PLUMBING GENERAL NOTES
1. ALL WORKMANSHIP AND MATERIAL SHALL BE IN STRICT ACCORDANCE WITH APPLICABLE
LOCAL CODES, RULES AND ORDINANCES (FBC- 2010).
2. CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE HIMSELF WITH ALL
EXISTING CONDITIONS.
3. ALL MATERIAL SHALL BE NEW.
4. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST
CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE.
5. ALL EXCAVATION AND BACKFILL AS REQUIRED FOR THIS PHASE OF CONSTRUCTION SHALL
BE A PART OF THIS CONTRACT.
6. REQUIRED INSURANCE SHALL BE PROVIDED BY THE CONTRACTOR FOR PROTECTION
AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF WORK.
7. CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, INSPECTION AND TESTS.
8. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FOR THE EXACT LOCATION OF FIXTURES,
PIPING, EQUIPMENT, ETC.
9. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH
THE PROGRESS OF CONSTRUCTION. REPORT ANY DISCREPANCY TO ENGINEER /ARCHITECT
PRIOR TO BEGINING CONSTRUCTION.
10. WATER PIPING SHALL BE TYPE "L" COPPER FOR 2" AND UNDER AND TYPE "K" COPPER
FOR 2 -1/2" AND ABOVE. ALL UNDERGROUND WATER PIPING SHALL BE TYPE "K" COPPER.
TYPE "M" IN CONCEALED SPACES IS ACCEPTABLE.
11. SOIL, WASTE AND VENT PIPING SHALL BE CAST IRON NO HUB 301 -72 ABOVE GRADE.
BELOW GRADE USE SCHEDULE 40 PVC D.W.V.
CONDENSATE DRAIN LINE USE SCHEDULE 40 PVC D.W.V.
PVC SHALL NOT BE USED IN ANY MECHANICAL ROOMS OR IN ANY RETURN AIR PLENUMS . USE
COPPER PIPE.
12. INSULATE ALL HOT WATER, HOT WATER RETURN, CONDENSATE LINES, EXHAUST LINES
ABOVE GRADE AND FIRST 8' -0" OF COLD WATER LINE FROM WATER HEATER /BOILER
AS FOLLOWS:
HW SUPPLY AND RETURN - 1" THICK PREFORMED FIBERGLASS PIPE INSULATION
W/ FACTORY JACKET. CONDENSATE PIPING -44" ARMAFLEX PREFORMED. EXHAUST
PIPE - 3" THICK CALCIUM SILICATE BLOCK INSULATION W/1200 F. STEVENS
CLASS CLOTH WRAP.
13. ISOLATE COPPER PIPE FROM HANGER OR SUPPORTS WITH ISOLATOR PAD (HAIR FELT LINING).
14. DIELECTRIC COUPLINGS ARE REQUIRED BETWEEN ALL DISSIMILAR METAL IN PIPING
AND EQUIPMENT CONNECTIONS.
15. ALL FIRE RATED FLOOR AND WALL PENETRATIONS SHALL BE PROPERLY PROTECTED FROM
FIRE, SMOKE AND WATER PENETRATION BY FILLING VOIDS BETWEEN PIPE AND WALL/FLOOR
SLEEVES WITH FIRE RATED FOAM, CHASE TECHNOLOGY CORP.- CTC PR -855 OR 3M, CP -25
CAULKING OR 303 PUTTY, TO ACHIEVE SAME RATING AS WALLS OR FLOORS.
16. PROVIDE ACCESS PANELS FOR ALL CONCEALED VALVES. ACCESS PANELS IN RATED WALLS
MUST MAINTAIN THE SAME RATING AND MUST MATCH THE FINISH OF THE WALL IN
WHICH IT IS INSTALLED.
PROVIDE STAINLESS STEEL COMBINATION COVER PLATE AND CLEANOUT PLUG OR ACCESS
PANEL FOR ALL WALL CLEANOUTS.
IT FURNISH AND INSTALL APPROVED P.D.I. SHOCK ARRESTORS ON MAIN LINES. REFER TO
SCHEDULE IN THIS SHEET.
18. ALL AUTOMATIC ELECTRIC WATER HEATERS SHALL MEET THE STANDARDS OF THE LATEST
ENERGY EFFICIENCY CODE.
19. ALL INSTALLATIONS SHALL MEET THE STANDARDS OF THE LOCAL AUTHORITY AND
HEALTH DEPARTMENT.
20• OFF SET VENT PIPES 10' -0' AWAY FROM ANY FRESH AIR INTAKE OR DOOR OPENING
21. PROVIDE 1/2" TRAP PRIMER LINE FOR ALL FLOOR DRAINS FROM THE NEAREST PLUMBING
FIXTURE OR USE AUTOMATIC TRAP PRIMER AS PPP P1 -500 WITH INTEGRAL BACKFLOW
PREVENTER AND VACUUM BREAKER.
2
P1.1
PLUMBING SYMBOL LEGEND
MARK
SYMBOL
DESCRIPTION
COLD
WATER
SANITARY LINE
- - - - -
VENT LINE
- 3101-
SAFEWASTE LINE
-
COLD WATER LINE
--
HOT WATER LINE
- - - HWR
HOT WATER RETURN
SD
STORM DRAIN LINE
CD
CONDENSATE LINE
FM
FORCE MAIN LINE
9 DN
PIPE DOWN
-'-'� UP
PIPE UP
- --D4--
GATE VALVE
VALVE W/ EL -451 TRANSF., TOILET SEAT MODEL #SC534
FLOOR PENETRATION
ABOVE COUNTER LAVATORY
(AT TOILET ROOMS)
WATER HAMMER ARRESTOR
® RD
ROOF DRAIN
OD
OVERFLOW ROOF DRAIN
® GD
GARAGE DRAIN
® AD
AREA DRAIN
® CO
CLEAN OUT
jIL, VTR
VENT THRU ROOF
RWL
RAIN WATER LEADER
-ID FD
FLOOR DRAIN
-DQ� -• HB
HOSE BIBB W/ SHUT -OFF VALVE
ZURN MODEL FD- 2322 -ST
AND VACUUM BREAKER
ZURN 1343 OR EQUAL
P do T RELIEF VALVE
WALL VALLL VACUUM SHUT-OFF
MODEL #K-T1 1838, W/ W�OUNT VALVE.�K 1830 -INA
VEHAND
COUNTER TOP SINK
(LOUNGE ROOM)
ZURN MODEL Z1350 (ENCASED)
1/2"
OR EQUAL
WL
XX
RAIN WATER LEADER RISER
CW
XX
COO) WATER RISER
NO
NORMALLY OPEN
NC
NORMALLY CLOSED
U/G
UNDER GROUND
P1.1
FIXTURE CONNECTION SCHEDULE
MARK
DESCRIPTION
WASTE
COLD
WATER
HOT
WATER
MANUFACTURE AND MODEL
ACCESSORIES
W
WATER CLOSET TANK TYPE
(FLOOR MOUNTED)
4"
1/2"
__ -
KOHLER "ESCALE" TWO -PIECE TOILET
MODEL #K -3588, ELONG. BOWL (1.6 GPM)
TOILET SEAT "E70004 ", BOWL "K- 43080, TANK "K -4472"
W_ 1
ADA WATER CLOSET FLUSH VALVE
(FLOOR MOUNTED)
40
SEE ROOF PLAN
--- ___
TOTO MODEL CT705ELN(G), ELONGATED
SLOAN "ROYAL OPTIMA" MODEL 111- 1.28HWS FLUSHOM.
GARAGE DRAIN
SEE PLANS
- - --
ZURN MODEL Z505 OR EQUAL
P2.3 SECOND FLOOR PLAN NEW CONSTRUCTION PLUMBING PLAN.
FRONT BOWL (1.28 GPM)
VALVE W/ EL -451 TRANSF., TOILET SEAT MODEL #SC534
L -1
ABOVE COUNTER LAVATORY
(AT TOILET ROOMS)
1 1/4"
1/2"
1/2"
KOHLER "ESCALE" ABOVE COUNTER
KOHLER "PURIST" TOUCHLESS WALL MOUNTED FAUCET TRIM,
TRENCH DRAIN
SEE PLANS
- - --
ABT POLYDRAIN TRENCH DRAIN
8
BATH. SINK MODEL #K -19047 (0.5 GPM)
MODEL #K- T11837, W/ WAL MOUNT VALVE #K- 11830 -NA
SK
ADA COUNTER R00� TOP SINK
1 1/2"
1/2"
1/2"
KOHLER COUNTER
M DEL
FAUCET
ZURN MODEL FD- 2322 -ST
P3.1 DOMESTIC WATER PIPING ISOMETRIC
WATER SUPPLY
P do T RELIEF VALVE
IN"K #K-19047 GPM)
MODEL #K-T1 1838, W/ W�OUNT VALVE.�K 1830 -INA
SK -1
COUNTER TOP SINK
(LOUNGE ROOM)
1 1/2"
1/2"
1/2"
KOHLER "UNDERTONE" SINGLE BOWL
KOHLER "ELATE" KITCHEN SINK FAUCET
VALVE.
POTTED TO BE
USEDYAT
3/4" RELIEF DRAIN LINE
WITH THE WATER HEATER
S. STEEL SINK MODEL #K- 3335 -NA
MODEL #K- 13963 -CP (MAX. 1.8 GPM)
J.SK
JANITOR SINK
1 1/2"
1/2"
1/2"
ADVANCE TABCO MODEL #9 -OP -40
T &S FAUCET MODEL B- 0665 -BSTR
D/W
DISHWASHER
1"IN
- --
1/2'
FIXTURE AS SPECIFIED BY ARCH / OWNER
DRAIN VALVE
EWC
ADA ELECTRIC WATER COOLER
1 1/4"
1/2"
- --
OASIS MODEL M8CREE
1/2" SUPPLY PIPES, MCGIURE ANGLE STOPS AND
DELETE PROVIDED
3/4" PLYWOOD BELOW
THE E
WITH WATER HEATER
ADJUSTABLE *Pw TRAP .
FLOOR
WATER HEA-. ER -,HERMOSTA
PAN AS PLATFCRAI I
SHALL BE SET AT 110'F
NOTES:
1. ALL FIXTURE AND FAUCETS SWILL COMPLY WITH MIAMI WATER
CONSERVATION REGULATIONS SECTION 8 -31, TABLE 604.4
2. ALL WALL HUNG PLUMBING FIXTURES SHALL COMPLY WITH
F.B.0 -2010 SECTION 2318.1.15 & 2517.5.1.1
3• INSULATE PER A.D.A. ALL EXPOSED HANDICAP LAVATORIES DRAIN
PIPING AND HOT & COLD STOP AND SUPPLIES.
COVERS SHALL BE SOFT, REMOVABLE AND UPC APPROVED.
MANUFACTURE: PLUMBEREX HANDY- SHIELD OR PRO- SERIES.
8 MIXING VALVE DETAIL
P1.1 NO SCALE
f-
I
TEMPERED WATER LINE I
(TEMP NOT TO EXCEED 110*
MIXING VALVE LEONARD
MODEL 7M -30
OR EQUAL
3 /41NLET/3 /4'OU7LET
COLD WATER SUPPLY U
HOT WATER SUPPLY LINE
3
P1.1
DRAIN SCHEDULE
No
DESCRIPTION
DRAIN
CW
REMARKS
FD
FLOOR
3"
1/2"
MODEL Z415B OR EQUAL
3to6
TOILET ROOMS)
1/8
B
TRAP PRIMER
RD
ROOF DRAIN
SEE ROOF PLAN
- - --
ZURN MODEL Z100 OR EQUAL
GD
GARAGE DRAIN
SEE PLANS
- - --
ZURN MODEL Z505 OR EQUAL
P2.3 SECOND FLOOR PLAN NEW CONSTRUCTION PLUMBING PLAN.
TRENCH DRAIN
SEE PLANS
- - --
ABT TRENCH FORMER SYSTEM
TD
FIRST FLOOR
CHECK VALVE
THERMAL EXPANSION TANK p
MODEL TFX -12 OR EQUAL
TRENCH DRAIN
SEE PLANS
- - --
ABT POLYDRAIN TRENCH DRAIN
8
P2.6 FOURTH FLOOR PLAN NEW CONSTRUCTION SANITARY PLAN.
THIRD FLOOR
BALL VALVE (TYP.)
HOT WATER TO
SAM•
SYSTEM MODEL 2512F OR EQUAL
AD
AREA DRAIN
3"
- - --
ZURN MODEL FD- 2322 -ST
P3.1 DOMESTIC WATER PIPING ISOMETRIC
WATER SUPPLY
P do T RELIEF VALVE
OR EQUAL APPROVED
PD
PLANTER DRAIN
3"
- -- (ZU
N ODEL Z415B OR EQ AL
P3.3 STORM DRAINAGE PIPING ISOMETRIC
ELECTRIC WATER HEATER
DELETE IF PROVIDED
VALVE.
POTTED TO BE
USEDYAT
3/4" RELIEF DRAIN LINE
WITH THE WATER HEATER
1
PLANTPER) ,
4
P1.1
SLOPE OF
HORIZ. DRAINAGE PIPE
P1.1
SIZE (inches)
P.D.I. DESIGNATION
MINIMUM SLOPE (inch per foot)
FIXTURE UNITS
2-1/2 or less
CONNECTION
1/4
SIOUX CHIEF 652 -A
3to6
FULL FLOW BALL VALVES AND
1/8
B
8 or larger
12 -32
1/16
TABLE 704.1 OF THE FLORIDA
PLUMBING CODE 2010
5
131.1
WATER HAMMER ARRESTOR
SCHEDULE
P1.1
P.D.I. DESIGNATION
MANUF. & MODEL
FIXTURE UNITS
VACUUM RELIEF VALVE
CONNECTION
A
SIOUX CHIEF 652 -A
1 -11
FULL FLOW BALL VALVES AND
1/2"
B
SIOUX CHIEF 653-B
12 -32
3/4"
C
SIOUX CHIEF 654-C
33-60
1"
SIOUX CHIEF SHOCK ARRESTORS APPROVED FOR INSTALLATION WITH NO
ACCESS DOOR REQUIRED. CONFORMS TO ANSI /ASSE 1010 STANDARDS.
6 TYPICAL CONDENSATE DRAIN TRAP
P1.1 SCALE: N.T.S.
18" YIN
27 MIN
KM
DRAIN PAN
-•I- I DRAIN LINE SHALL BE AT LEAST THE
YIN
3'
S&AS THE NIPPLE ON THE
PLUMBING INDEX
TYPICAL ELECTRICAL WATER HEATER DETAIL
DRAWING
P1.1
NO SCALE
1
P1.1 PLUMBING INDEX, NOTES, SCHEDULES AND DETAILS
VACUUM RELIEF VALVE
SHUT -OFF VALVE
PROVIDE WITH QUARTER TURN
INUNE CIRCULATING PUMP TO BE
*I
"TACO"
2
P1.2 PLUMBING DETAILS
FULL FLOW BALL VALVES AND
A
A MODEL 1108, 120V,
1,A, 1/12 HP.
3 /4" CW
3
P2.1 FIRST FLOOR PLAN NEW CONSTRUCTION DOMESTIC WATER
4
P2.2 FIRST FLOOR PLAN NEW CONSTRUCTION SANITARY PLAN.
WATTS SERIES PLT -5
5
P2.3 SECOND FLOOR PLAN NEW CONSTRUCTION PLUMBING PLAN.
(2.1 GALLONS)
6
P2.4 THIRD FLOOR PLAN NEW CONSTRUCTION PLUMBING PLAN.
HEAT TRAP*
CHECK VALVE
THERMAL EXPANSION TANK p
7
P2.5 FOURTH FLO ^vR PLAN NEW CONSTRUCTION DOMESTIC WATER
HOT WATER
WATTS SERIES PLT -5
8
P2.6 FOURTH FLOOR PLAN NEW CONSTRUCTION SANITARY PLAN.
(2.1 GALLONS)
BALL VALVE (TYP.)
HOT WATER TO
SAM•
9
P2.7 ROOF LEVEL PLAN NEW CONSTRUCTION PLUMBING PLAN
10
P3.1 DOMESTIC WATER PIPING ISOMETRIC
WATER SUPPLY
P do T RELIEF VALVE
11
P3.2 SANITARY PIPING ISOMETRIC
TO HEATER.
12
P3.3 STORM DRAINAGE PIPING ISOMETRIC
ELECTRIC WATER HEATER
DELETE IF PROVIDED
VALVE.
FULL
FULL SIZE
3/4" RELIEF DRAIN LINE
WITH THE WATER HEATER
PROVIDE A HARD COPPER RELIEF VALVE,
TERMINATE OVER SERVICE SINK
ELECTRIC WATER
DISCHARGE AT EXTERIOR BUILDING
SHOP DRAWING REQUIREMENTS
1. SHOP DRAWINGS, SHALL BE SUBMITTED COMPLETE, TOGETHER AT ONE TIME AND MUST COME
THROUGH THE ARCHITECT. ALL SUBMITTALS SHALL BE MADE WITHIN 30 DAYS OF NOTICE TO
PROCEED.
2. ALL SUBMITTALS MUST CLEARLY INDICATE EXACTLY WHICH ITEMS ARE BEING PROPOSED FOR
USE. IF NOT, THE SUBMITTAL SHALL BE REJECTED.
3. SUBSTITUTIONS SHALL BE LIMITED TO ONE OF THE ALTERNATES LISTED IN THE
CONSTRUCTION DOCUMENTS. PRODUCTS CONSIDERED TO BE EQUAL SHALL BE REVIEWED AND
ACCEPTED BY THE ENGINEER, ARCHITECT AND OWNER (10) DAYS PRIOR TO BID DATE.
4. THE CONTRACTOR ASSUMES ALL DESIGN RESPONSIBILITY AND ALL FINANCIAL RISKS FOR
PROCEEDING PRIOR TO SHOP DRAWINGS PROCESSING, AND ON ANY ITEM OR WORK THAT IS
AT VARIANCE TO THE CONSTRUCTION DOCUMENTS.
5. SHOP DRAWINGS AND SUBMITTALS FOR EACH ITEM SHALL BE REVIEWED NO MORE THAN
TWICE. A THIRD SUBMITTAL ON AN ITEM MUST BE ACCOMPANIED BY A PURCHASE ORDER
FROM THE CONTRACTOR OR IT SHALL BE REJECTED.
6. CIRCUMSTANCES NECESSITATING A REVISION TO THE PERMITTED DOCUMENTS NOT
PROCESSED PRIOR TO INSTALLATION MAY NOT BE ACCEPTED. IF ACCEPTED IT MUST BE
LEGIBLE, ACCURATE AND ACCOMPANIED BY A PURCHASE ORDER ORDER FROM THE
CONTRACTOR. THE REVISION SHALL BE CHARGED TO THE CONTRACTOR AND DELIVERED TO
HIM ON A C.O.D. BASIS.
7. SUBSTITUTIONS FROM THE BASE DESIGN OR VARIATIONS TO THE PERMITTED CONTRACT
DOCUMENTS, WHETHER RESULTING FROM PROCESSED SHOP DRAWINGS OR NOT, THAT RESULT
IN REQUIREMENTS IN LETTERS OF AUTHORIZATION AND /OR PERMIT CONTRACT DOCUMENT
CHANGES MANDATED BY THE AUTHORITY HAVING JURISDICTION WILL NOT BE MADE BY THIS
OFFICE UNLESS ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR, AND
RELEASED ON A C.O.D. BASIS.
8. CONTRACTOR SHALL SUBMIT 5 COPIES OF SHOP DRAWINGS.
9
TYPICAL ELECTRICAL WATER HEATER DETAIL
P1.1
NO SCALE
COLD WATER SUPPLY
VACUUM RELIEF VALVE
SHUT -OFF VALVE
PROVIDE WITH QUARTER TURN
INUNE CIRCULATING PUMP TO BE
*I
"TACO"
F_
314" HW WATTS MODEL 36-M1
CD
FULL FLOW BALL VALVES AND
A
A MODEL 1108, 120V,
1,A, 1/12 HP.
3 /4" CW
FINISHED CEILING
UNIONS (TYPICAL)
THERMAL EXPANSION TANK
WATTS SERIES PLT -5
CHECK VALVE
(2.1 GALLONS)
HEAT TRAP*
CHECK VALVE
THERMAL EXPANSION TANK p
3/4" HW
HOT WATER
WATTS SERIES PLT -5
SHUT -OFF VALVE UNERCULATION
(2.1 GALLONS)
BALL VALVE (TYP.)
HOT WATER TO
SAM•
HEAT TRAP*
HEAT TRAP (TYP.) * I
- -
UNION
WATER SUPPLY
P do T RELIEF VALVE
SHUT -OFF VALVE
TO HEATER.
P & T RELIEF
P & T RELIEF LINE
ELECTRIC WATER HEATER
DELETE IF PROVIDED
VALVE.
FULL
FULL SIZE
3/4" RELIEF DRAIN LINE
WITH THE WATER HEATER
PROVIDE A HARD COPPER RELIEF VALVE,
TERMINATE OVER SERVICE SINK
ELECTRIC WATER
DISCHARGE AT EXTERIOR BUILDING
DRAIN VALVE
HEATER
6"MIN. A.F.F
BY MANUFACT.
SET HEATER WITHIN 24" X 24" X 4"
DRAIN VALVE
DEEP GALVANIZED SHEET METAL DRAIN
I
PAN (24 GAGE MINIMUM)
DELETE PROVIDED
3/4" PLYWOOD BELOW
THE E
WITH WATER HEATER
WATER , I
pD N
FLOOR
WATER HEA-. ER -,HERMOSTA
PAN AS PLATFCRAI I
SHALL BE SET AT 110'F
I
2"x 2 "x 1/8" ANGLE IRON SIZE I I
PROVIDE A 3Z4"HARD COPPER RELIEF VALVE,
DISCHARGE 2-MIN. ABOVE MOP SINK
(2 BRACKETS REQ'D.) I
FOR AIR GAP COMPLY
MOUNT HEATER AS in SAFETY PAN DRAIN LINE I
HIGH AS POSSIBLE TERMINATE OVER SERVICE SINK
1 "DRAIN LINE TERMINATED
1 2` ANCHOR BOLT OR I I
/
2'MIN. ABOVE MOP SINK
FOR AIR GAP COMPLY
EXPANSION BOLT (2 PER
BRACKET)
WATER HEATER
SCHEDULE
WATER HEATER SCHEDULE
I.D.
MANUFACTURER
MODEL
GALS
VOLTAGE
KW
PHASE
EFF
REMARKS
I.D.
MANUFACTURER
MODEL
GALS
VOLTAGE
KW
PHASE
EFF
REMARKS
EYM -1
LOCHNVAR ETT05OKK
50
208
4.5
1
0.92
FIRST FLOOR
EWH-2
L•OCHINVAR
MT03OKK
30
208
___j_
4.5
1
1.93
FOURTH FLOOR
::1
• i
a
Design Services
For The Built
Environment
E
Atlanta Birmingham
Cincinnati
Columbus Dallas
Fort Lauderdale
Knoxville Jackson
Jacksonville Louisville
Memphis Nashville
Richmond Tampa
7
G R E S H A M
S M I T A N D
P A R T N E R S
6030 Hollywood Blvd.
Suite 210
Hollywood, Florida 33024
9 54.9 81.9100
FIRM'S FLORIDA
CERT. NO.
AAP000034/CA3806
IB26000797/LC26000381
707 N.E. 3rd AVE., SUITE 200
FORT IAUDERDALB. FL. 33304
(954) 527 -1112
CA#00009181
PIT. YGR: IMMUEL H00
PROJECT f: 120717
REVISION
I No. - Date - Revision I
02/01/13 1 Addendum #1
PLUMBING INDEX, NOTES,
SCHEDULE AND DETAILS.
P1.1
FILE:
PROJECT: 29080.00
DATE: 11/29/2012
C.
0 D
Q
s
:
c' 0
CD
�4E04GE
JUAN,
• Pf4O 1VA .
•P.E.
SE #48100
DATE: t7 02/01/13
REVISION
I No. - Date - Revision I
02/01/13 1 Addendum #1
PLUMBING INDEX, NOTES,
SCHEDULE AND DETAILS.
P1.1