13-96 (2)-045P� 1 I PLUMBING GENERAL NOTES
1. ALL WORKMANSHIP AND MATERIAL SHALL BE IN STRICT ACCORDANCE WITH APPLICABLE
LOCAL CODES, RULES AND ORDINANCES (FBC- 2010).
2 CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE HIMSELF WITH ALL
EXISTING CONDITIONS.
3. ALL MATERIAL SHALL BE NEW.
4. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST
CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE.
5. ALL EXCAVATION AND BACKFILL AS REQUIRED FOR THIS PHASE OF CONSTRUCTION SHALL
BE A PART OF THIS CONTRACT.
6. REQUIRED INSURANCE SHALL BE PROVIDED BY THE CONTRACTOR FOR PROTECTION
AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF WORK.
7. CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, INSPEC11ON AND TESTS.
8. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FOR THE EXACT LOCA11ON OF FIXTURES,
PIPING, EQUIPMENT, ETC.
9. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH
THE PROGRESS OF CONSTRUCTION. REPORT ANY DISCREPANCY TO ENGINEER /ARCHITECT
PRIOR TO BEGINING CONSTRUCTION.
10. WATER PIPING SHALL BE TYPE "L" COPPER FOR 2" AND UNDER AND TYPE "K" COPPER
FOR 2 -1/2" AND ABOVE. ALL UNDERGROUND WATER PIPING SHALL BE TYPE "K" COPPER.
TYPE "M" IN CONCEALED SPACES IS ACCEPTABLE.
11. SOIL, WASTE AND VENT PIPING SHALL BE CAST IRON NO HUB 301 -72 ABOVE GRADE.
BELOW GRADE USE SCHEDULE 40 PVC D.W.V.
CONDENSATE DRAIN LINE USE SCHEDULE 40 PVC D.W.V.
PVC SHALL NOT BE USED IN ANY MECHANICAL ROOMS OR IN ANY RETURN AIR PLENUMS USE
COPPER PIPE.
12. INSULATE ALL HOT WATER, HOT WATER RETURN, CONDENSATE LINES, EXHAUST LINES
ABOVE GRADE AND FIRST 8' -0" OF COLD WATER LINE FROM WATER HEATER /BOILER
AS FOLLOWS:
HW SUPPLY AND RETURN - 1" THICK PREFORMED FIBERGLASS PIPE INSULATION
W/ FACTORY JACKET. CONDENSATE PIPING -Y4" ARMAFLEX PREFORMED. EXHAUST
PIPE - 3" THICK CALCIUM SILICATE BLOCK INSULATION W/1200 F. STEVENS
CLASS CLOTH WRAP.
13. ISOLATE COPPER PIPE FROM HANGER OR SUPPORTS WITH ISOLATOR PAD (HAIR FELT LINING).
14. DIELECTRIC COUPLINGS ARE REQUIRED BETWEEN ALL DISSIMILAR METAL IN PIPING
AND EQUIPMENT CONNECTIONS.
15. ALL FIRE RATED FLOOR AND WALL PENETRATIONS SHALL BE PROPERLY PROTECTED FROM
FIRE, SMOKE AND WATER PENETRATION BY FILLING VOIDS BETWEEN PIPE AND WALL /FLOOR
SLEEVES WITH FIRE RATED FOAM, CHASE TECHNOLOGY CORP.- CTC PR -855 OR 3M, CP -25
CAULKING OR 303 PUTTY, TO ACHIEVE SAME RATING AS WALLS OR FLOORS.
16. PROVIDE ACCESS PANELS FOR ALL CONCEALED VALVES. ACCESS PANELS IN RATED WALLS
MUST MAINTAIN THE SAME RATING AND MUST MATCH THE FINISH OF THE WALL IN
WHICH IT IS INSTALLED.
PROVIDE STAINLESS STEEL COMBINATION COVER PLATE AND CLEANOUT PLUG OR ACCESS
PANEL FOR ALL WALL CLEANOUTS.
17. FURNISH AND INSTALL APPROVED P.D.I. SHOCK ARRESTORS ON MAIN LINES. REFER TO
SCHEDULE IN THIS SHEET.
18. ALL AUTOMATIC ELECTRIC WATER HEATERS SHALL MEET THE STANDARDS OF THE LATEST
ENERGY EFFICIENCY CODE.
19. ALL INSTALLATIONS SHALL MEET THE STANDARDS OF THE LOCAL AUTHORITY AND
HEALTH DEPARTMENT.
20• OFF SET VENT PIPES 10' -0" AWAY FROM ANY FRESH AIR INTAKE OR DOOR OPENING
21. PROVIDE 1/2" TRAP PRIMER LINE FOR ALL FLOOR DRAINS FROM THE NEAREST PLUMBING
FIXTURE OR USE AUTOMATIC TRAP PRIMER AS PPP P1 -500 WITH INTEGRAL BACKFLOW
PREVENTER AND VACUUM BREAKER.
P1.1
PLUMBING SYMBOL LEGEND
MARK
SYMBOL
DESCRIPTION
COLD
WATER
SANITARY LINE
- - - - -
VENT LINE
-�
SAFEWASTE LINE
-
COLD WATER LINE
--
HOT WATER LINE
- - - HWR
HOT WATER RETURN
SD
STORM DRAIN LINE
CD
CONDENSATE LINE
FM
FORCE MAIN LINE
- DN
PIPE DOWN
-� UP
PIPE UP
-DQ-
GATE VALVE
VALVE W/ EL -451 TRANSF., TOILET SEAT MODEL #SC534
FLOOR PENETRATION
ABOVE COUNTER LAVATORY
WATER HAMMER ARRESTOR
® RD
ROOF DRAIN
OD
OVERFLOW ROOF DRAIN
® GD
GARAGE DRAIN
in AD
AREA DRAIN
® CO
CLEAN OUT
jjL, VTR
VENT THRU ROOF
RWL
RAIN WATER LEADER
FD
FLOOR DRAIN
-04�- HB
HOSE BIBB W/ SHUT -OFF VALVE
ZURN MODEL FD- 2322 -ST
AND VACUUM BREAKER
BALL VALVE (TYP.)
ZURN 1343 OR EQUAL
®
WALL HYDRANT W SHUT -OFF
W/ WALLM MOUNT VALVE #K-11830-NA
VALVE AND VACUUM BREAKER
COUNTER TOP SINK
ZURN MODEL Z1350 (ENCASED)
1/2"
OR EQUAL
L
w-
RAIN WATER LEADER RISER
CW
XX
COLD WATER RISER
NO
NORMALLY OPEN
NC
NORMALLY CLOSED
U/G
UNDER GROUND
Pl.l
FIXTURE CONNECTION SCHEDULE
MARK
DESCRIPTION
WASTE
COLD
WATER
HOT
WATER
MANUFACTURE AND MODEL
ACCESSORIES
W
WATER CLOSET TANK TYPE
(FLOOR MOUNTED)
4"
1/2"
- --
KOHLER " ESCALE" TWO -PIECE TOILET
MODEL #K -3588, ELONG. BOWL (1.6 GPM)
TOILET SEAT "E70004 ", BOWL "K- 4308 ", TANK "K -4472"
W -1
ADA WATER CLOSET FLUSH VALVE
4
»
1
- --
TOTO MODEL CT705ELN(G), ELONGATED
SLOAN "ROYAL OPTIMA" MODEL 111- 1.28HWS FLUSHOM.
GARAGE DRAIN
(FLOOR MOUNTED)
- - --
ZURN MODEL Z505 OR EQUAL
P2.3 SECOND FLOOR PLAN NEW CONSTRUCTION PLUMBING PLAN.
FRONT BOWL (1.28 GPM)
VALVE W/ EL -451 TRANSF., TOILET SEAT MODEL #SC534
L -1
ABOVE COUNTER LAVATORY
1 1/4"
1/2"
1/2"
KOHLER "ESCALE" ABOVE COUNTER
KOHLER "PURIST" TOUCHLESS WALL MOUNTED FAUCET TRIM,
TRENCH DRAIN
(AT TOILET ROOMS)
- - --
ABT POLYDRAIN TRENCH DRAIN
8
BATH. SINK MODEL #K -19047 (0.5 GPM)
MODEL #K- T11837, W/ WAL MOUNT VALVE #K- 1130 -NA
SK
TOP SINK
1 1/2"
1/2"
1/2"
COUNTER
ODEL
"MEMIORSO I
ZURN MODEL FD- 2322 -ST
(EXAM ROOM)
BALL VALVE (TYP.)
HOT
LINE
BATH. SINKS #K-19047 GPM)
W/ WALLM MOUNT VALVE #K-11830-NA
SK -1
COUNTER TOP SINK
1 1/2"
1/2"
1/2"
KOHLER "UNDERTONE" SINGLE BOWL
KOHLER "ELATE" KITCHEN SINK FAUCET
UNION
(LOUNGE ROOM)
WATER SUPPLY
P do T RELIEF VALVE
S. STEEL SINK MODEL #K- 3335 -NA
MODEL #K- 13963 -CP (MAX. 1.8 GPM)
J.SK
JANITOR SINK
1 1/2"
1/2"
1/2"
ADVANCE TABCO MODEL #9 -OP -40
T &S FAUCET MODEL B- 0665 -BSTR
D/W
DISHWASHER
1 "I.W
- --
1/2"
FIXTURE AS SPECIFIED BY ARCH / OWNER
EWC
ADA ELECTRIC WATER COOLER
1 1/4"
1/2"
- --
OASIS MODEL M8CREE
1/2" SUPPLY PIPES, MCGIURE ANGLE STOPS AND
ADJUSTABLE
PROVIDE A HARD COPPER RELIEF VALVE,
SET HEATER WITHIN 24" X 24" X 4"
DRAIN VALVE
P TRAP.
DEEP GALVANIZED SHEET METAL DRAIN 1
6 0MIN. A.F.F
PAN (24 GAGE MINIMUM)
-
NOTES:
1. ALL FIXTURE AND FAUCETS SHALL COMPLY WITH MIAMI WATER
CONSERVATION REGULATIONS SECTION 8 -31, TABLE 604.4
2. ALL WALL HUNG PLUMBING FIXTURES SHALL COMPLY WITH
F.B.0 -2010 SECTION 2318.1.15 & 2517.5.1.1
3. INSULATE PER A.D.A. ALL EXPOSED HANDICAP LAVATORIES DRAIN
PIPING AND HOT & COLD STOP AND SUPPLIES.
COVERS SHALL BE SOFT, REMOVABLE AND UPC APPROVED.
MANUFACTURE: PLUMBEREX HANDY- SHIELD OR PRO- SERIES.
8 MIXING VALVE DETAIL
NO SCALE
� IIO
TEMPERED WATER LINE I
(TEMP NOT TO EXCEED 110') dm
4- MIXING VALVE LEONARD
MODEL TM -30
OR EQUAL
3/41NLET/3/4 "OUTLET
140
COLD WATER SUPPLY UNE
HOT WATER SUPPLY LINE
3
P1.1
DRAIN SCHEDULE
No
DESCRIPTION
DRAIN
CW
REMARKS
FD
FLOOR DRAIN
3"
1/2"
ZURN MODEL Z415B OR EQUAL
3to6
(TOILET ROOMS)
1/8
B
PROVIDE TRAP PRIMER
RD
ROOF DRAIN
SEE ROOF PLAN
- - --
ZURN MODEL Z100 OR EQUAL
GD
GARAGE DRAIN
SEE PLANS
- - --
ZURN MODEL Z505 OR EQUAL
P2.3 SECOND FLOOR PLAN NEW CONSTRUCTION PLUMBING PLAN.
TRENCH DRAIN
SEE PLANS
- - --
ABT TRENCH FORMER SYSTEM
TD
FIRST FLOOR
(2.1 GALLONS)
MODEL TFX -12 OR EQUAL
TRENCH DRAIN
SEE PLANS
- - --
ABT POLYDRAIN TRENCH DRAIN
8
P2.6 FOURTH FLOOR PLAN NEW CONSTRUCTION SANITARY PLAN.
THIRD FLOOR
THERMAL EXPANSION TANK 0
SYSTEM MODEL 2512F OR EQUAL
AD
AREA DRAIN
3"
- - --
ZURN MODEL FD- 2322 -ST
P3.1 DOMESTIC WATER PIPING ISOMETRIC
BALL VALVE (TYP.)
HOT
LINE
OR EQUAL APPROVED
PD
PLANTER DRAIN
3"
--
ZURN MODEL Z415B OR EQUAL
P3.3 STORM DRAINAGE PIPING ISOMETRIC
UNION
POTTED PLANTS TO BE
WATER SUPPLY
P do T RELIEF VALVE
1
U(ONLY AT TR.
4
Pl.l
SLOPE OF
HORIZ. DRAINAGE PIPE
0
SIZE (inches)
P.D.I. DESIGNATION
MINIMUM SLOPE (inch per foot)
FIXTURE UNITS
2-1/2 or less
CONNECTION
1/4
SIOUX CHIEF 652 -A
3to6
Lit
�e
1/8
B
8 or larger
12 -32
1/16
TABLE 704.1 OF THE FLORIDA
PLUMBING CODE 2010
5
P1.1
WATER HAMMER ARRESTOR
SCHEDULE
0
P1.1
P.D.I. DESIGNATION
MANUF. & MODEL
FIXTURE UNITS
COLD WATER SUPPLY
CONNECTION
A
SIOUX CHIEF 652 -A
1 -11
Lit
�e
1/2"
B
SIOUX CHIEF 653 -B
12 -32
FULL FLOW BALL VALVES AND
3/4"
C
SIOUX CHIEF 654-C
33 -60
1"
SIOUX CHIEF SHOCK ARRESTORS APPROVED FOR INSTALLATION WITH NO
ACCESS DOOR REQUIRED. CONFORMS TO ANSI /ASSE 1010 STANDARDS.
TYPICAL CONDENSATE DRAIN TRAP
SCALE: N.T.S.
' * ; . 136
18" MIN
2" MIN
OUT
DRAIN PAN
-i- \--DRAIN LINE SHALL BE AT LEAST THE
3" MIN SbyhNS&AS THE NIPPLE ON THE
PLUMBING INDEX
TYPICAL
DRAWING
0
P1.1
1
P1.1 PLUMBING INDEX, NOTES, SCHEDULES AND DETAILS
COLD WATER SUPPLY
VACUUM RELIEF VALVE
SHUT -OFF VALVE
2
P1.2 PLUMBING DETAILS
Lit
�e
PROVIDE WITH QUARTER TURN
1
1 A "TACO" MODEL # 110B, 120V,
3
P2.1 FIRST FLOOR PLAN NEW CONSTRUCTION DOMESTIC WATER
FULL FLOW BALL VALVES AND
60Hz, 10, 1/12 HP.
4
P2.2 FIRST FLOOR PLAN NEW CONSTRUCTION SANITARY PLAN.
5
P2.3 SECOND FLOOR PLAN NEW CONSTRUCTION PLUMBING PLAN.
7
WATTS SERIES PLT -5
6
P2.4 THIRD FLOOR PLAN NEW CONSTRUCTION PLUMBING PLAN.
(2.1 GALLONS)
7
P2.5 FOURTH FLOOR PLAN NEW CONSTRUCTION DOMESTIC WATER
..
o
8
P2.6 FOURTH FLOOR PLAN NEW CONSTRUCTION SANITARY PLAN.
CHECK VALVE
THERMAL EXPANSION TANK 0
9
P2.7 ROOF LEVEL PLAN NEW CONSTRUCTION PLUMBING PLAN
WATTS SERIES PLT -5
10
P3.1 DOMESTIC WATER PIPING ISOMETRIC
BALL VALVE (TYP.)
HOT
LINE
11
P3.2 SANITARY PIPING ISOMETRIC
WATER TO
HEAT TRAP �
HEAT TRAP (TYP.) * -
12
P3.3 STORM DRAINAGE PIPING ISOMETRIC
UNION
/
WATER SUPPLY
P do T RELIEF VALVE
SHUT -OFF VALVE J
TO HEATER.
ELECTRIC WATER HEATER
�G DELETE IF PROVIDED
P & T RELIEF
SHOP DRAWING REQUIREMENTS
1. SHOP DRAWINGS, SHALL BE SUBMITTED COMPLETE, TOGETHER AT ONE TIME AND MUST COME
THROUGH THE ARCHITECT. ALL SUBMITTALS SHALL BE MADE WITHIN 30 DAYS OF NOTICE TO
PROCEED.
2. ALL SUBMITTALS MUST CLEARLY INDICATE EXACTLY WHICH ITEMS ARE BEING PROPOSED FOR
USE. IF NOT, THE SUBMITTAL SHALL BE REJECTED.
3. SUBSTITUTIONS SHALL BE LIMITED TO ONE OF THE ALTERNATES LISTED IN THE
CONSTRUCTION DOCUMENTS. PRODUCTS CONSIDERED TO BE EQUAL SHALL BE REVIEWED AND
ACCEPTED BY THE ENGINEER, ARCHITECT AND OWNER (10) DAYS. PRIOR TO BID DATE.
4. THE CONTRACTOR ASSUMES ALL DESIGN RESPONSIBILITY AND ALL FINANCIAL RISKS FOR
PROCEEDING PRIOR TO SHOP DRAWINGS PROCESSING, AND ON ANY ITEM OR WORK THAT IS
AT VARIANCE TO THE CONSTRUCTION DOCUMENTS.
5. SHOP DRAWINGS AND SUBMITTALS FOR EACH ITEM SHALL BE REVIEWED NO MORE THAN
TWICE. A THIRD SUBMITTAL ON AN ITEM MUST BE ACCOMPANIED BY A PURCHASE ORDER
FROM THE CONTRACTOR OR IT SHALL BE REJECTED.
6. CIRCUMSTANCES NECESSITATING A REVISION TO THE PERMITTED DOCUMENTS NOT
PROCESSED PRIOR TO INSTALLATION MAY NOT BE ACCEPTED. IF ACCEPTED IT MUST BE
LEGIBLE, ACCURATE AND ACCOMPANIED BY A PURCHASE ORDER ORDER FROM THE
CONTRACTOR. THE REVISION SHALL BE CHARGED TO THE CONTRACTOR AND DELIVERED TO
HIM ON A C.O.D. BASIS.
7. SUBSTITUTIONS FROM THE BASE DESIGN OR VARIATIONS TO THE PERMITTED CONTRACT
DOCUMENTS, WHETHER RESULTING FROM PROCESSED SHOP DRAWINGS OR NOT, THAT RESULT
IN REQUIREMENTS IN LETTERS OF AUTHORIZATION AND /OR PERMIT CONTRACT DOCUMENT
CHANGES MANDATED BY THE AUTHORITY HAVING JURISDICTION WILL NOT BE MADE BY THIS
OFFICE UNLESS ACCOMPANIED BY A PURCHASE ORDER FROM THE CONTRACTOR, AND
RELEASED ON A C.O.D. BASIS.
8. CONTRACTOR SHALL SUBMIT 5 COPIES OF SHOP DRAWINGS.
9
TYPICAL
ELECTRICAL WATER HEATER DETAIL
707.14.'
P1.1
NO SCALE
FL. 33k4
COLD WATER SUPPLY
VACUUM RELIEF VALVE
SHUT -OFF VALVE
INUNE CIRCULATING PUMP TO BE
3/4 7 HW WATTS MODEL 36-M1
Lit
�e
PROVIDE WITH QUARTER TURN
1
1 A "TACO" MODEL # 110B, 120V,
3/4" CW
FINISHED CEILING
FULL FLOW BALL VALVES AND
60Hz, 10, 1/12 HP.
UNIONS (TYPICAL)
THERMAL EXPANSION TANK
7
WATTS SERIES PLT -5
CHECK VALVE
(2.1 GALLONS)
..
o
3/4" HW
HEAT TRAP*
CHECK VALVE
THERMAL EXPANSION TANK 0
HOT WATER
WATTS SERIES PLT -5
SHUT -OFF VALVE RECIRCULATION
(2.1 GALLONS) 0
BALL VALVE (TYP.)
HOT
LINE
I
XQ
WATER TO
HEAT TRAP �
HEAT TRAP (TYP.) * -
0
SYSTEM. �-
UNION
/
WATER SUPPLY
P do T RELIEF VALVE
SHUT -OFF VALVE J
TO HEATER.
ELECTRIC WATER HEATER
�G DELETE IF PROVIDED
P & T RELIEF
3/4w P & T RELIEF LINE
WITH THE WATER HEATER
VALVE.
FULL SIZE
3/4" RELIEF DRAIN LINE
TERMINATE OVER SERVICE SINK
ELECTRIC WATER
AIR GAP FITTING
HEATER
3
BY�MANUFACT.
PROVIDE A HARD COPPER RELIEF VALVE,
SET HEATER WITHIN 24" X 24" X 4"
DRAIN VALVE
DISCHARGE AT EXTERIOR BUILDING
DEEP GALVANIZED SHEET METAL DRAIN 1
6 0MIN. A.F.F
PAN (24 GAGE MINIMUM)
-
DELETE IF PROVIDED
3/4" PLYWOOD BELOW I
WITH THE WATER HEATER
WATER HEATER DRAIN t I
FLOOR
WATER HEATER THERMOSTAT
PAN AS PLATFORM 1
SHALL BE SET AT 110 F
2 "X 2 "X 1 /8" ANGLE IRON SIZE 11. I
ANGLE 1
PROVIDE A 314 "HARD COPPER RELIEF VALVE.
DISCHARGE 2 MIN. ABOVE MOP SINK
2 BRACKETS ) I I
FOUNT
FOR AIR GAP COMPLY
HEATER 1" SAFETY PAN DRAIN LINE
53" A.F.F. TERMINATE OVER SERVICE SINK
1 "DRAIN LINE TERMINATED
I
2 1/2" ANCHOR BOLT OR I
2"MIN. ABOVE MOP SINK
FOR AIR GAP COMPLY
EXPANSION BOLT (2 PER
BRACKET)
WATER HEATER SCHEDULE
WATER HEATER SCHEDULE
I.D.
MANUFACTURER
MODEL
GALS
VOLTAGE
KW
PHASE
EFF
REMARKS
I.D.
MANUFACTURER
MODEL
GALS.
VOLTAGE
KW
PHASE
EFF
REMARKS
EWH -1
LOCHINVAR E1TO50KK
50
208
4.5
1
0.92
FIRST FLOOR
EWH -2
LOCHINVAR
ES1030KK
30
208
4.5
1
0.93
FOURTH FLOOR
G S cC P
0
Design Services
For The Built
Environment
Atlanta Birmingham
Cincinnati
Columbus Dallas
Fort Lauderdale
Knoxville Jackson
Jacksonville Louisville
Memphis Nashville
Richmond Tampa
G R E S H A M
SMITH AND
P A R T N E R S
6030 Hollywood Blvd.
Suite 210
Hollywood, Florida 33024
954.981.9100
FIRM'S FLORIDA
CERT. NO.
AAP000034 /CA3806
IB26000797/LC26000381
0
GEORGE SANJUAN, P.E.
FLORIDA LICENSE #46100
DATE: 03/29/13
REVISION
No. - Date - Revision
Q02/01/13
Q03/15/13
707.14.'
d du 1
City Comments Response
FOft D
FL. 33k4
(954).527-N
4610
:CA' / P000918
PTT. MGR: MICHAEL M %� ST
F
Lit
�e
PROJECT #: 1207177'i .�
P
is
o0
Ljj m
wQ
00
o
O
rn =
XQ
LO
LL.I
0
GEORGE SANJUAN, P.E.
FLORIDA LICENSE #46100
DATE: 03/29/13
REVISION
No. - Date - Revision
Q02/01/13
Q03/15/13
d du 1
City Comments Response
Q3
03/29/13 I
y ri nt e on
I
jam\
PLUMBING INDEX, NOTES,
SCHEDULE AND DETAILS.
FILE:
PROJECT: 29080.00
DATE: 11/29/2012