13-96 (2)-041TYPICAL TURNING
VANE ON ALL
ELBOWS
CORNER
ANGLE
I
I II I
L- I'-
TYPICAL DUCTWORK
ELBOW TURNING
4 VANE DETAIL
M5.1 SCALE: N.T.S.
CAULK WATER TIGHT ALL
AROUND LOUVER. SEE
ARCH. PLANS FOR ALL
DETAILS OF WATERPROOFING CBS EXT. WALL
PLENUM
/-DUCT
�- BIRDSCREEN
r'Iii
FLOW
INTAKE OR EXHAUST
LOUVER SHALL BE 4"
DEEP LOUVER WITH 30'
DRAINABLE BLADES.
EXTRUDED ALUMINUM
W /BIRD SCREEN. Y 12" MINIMUM OR
COORDINATE COLOR LAS SHOWN ON
WITH ARCHITECT. FLOOR PLAN
CCHANNEL TYPE SHOWN
FLANGE TYPE IS SIMILAR
OUTSIDE AIR INTAKE
OR EXHAUST AIR LOUVER_ DETAIL
SCALE: N.T.S.
METAL PIPE
FILL GAP COMPLETELY
2 OR 3 HOUR FIRE RATED
HANGER SIZE
OR CONDUIT
AROUND PIPE WITH CAULK CONCRETE BLOCK WALL-,,
IN x 1/16"
1' (25mm) DEPTH
2 OR 3 HOUR FIRE
RATED CONCRETE
CP-25 OR PUTTY 303
FLUSH TO SURFACE OF
SUPPORTING
MATERIAL
AROUND
CAULK CP -25 OR
PUTTY 303 WITHIN
FLOOR SLAB
OVER 10 SF
SLAB (SEE NOTE 3)
1 4' -0"
ASSRQ'D
WALL
DUCT
DEPTH 1/2'
MAXIMUM D/8
1 ,
METAL PIPE
OFFSET ALLOWED IN
LAST D INCHES TO
OR CONDUIT
DEVICE WHERE D IS
THE INTERNAL FLEX
COVER CAULK SURFACE
DIAMETER
•. -
E OR
MIN. 1" WIDE 22 GAUGE GALV. STEEL STRAP
HANGER AS PER SMACNA FIG. 3 -10
VOLUME DAMPER W/ LOCKING
ER
QUADRANT & STANDOFF
SUPPORTING MATERIAL
BACKER ROD UNTIL
ADJUSTABLE STAIN. STL
MATCH FLEX DUCT
SUCH AS FIBERGLASS
CURBED (24-72 HOURS)
DUCT SEALER
INSULATE TOP PANEL OF DIFFUSER OR FULLY HINGED & GASKETED
f�
`• f GRILLE- TAPE TO CEIUNG GRID WITH SILVER
INSULATION, BACKER ROD
(TO PREVENT SAGGING
-;
FOIL TAPE
DOOR FOR DAMPERS IN
__..._._--- _- _- _____;
OR SAFING. NEED ONLY
ENOUGH TO SUPPORT
OF CAULK IF IT
WEIGHT OF CP -25 OR
OCCURS) (SEE NOTE 5
PUTTY 303
SECTION VIEW
SECTION VIEW
1 WRAP OF 2' (50mm)
NOTES:
WIDE FS-195 WRAP/
I. FOR CONCRETE BLOCK WALLS, CENTER CAULK CP -25 OR PUTTY
WOOD OR
STRIP FLUSH TO EXTERIOR
303 WITHIN WALL WITH DAMMING ON BOTH SIDES.
STEEL- STUD
GYPSUM PANEL (SEE
2. RECOMMENDATIONS BASED ON PRODUCY PERFORMANCE PER ASTM
NOTE 1)
E -814 (UL 1479) FIRE TEST AND UL CLASSIFICATION FIRE STOP
SYSTEMS 49,33 AND 91.
3. WET INSTALLED DEPTH OF CAULK CP -25 OR PUTTY 303 DEPENDS
NSULATED METAL PIPE
TYPE & SIZE OF PIPE:
WET DEPTH PIPE SIZE FIRE RATING
2 HOUR RATED WALL
112" (13mm) MAX 8' 203mm 2 HRS.
1 (25mm) MAX 8' (152mm) 3 HRS.
2 LAYERS OF 5/8'
(16mm) THICK
4. UP TO 40X SHRINKAGE OF CP -25 OR PUTTY 303 IS ACCEPTABLE
GYPSUM WALL BOARD
AFTER WET DEPTH INSTALLATION.
OR CONCRETE BLOCK
SEAL ENTIRE //RIDGE &))
5. OPTIONS TO MASKING TAPE TO PREVENT SAGGING:
WALL (SEE NOTE 4
INSTALL ADDITIONAL DAMMING MAEERIAL OVER PRODUCT TO
LAYER OF CAULK(CPm25
HOLpA.
B. REMOVE PRODUCT FROM CONTAINER AND ALLOW TO AIR CURE
IN SMALL BATCHES FOR 12 HOURS. THEN HAND FORM INTO OPENING.
8. WHEN ANNULAR SPACE EXCEEDS % (19mm), A 28 AWG METAL
SEC -nON VIEW
COVER PLATE MUST BE MECHANICALLY SECURED ATOP THE 3M
FIRE BARRIER APPUCATION, OR TIGHTLY PACK A
NON - COMBUSTIBLE DAMMING MATERIAL ATOP INSTALLED CAULK OR
PUTTY. COVER PLATE NOT REQUIRED FOR 2 HOUR RATING UP TO 1W
(47.6mm) ANNULAR SPACE.
3
PIPE SLEEVE DETAIL
M5.1
SCALE: N.T.S.
TYPICAL INSTALLATION DETAILS
(A) RETAINING ANGLES:
MINIMUM 1 -1/2" X 1 -1/2' X 0.054 (16 GA.)
RETAINING ANGLES MUST OVERLAP STRUCTURE OPENIP
1" MINIMUM AND COVER CORNERS OF OPENINGS AS SI
(B) CLEARANCE: 1/8" PER LINEAR FOOT
BOTH DIMENSIONS
(C) STEEL SLEEVE:
(D) APPROVED FIRE DAMPER (CURTAIN OR BLADE TYPE)
(E) SECURE RETAINING ANGLES TO SLEEVE
NO. 10 STEEL SCREWS
(F) SECURE DAMPER TO SLEEVE ON 8" CENTERS WITH
NO. 10 STEEL SCREWS
(G) CONNECT DUCT TO SLEEVE WITH BREAKAWAY
CONNECTION
(H) FULLY GASKETED HINGED CAM LOCK FIRE DAMPER
ACCESS DOOR. LABEL "FIRE DAMPER ACCESS'.
NOTE:
ALL SMOKE AND FIRE DAMPERS (UNDER
16" IN HEIGHT) SHALL BE OVERSIZED
BY 2" AND TRANSITIONED DOWN TO
DUCT SIZE TO MAXIMIZE FREE AREA. 2 "X3 -X1,
BY HVAC, wn I INUUUb
ALL SIDES I TP. OF 2
USE ONE OF AVAUABLE POWER INPUTS HOIL.
1 2 10 12 14 I 1) PROVIDE EQUIPMENT AND
LABOR SHOWN ON DETAILS X&X
IF REQ (NO EXISTING FIRE
20 ALARM SYSTEM).
2) FOR WIRING OF AUXILIARY
VA iDEVICES REFER TO
MANUFACTURERS INSTALLATION
INSTRUCTIONS OR CONTACT
AUXIUARY ALARM CONTROL CONTACTS MANUFACTURER
3) FOR WIRING OF AUALIARY DEVICES
AUDIBLEf1ASIBLE ALARM R TO MANUFACTURERS
EQUIVIIIFFNNT TO SIMPLEX ALAR 15 16 17 18 19 20 INSTALLATION INSTRUCTIONS OR
MODEL 0093 AT 120 VAC CONTACT MANUFACTURER
FOR STAND ALONE APPLICATIONS I NO C NO NO C NO
FOR COMPLIANCE TO NFPA 90A. 1
LOCATE IN NORMALLY OCCUPIED l
AREA OF PREMISES I AUXILIARY ALARM CONTROL CONTACTS 1
CONTRACTOR SHALL SUBMIT SHOP SHOWN IN STANDBY CONTACTS TRANSFER
DRAWINGS TO BUILDING DEPARTMENT DURING ALARM AS INDICATED BY THE ARROWS
WITH TESTING PROCEDURES PRIOR I FIRE ALARM PANEL INTERFACE CONTACTS
TO STARTING ANY WORK. I 8 &-/IN-0--o 9
TROUBLE CONTACTS
LOW VOLTAGE ALARM INITIATION CONTACTS CLOSED IN STANDBY
DURING IN ALARM AS INDICATED BY THE ARROWS OPEN WHILE DETECTOR
® l 5 ( + )ALARM SIGNAL I REMOVED AND DURING
° 6 RESET
® ( -) AUXILIARY POWER
7 ( +) AUALIARY POWER
TROUBLE
POWER 15 CONTACTS I DUCT DETECTOR EQUIVALENT
° _____________� TO SIMPLEX 12098 AT 120 VAC
A/C DUCT SMOKE DETECTOR - WIRING DETAIL
> > (WITHOUT FIRE ALARM CONTROL PANED
DUCT THRU WALL FIRE DAMPER DETAIL
SYSTEM
CONTROL
POWER OR
THERMOSTAT
SCALE: N.T.S.
FAN FAN
CONTROL FAN
15 16 17 18 19 20
NOT JONJONOLO
AUXILIARY ALARM CONTROL CONTACTS
SHOWN IN STANDBY CONTACTS TRANSFER
DURING ALARM AS INDICATED BY THE ARROWS
HVAC FAN CONTROL WIRING
FOR SYSTEM SHUT -DOWN
SCALE: N.T.S.
I1 1/2• 28 GAGE 1
BAND CLAMP WITH
STRAP
DUCT
MAY
:H TO
E OR
NPER
I)
ICAL)
rmr.
NUT
ARM
ROUND DAMPER
FlG. C
o
BEARING OPTION
ROD ;ONTINUOUS
ON 2 W.G. CLASS
AND ON .A L DAMPERS
OVER 12 DIA. ELEVATION DUCT
TWO BLADE ARRANGEMENT
EL-2
1/2' QUADRANT DUCT
1 V2' ROD
CLEARANCE
19' TO 48" AROUND
NOTE: OVER 12' HIGH USE
MULTIPLE BLADES.
ELia
END BEEAARIING
3/8' QUADRANT DUCT
3/8' PIN
DUCT SIZE
HANGER SIZE
12' MAX.
UP THRU 2 SF
IN x 1/16"
CLEARANCE
2 THRU 4 SF
ALL
UP TO 18'
AROUND
1' x 1/8"
EL -A
OVER 10 SF
1 1' x 1 8'
1 4' -0"
ASSRQ'D
DUCT
DEPTH 1/2'
MAXIMUM D/8
1 ,
ELEVATION
FIG. A OR B
OFFSET ALLOWED IN
INSIDE
END BEARING
REQUIRED ON 3' W.G.
CLASS DUCT AND OVER.
OPTIONAL FOR OTHERS
2 VOLUME DAMPER
M5.1 SCALE: N.T.S.
22 GA HANGER STRAPS
DUCT SIZE
HANGER SIZE
MAX SPACING
UP THRU 2 SF
IN x 1/16"
8' -0'
2 THRU 4 SF
1' x 1/8'
8' -0'
4 THRU 10 SF
1' x 1/8"
6' -0'
OVER 10 SF
1 1' x 1 8'
1 4' -0"
IroTe
1 1 HANf2R BALD Q
nwE IS W rAL JWP
NOTE:
HANG DUCTS ACCORDING
TO SMACNA STANDARDS
TYPICAL HANG(
STRAP AND S/
HANGING DETA.6
SECURE WIRE
TVDlf.AI 7 GAD
METHOD OF HANGING DUCTS DETAIL
SCALE: N.T.S.
UPPER ATTACHMENT MAX. SAG 1/20' PER FOOT
PER SMACNA
BETWEEN SUPPORT POINTS
CEILING.
DUCT SEALER AT 45" TAKEOFF
FLOW
TITUS -XX RETURN
OR ROUND BELLMOUTH COLLAR
AIR LINEAR DIFFUSER.
ROUND BELLMOUTH COLLAR
0
CONNECTION TO MAIN
2' -p- 2' ---� N SIDE OF DUCT
SLIPPY AIR DUCT
MAXIMUM D/8
1 ,
OFFSET ALLOWED IN
LAST D INCHES TO
DEVICE WHERE D IS
THE INTERNAL FLEX
DIAMETER
•. -
MIN. 1" WIDE 22 GAUGE GALV. STEEL STRAP
HANGER AS PER SMACNA FIG. 3 -10
VOLUME DAMPER W/ LOCKING
ER
QUADRANT & STANDOFF
NECK SIZE TO
ADJUSTABLE STAIN. STL CLAMP
ADJUSTABLE STAIN. STL
MATCH FLEX DUCT
Cep
SIZE INDICATED
DUCT SEALER
INSULATE TOP PANEL OF DIFFUSER OR FULLY HINGED & GASKETED
f�
`• f GRILLE- TAPE TO CEIUNG GRID WITH SILVER
CEILING 24" X 24" ACCESS
-;
FOIL TAPE
DOOR FOR DAMPERS IN
__..._._--- _- _- _____;
---------------------------------------------------- - - - - -- --
NON- ACCESSIBLE CEILINGS
CEILING (T -BAR
SHOWN. GYP. AIR DISTRIBUTION DEVICE LAYIN SHOWN. '
BOARD SIMILAR) SURFACE MOUNT SIMILAR
(`COTES
1. FLEXIBLE DUCTS SHALL BE ONE PIECE AND SHALL NOT BE SPLICED TOGETHER.
2. EXTEND FLEXIBLE DUCT INSULATION TO DUCT /DIFFUSER PANEL INSULATION AND SEAL WITH MASTIC.
3. FLEXIBLE AIR DUCT SHALL NOT EXCEED 8 FT. WHEN EXTENDED. ELBOW RADIUS SIZED FOR NO LESS THAN R/D - 1.0.
4. MAXIMUM SAG OF FLEXIBLE DUCT BETWEEN SUPPORTS SWILL BE 1/2" PER FOOT.
5. MINIMUM 1' WIDE 22 GAUGE GALVANIZED STRAP HANGER WITH HEMMED EDGES IN ACCORDANCE WITH SMACNA FIGURE B -10.
� FLEXIBLE DUCT TAKEOFF DETAIL
SCALE: N.T.S.
FROM FLOOR
DUCT GAUGE
28, 26
24,22,20
18,16
ALLOWABLE
LOAD PER
FASTENER
25 LBS.
35 LBS.
50 LBS.
X = 1", Y = 2" ADD OTHERS
TO ACCOMIDATE LOAD. MINIMUM
OF 3 ON 24" WIDE DUCT
ADD ALONG SIDES NEAREST
ANCHORS.
DUCT RISER SUPPORTS
SCALE: N.T.S.
FLOW DUCT COLLAR
SOUND INSULATI ❑N
TITUS® INSULATED HIGH
RECTANGULAR LINEAR
ADAPTER,
SUSPENDED TECHZ ❑NE ®CEILING.
TITUS ®ML -37 OR 38
LINEAR DIFFUSER.
5 LINEAR DIFFUSER MOUNTING DETAIL
5.1 SCALE: N.T.S.
(A) RETAINING ANGLES: MINIMUM 1)r X 1Y2" X 0.054 (16 GA)
(B) CLEARANCE W PER LINEAR FOOT BOTH DIMENSIONS DUCT MAY ATTACH TO
(C) STEEL SLEEVE: SLEEVE THICKNESS NOT TO BE LESS THAN DUCT GAGE SLEEVE OR DAMPER
DUCT DIMENSION (13) MINIMUM SLEEVE
(IN DIAMETER OR GAGE THICKNESS UNCOATED (A)
RECTANGULAR STEEL (E)
DIMENSION)
12" DOWN 26 .018"
13" - 30" 24 .024"
31' - 54" 22 .030" (C)
55" - 84" 20 .036" (D)
85" - UP 18 .047" (H) (F)
(D) FIRE DAMPER (RUSKIN STYLE G FOR GRILLES)
(E) SECURE RETAINING ANGLES TO SLEEVE ONLY ON 8"
CENTERS WITH; 0 DUCT
1. Xz" LONG WELDS. OR
2. Y4" BOLTS AND NUTS. OR -
3. NO. 10 STEEL SCREWS. OR I
4. MINIMUM V STEEL RIBETS
(F) SECURE DAMPER TO SLEEVE ON 8" CENTER WITH:
1. V LONG WELDS. OR
2. Y4" BULTS AND NUTS IN HOLES PROVIDED. OR
3. NO. 10 STEEL SCREWS. OR
4. MINIMUM We' STEEL RIBETS (G) TYPICAL
(G) SECURE DUCT TO SLEEVE WITH A CONNECTION AS SHOWN
(H) STEEL SUPPLY/ RETURN AIR GRILLE
T
VERTICAL POSITION IS SHOWN; OBSERVE AIR FLOW
DIRECTION SPECIFIED PROVIDE ACCESS DOORS AS
PLAIN "S" SUP SPECIFIED FOLLOW INSTALLATION INSTRUCTION FOR
FUSIBLE LINKS RETAINING ANGLES MUST LAP
STANDING S STRUCTURAL OPENING 1" MINIMUM AND COVER
CORNERS OF OPENINGS. ANGLES MUST NOT BE
JOINTS SHALL BE CONSISTENT WITH DESIGNATIONS ATTACHED TO EACH OTHER AT CORNERS.
FOR DUCT PRESSURE CLASSIFICATION.
9 FIRE DAMPER INSTALLATION DETAILS
SCALE: N.T.S.
G S & p 'I
Design Services
For The Built
Environment
■
Atlanta Birmingham
Cincinnati
Columbus Dallas
Fort Lauderdale
Knoxville Jackson
Jacksonville Louisville
Memphis Nashville
Richmond Tampa
■
G R E S H A M
SMITH AN D
P A R T N E R S
6030 Hollywood Blvd.
Suite 210
Hollywood, Florida 33024
954.98'1.9100
FIRM'S FLORIDA
CERT. NO.
AAP000034/CA3806
IB26000797/LC26000381
ar � �
}_ cn
�
m
_
48MIM
r ft d []
If I
m Q
I-, Ij
V
'
"
Lo
Ca
Q LO �
LLl 0
kfvL
N100
cc
K A F t�4
O •' p P•'
l000k* 148100
DAT r 112YtVA
REVISION
No. - Date - Revision
MECHANICAL
DETAILS PLAN 1
M5.1
FILE:
PROJECT: 29080.00
DATE: 1 1 /29/201 2
SUSPENDED TECHZONE®
CEILING.
®MLR
FLOW
TITUS -XX RETURN
AIR LINEAR DIFFUSER.
R/A LINEAR DIFFUSER
FLOW DUCT COLLAR
SOUND INSULATI ❑N
TITUS® INSULATED HIGH
RECTANGULAR LINEAR
ADAPTER,
SUSPENDED TECHZ ❑NE ®CEILING.
TITUS ®ML -37 OR 38
LINEAR DIFFUSER.
5 LINEAR DIFFUSER MOUNTING DETAIL
5.1 SCALE: N.T.S.
(A) RETAINING ANGLES: MINIMUM 1)r X 1Y2" X 0.054 (16 GA)
(B) CLEARANCE W PER LINEAR FOOT BOTH DIMENSIONS DUCT MAY ATTACH TO
(C) STEEL SLEEVE: SLEEVE THICKNESS NOT TO BE LESS THAN DUCT GAGE SLEEVE OR DAMPER
DUCT DIMENSION (13) MINIMUM SLEEVE
(IN DIAMETER OR GAGE THICKNESS UNCOATED (A)
RECTANGULAR STEEL (E)
DIMENSION)
12" DOWN 26 .018"
13" - 30" 24 .024"
31' - 54" 22 .030" (C)
55" - 84" 20 .036" (D)
85" - UP 18 .047" (H) (F)
(D) FIRE DAMPER (RUSKIN STYLE G FOR GRILLES)
(E) SECURE RETAINING ANGLES TO SLEEVE ONLY ON 8"
CENTERS WITH; 0 DUCT
1. Xz" LONG WELDS. OR
2. Y4" BOLTS AND NUTS. OR -
3. NO. 10 STEEL SCREWS. OR I
4. MINIMUM V STEEL RIBETS
(F) SECURE DAMPER TO SLEEVE ON 8" CENTER WITH:
1. V LONG WELDS. OR
2. Y4" BULTS AND NUTS IN HOLES PROVIDED. OR
3. NO. 10 STEEL SCREWS. OR
4. MINIMUM We' STEEL RIBETS (G) TYPICAL
(G) SECURE DUCT TO SLEEVE WITH A CONNECTION AS SHOWN
(H) STEEL SUPPLY/ RETURN AIR GRILLE
T
VERTICAL POSITION IS SHOWN; OBSERVE AIR FLOW
DIRECTION SPECIFIED PROVIDE ACCESS DOORS AS
PLAIN "S" SUP SPECIFIED FOLLOW INSTALLATION INSTRUCTION FOR
FUSIBLE LINKS RETAINING ANGLES MUST LAP
STANDING S STRUCTURAL OPENING 1" MINIMUM AND COVER
CORNERS OF OPENINGS. ANGLES MUST NOT BE
JOINTS SHALL BE CONSISTENT WITH DESIGNATIONS ATTACHED TO EACH OTHER AT CORNERS.
FOR DUCT PRESSURE CLASSIFICATION.
9 FIRE DAMPER INSTALLATION DETAILS
SCALE: N.T.S.
G S & p 'I
Design Services
For The Built
Environment
■
Atlanta Birmingham
Cincinnati
Columbus Dallas
Fort Lauderdale
Knoxville Jackson
Jacksonville Louisville
Memphis Nashville
Richmond Tampa
■
G R E S H A M
SMITH AN D
P A R T N E R S
6030 Hollywood Blvd.
Suite 210
Hollywood, Florida 33024
954.98'1.9100
FIRM'S FLORIDA
CERT. NO.
AAP000034/CA3806
IB26000797/LC26000381
ar � �
}_ cn
�
m
_
48MIM
r ft d []
If I
m Q
I-, Ij
V
'
"
Lo
Ca
Q LO �
LLl 0
kfvL
N100
cc
K A F t�4
O •' p P•'
l000k* 148100
DAT r 112YtVA
REVISION
No. - Date - Revision
MECHANICAL
DETAILS PLAN 1
M5.1
FILE:
PROJECT: 29080.00
DATE: 1 1 /29/201 2