND PIPING HYDROSTATICALLY AT 200 PSIG FOR 2 HOURS IN ACCORDANCE WITH NFPA -13. FLUSH OUT ALL PIPING IN ACCORDANCE WITH NFPA -13. PROVIDE TYPED AND COMPLETED NFPA -13 TEST CERTIFICATE FOR ABOVEGROUND PIPING. ALL WATERFLOW AND SUPERVISORY SWITCHES SHALL BE TESTED FOR PROPER OPERATION AND ANNUNCIATION. FURNISH TO OWNER'S REPRESENTATIVE ALL LITERATURE AND INSTRUCTIONS FOR THE PROPER OPERATION AND MAINTENANCE OF ANY EQUIPMENT AND DEVICES INSTALLED. 13. CONTRACTOR SHALL PROVIDE FIRE SPRINKLER SHOP DRAWINGS, CUT SHEETS FOR ALL COMPONENTS AND HYDRAULIC CALCULATIONS TO BUILDING DEPARTMENT FOR APPROVAL PRIOR INSTALLATION. CONTRACTOR SHALL BE RESPONSABLE TO REQUEST A FLOW TEST TO PERFORM HYDRAULIC CALCULATIONS. GROOVED 90 ELBOW FLEXIBLE COUPLING REFER TO FLOOR PLAN FOR FIRE RISER SIZE AND LOCATION. MAIN DRAIN VALVE - zl0 INDICATING CONTROL M 0J TO SYSTEM 300 LB. PRESSURE GAUGE O POTTER FLOW SWITCH ALARM BELL (COORDINATE ELECTRICAL CONNECTION W/ ELECTRICIAN) VALVE WITH TAMPER SWITCH. PIPE TO RUN EXPOSED ON SIDE OF BUILDING AND THEN PENETRATE BUILDING WALL saR FINISHED FLOOR UNDERGROUND SERVICE NOTE. TO DOUBLE DETECTOR CHECK VALVE ALL PIPE AND FITTINGS ABOVE GROUND ARE TO BE GALVANIZED. FIRE RISER DETAIL SCALE N.T.S. SHOP DRAWING REQUIREMENTS 1. CONTRACTOR SHALL SUBMIT 6 COPIES OF COMPLETED SHOP DRAWINGS, TOGETHER AT ONE TIME AND MUST COME THROUGH THE ARCHITECT. ALL SUBMITTALS SHALL BE MADE WITHIN 30 DAYS OF NOTICE TO PROCEED. 2. ALL SUBMITTALS MUST CLEARLY INDICATE EXACTLY WHICH ITEMS ARE BEING PROPOSED FOR USE. IF NOT, THE SUBMITTAL SHALL BE REJECTED. 3• SUBSTITUTIONS SHALL BE LIMITED TO ONE OF THE ALTERNATES LISTED IN THE CONSTRUCTION DOCUMENTS. PRODUCTS CONSIDERED M BE EQUAL SHALL BE REVIEWED AND ACCEPTED BY THE ENGINEER, ARCHITECT AND OWNER (10) DAYS PRIOR TO BID DATE. 4. THE CONTRACTOR ASSUMES ALL DESIGN RESPONSIBILITY AND ALL FINANCIAL RISKS FOR PROCEEDING PRIOR TO SHOP DRAWINGS PROCESSING, AND ON ANY ITEM OR WORK THAT IS AT VARIANCE TO THE CONSTRUCTION DOCUMENTS. 5• SHOP DRAWINGS AND SUBMITTALS FOR EACH ITEM SHALL BE REVIEWED NO MORE THAN TWICE. A THIRD SUBMITTAL ON AN ITEM MUST BE ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR OR IT SHALL BE REJECTED. 6. CIRCUMSTANCES NECESSITATING A REVISION TO THE PERMITTED DOCUMENTS NOT PROCESSED PRIOR TO INSTALLATION MAY NOT BE ACCEPTED. IF ACCEPTED IT MUST BE LEGIBLE, ACCURATE AND ACCOMPANIED BY A PURCHASE ORDER ORDER FROM THE CONTRACTOR. THE REVISION SHALL BE CHARGED TO THE CONTRACTOR AND DELIVERED TO HIM ON A C.O.D. BASIS. 7. SUBSTITUTIONS FROM THE BASE DESIGN OR VARIATIONS TO THE PERMITTED CONTRACT DOCUMENTS, WHETHER RESULTING FROM PROCESSED SHOP DRAWINGS OR NOT, THAT RESULT IN REQUIREMENTS IN LETTERS OF AUTHORIZATION AND /OR PERMIT CONTRACT DOCUMENT CHANGES MANDATED BY THE AUTHORITY HAVING JURISDICTION WILL NOT BE MADE BY THIS OFFICE UNLESS ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR, AND RELEASED ON A C.O.D. BASIS. FIRE PROTECTION LEGEND FIRE SPRINKLER SYSTEM INDEX--- - 1 .............................................................................................................................................................................................................................................................. FP1.1 FIRE SPRINKLER SYSTEM INDEX, SYMBOL LEGEND AND NOTES. 2 FP2.1 ............................... FIRST FLOOR PLAN - NEW CONSTRUCTION FIRE SPRINKLER PLAN, _ _ - _ - - - 3 FP2.2 ----------------------------------------------------------------------------------------------------------------------------------------------------------- .....------------------ - - - - -- - - .... - SECOND FLOOR PLAN - NEW CONSTRUCTION FIRE SPRINKLER RAN_" 4 FP2.3 ---------------------------------------------------------------------------------------------------------------------------------------------------------------------------- - - - - -- -- ---------------------------------------------------------------- THIRD FLOOR PLAN - NEW CONSTRUCTION FIRE SPRINKLER PLAN 5 FP2.4 ----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- - - - - -- ------ - - - - -- FOURTH FLOOR PLAN - NEW CONSTRUCTION FIRE SPRINKLER PLAN 6 -- ---------------------------- - - ---- ---------- - - - - -- ---- - - - - -- ------------------------ -- SHOP DRAWING REQUIREMENTS 1. CONTRACTOR SHALL SUBMIT 6 COPIES OF COMPLETED SHOP DRAWINGS, TOGETHER AT ONE TIME AND MUST COME THROUGH THE ARCHITECT. ALL SUBMITTALS SHALL BE MADE WITHIN 30 DAYS OF NOTICE TO PROCEED. 2. ALL SUBMITTALS MUST CLEARLY INDICATE EXACTLY WHICH ITEMS ARE BEING PROPOSED FOR USE. IF NOT, THE SUBMITTAL SHALL BE REJECTED. 3• SUBSTITUTIONS SHALL BE LIMITED TO ONE OF THE ALTERNATES LISTED IN THE CONSTRUCTION DOCUMENTS. PRODUCTS CONSIDERED M BE EQUAL SHALL BE REVIEWED AND ACCEPTED BY THE ENGINEER, ARCHITECT AND OWNER (10) DAYS PRIOR TO BID DATE. 4. THE CONTRACTOR ASSUMES ALL DESIGN RESPONSIBILITY AND ALL FINANCIAL RISKS FOR PROCEEDING PRIOR TO SHOP DRAWINGS PROCESSING, AND ON ANY ITEM OR WORK THAT IS AT VARIANCE TO THE CONSTRUCTION DOCUMENTS. 5• SHOP DRAWINGS AND SUBMITTALS FOR EACH ITEM SHALL BE REVIEWED NO MORE THAN TWICE. A THIRD SUBMITTAL ON AN ITEM MUST BE ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR OR IT SHALL BE REJECTED. 6. CIRCUMSTANCES NECESSITATING A REVISION TO THE PERMITTED DOCUMENTS NOT PROCESSED PRIOR TO INSTALLATION MAY NOT BE ACCEPTED. IF ACCEPTED IT MUST BE LEGIBLE, ACCURATE AND ACCOMPANIED BY A PURCHASE ORDER ORDER FROM THE CONTRACTOR. THE REVISION SHALL BE CHARGED TO THE CONTRACTOR AND DELIVERED TO HIM ON A C.O.D. BASIS. 7. SUBSTITUTIONS FROM THE BASE DESIGN OR VARIATIONS TO THE PERMITTED CONTRACT DOCUMENTS, WHETHER RESULTING FROM PROCESSED SHOP DRAWINGS OR NOT, THAT RESULT IN REQUIREMENTS IN LETTERS OF AUTHORIZATION AND /OR PERMIT CONTRACT DOCUMENT CHANGES MANDATED BY THE AUTHORITY HAVING JURISDICTION WILL NOT BE MADE BY THIS OFFICE UNLESS ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR, AND RELEASED ON A C.O.D. BASIS. FIRE PROTECTION LEGEND TYPE SYMBOL. TEMP DESCRITrIOM COVERAGE MANUFACTURER AND No 2 CONCEALED PENDENT SPRINKLER HEAD SIZE RATAIG FACTOR RECESSED PENDENT SPRINKLER HEAD MODEL PENDENT CONCEALED SIDEWALL SPRINKLER HEAD 155' F 5.6 STANDARD UPRIGHT SPRINKLER HEAD EXISTING SPRINKLER HEAD TO BE REMOVED F (TY3531) FIRE PROTECTION MAIN UPRIGHT 1/2' 155' F FIRE PROTECTION LINE STANDARD TYCO SERIES TY -FRB, QUICK RESPONSE W/ GLASS BULB. 1 -1/2' FIRE HOSE LINE -o PIPE DROP (TY3131) WHITE POLYESTER. S-- - - -S UPRIGHT EXISTING FIRE SPRINKLER LINE 200' F S X -i STANDARD FIRE SPRINKLER LINE TO BE REMOVED 2000 CQR GROOVED CONTROL VALVE W/TAMPER SWITCH ea (TY3131) WHITE POLYESTER. FLANGED CONTROL VALVE W/TAMPER SWITCH RECESSED PENDENT Z 155' F CHECK VALVE STANDARD 0-0 FLOW SWITCH (TY323ty STYMA ESC. WHITE O� HORIZONTAL HORIZONTAL 1 -112' FIRE HOSE RACK Do moo, 7IN? a ; z • _ .;r,.T� . - 5.6 - STANDARD HYDRAULIC REFERENCE NODE 'rT r � ' ` ' .. SIDEWALL EX (TY3331) CHROME PLATED. DENOTES EXISTING TO REMAIN H DENOTES NEW .��,IS;���i:.'- R DENOTES RELOCATED FIRE SPRINKLER HEAD SCHEDULE SYM. TYPE ORIFICE TEMP K COVERAGE MANUFACTURER AND No 2 SIZE RATAIG FACTOR AREA (WxL) MODEL PENDENT CONCEALED 1/2' 155' F 5.6 STANDARD TYCO SERIES RFII, QUICK RESPONSE W/ COVER PLATE (TY3531) UPRIGHT 1/2' 155' F 5.6 STANDARD TYCO SERIES TY -FRB, QUICK RESPONSE W/ GLASS BULB. (TY3131) WHITE POLYESTER. UPRIGHT 1/2' 200' F 5.6 STANDARD TYCO SERIES TY -FRB, QUICK RESPONSE W/ GLASS BULB. 2000 (TY3131) WHITE POLYESTER. RECESSED PENDENT 1/2' 155' F 5.6 STANDARD TYCO SERIES TY -FRB, QUICK RESPONSE W/ GLASS. BULB.- (TY323ty STYMA ESC. WHITE HORIZONTAL HORIZONTAL 1/2' 155' F 5.6 - STANDARD TYCO SERIES TY -FRB, QUICK RESPONSE W/ GLASS BULB. SIDEWALL (TY3331) CHROME PLATED. FLOW TEST DATA STATIC PRESSURE 63 PSI DATE: 11/09/12 RESIDUAL PRESSURE: 57 PSI LOCATION: 5995 SW 71ST STREET FLOW: 1,809 GPM SOUTH MIAMI, FL 33143 HYDRAULIC SIZING CRITERIA BUSINESS FACILITIES: - OCCUPANCY CLASSIFICATION: LIGHT HAZARD (OFFICES, BATHROOMS, CORRIDORS); ORDINARY HAZARD GROUP 1 (ELECTRICAL ROOM, STORAGE ROOM, JANITOR CLOSET, SHELL SPACES). - DENSITY: 0.10 GPM /SF; 0.15 GPM /SF - AREA OF APPLICATION: 1,500 SF MOST REMOTE AREA) - SPRINKLER COVERAGE: 225 SF; 130 SF. - TOTAL COMBINED HOSE STREAM DEMAND: 100 GPM; 250 GPM. G S & P 0 Design Services For The Built Environment Atlanta Birmingham Cincinnati Columbus Dallas Fort Lauderdale Knoxville Jackson Jacksonville Louisville Memphis Nashville Richmond Tampa G R E S H A M S M I T H A N D P A R T N E R S 6030 Hollywood Blvd. Suite 210 Hollywood, Florida 33024 954.981.9100 FIRM'S FLORIDA CERT. N0, AAP000034/CA3806 1B26000797/LC26000381 707 N.E. 3rd AVE.' SUITE 200 FORT LAUDERDALE, FL. 33304 (9M) 527 -1112 IL CA#00009181 PJT. YOR: 1 CEM KOO PROJECT #: 120717 d��' P.E. #4e1oo 19/10/19 FIRE SPRINKLER SYSTEM INDEX, SYMBOL LEGEND AND NOTES. FPlml FILE: PROJECT: 29080.00 DATE: 11/29/2012 �O W eti,t " OV'C, F No 2 , 0 • TgTF L1' �•� O n : 2` Rry: •Vi d��' P.E. #4e1oo 19/10/19 FIRE SPRINKLER SYSTEM INDEX, SYMBOL LEGEND AND NOTES. FPlml FILE: PROJECT: 29080.00 DATE: 11/29/2012