GENERAL NOTES:
—SPACE SENSORS LOCATED AS PER PLANS.
—FIRE ALARM CONTACTS TO BE PROVIDED BY DIV.16 ELECTRICAL CONTRACTOR. WIRE FROM LOCAL FIRE
ALARM CONTACTS TO THE MOTOR SHALL BE BY DIVISION 16 FOR FAN SHUTDOWN.
— MOTORIZED DAMPERS BY OTHERS.
—SD PROVIDED BY OTHERS AND INSTALLED BY F/A CONTRACTOR
—VAV MANUFACTURE TO PROVIDE FACTORING MOUNTING AND WIRING OF DDC VAV BOX CONTROLLER
— DIV.16 ELECTRICAL CONTRACTOR TO PROVIDE 120 OR 277 VAV POWER TO ALL VAV BOXES.
—ALL FIELD CONTROLLER DEVICES , INCLUDING RTUs AND VAVs CONTROLLERS, MUST COMMUNICATE USING BACNET MS/TP.
NO FIELD CONTROLLER DEVICE CAN BE SUPPORTED BY ANOTHER FIELD DEVICE FOR COMMUNICATION.
— SYSTEM OPERATOR MUST BE ABLE TO COMMUNICATE WITH ALL FIELD CONTROLLER DEVICES WITHOUT SUPPORT FROM ANOTHER FIELD DEVICE.
BASIS OF DESIGN AMERICAN AUTO— MATRIX: APPROVED EQUAL KAL —TECH CONTROLS / DAVE DOWLING / 954 - 464 -6922.
AI
DMCKM cE TEWMPAMM
s
AR
L--E F/
fl.� a RM
• S 75• Id DMAIM Alt (A ACMMR A SPACE TEMPERATURE 000�� c AI
DO HEUM STAGO
N
VAV BOX WITH HEATING CONTROL DIAGRAM
VAV COOLING AND HEATING SEQUENCE OF OPERATIONS:
RUN CONDITIONS — SCHEDULED: THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:
• OCCUPIED MODE: THE UNIT SHALL MAINTAIN;
A 74-F (ADJ.) COOLING SETPOINT AND A 70-F (ADJ.)HEATING SETPOINT
• UNOCCUPIED MODE (NIGHT SET BACK): THE UNIT SHALL MAINTAIN:
A 82F (ADJ.) COOLING SETPOINT AND A 65F (ADJ.) HEATING SETPOINT.
ZONE SETPOINT ADJUST /OPTIMAL START/UNOCCUPIED OVERRIDE: THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING
AND COOLING SETPOINTS AT THE ZONE SENSOR.THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START —UP. THIS ALGORITHM
SHALL MINIMIZE THE UNOCCUPIED WARM —UP OR COOL —DOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF
SCHEDULED OCCUPIED PERIOD.A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE
UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL OF THE UNIT SHALL
AUTOMATICALLY RETURN TO THE SCHEDULE.
FLOW CONTROL: THE UNIT SHALL MAINTAIN ZONE SETPOINTS BY CONTROLLING THE AIRFLOW THROUGH ONE OF THE FOLLOWING:
OCCUPIED:
• WHEN ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE DAMPER SHALL MODULATE BETWEEN THE MINIMUM OCCUPIED
AIRFLOW (ADJ.) AND THE MAXIMUM COOLING AIRFLOW (ADJ.) UNTIL THE ZONE IS SATISFIED.
• WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING SETPOINT AND THE HEATING SETPOINT, THE ZONE DAMPER SHALL MAINTAIN THE
MINIMUM REQUIRED ZONE VENTILATION (ADJ.).
• WHEN ZONE TEMPERATURE IS LESS THAN ITS HEATING SETPOINT, THE CONTROLLER SHALL ENABLE HEATING TO MAINTAIN THE ZONE
TEMPERATURE AT ITS HEATING SETPOINT.
UNOCCUPIED:
• WHEN THE ZONE IS UNOCCUPIED THE ZONE DAMPER SHALL CONTROL TO ITS MINIMUM UNOCCUPIED AIRFLOW (ADJ.).
• WHEN THE ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE DAMPER SHALL MODULATE BETWEEN THE MINIMUM
UNOCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM COOLING AIRFLOW (ADJ.) UNTIL THE ZONE IS SATISFIED.
- WHEN ZONE TEMPERATURE IS LESS THAN ITS UNOCCUPIED HEATING SETPOINT, THE CONTROLLER SHALL ENABLE HEATING TO MAINTAIN THE
ZONE TEMPERATURE AT THE SETPOINT.
ELECTRIC HEATING STAGES: THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND STAGE THE REHEATING TO MAINTAIN ITS
SETPOINT. TO PREVENT SHORT CYCLING, THERE SHALL BE A USER DEFINABLE (ADJ.) DELAY BETWEEN STAGES, AND EACH STAGE
SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.
DISCHARGE AIR TEMPERATURE: THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
• HIGH /LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER/LOWER THAN THE COOLING SETPOINT BY A USER DEFINABLE AMOUNT
(ADJ.).
AI
DOCK,= TEMPERATURE
Art �
F�ow �l,ow 5' F O
SPACE TEMPERATURE
DAMPM
000
AI AO ACruATOR °o °o
Alt FIAw SFJtSOR — /I
VAV BOX WITHOUT HEATING CONTROL DIAGRAM
VAV COOLING ONLY SEQUENCE OF OPERATIONS:
RUN CONDITIONS - SCHEDULED: THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES:
• OCCUPIED MODE-THE UNIT SHALL MAINTAIN:
A 74F (ADJ.) COOLING SETPOINT
• UNOCCUPIED MODE (NIGHT SET BACK): THE UNIT SHALL MAINTAIN
A 82'17 (ADJ.) COOLING SETPOINT.
ZONE SETPOINT ADJUST&NOCCUPIED OVERRIDE: THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE SETPOINT AT THE ZONE
SENSOR.THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START -UP. THIS ALGORITHM SHALL MINIMIZE THE UNOCCUPIED
WARM -UP OR COOL -DOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF SCHEDULED OCCUPIED PERIOD.A TIMED
LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR
AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL OF THE UNIT SHALL AUTOMATICALLY RETURN TO THE
SCHEDULE.
FLOW CONTROL: THE UNIT SHALL MAINTAIN ZONE SETPOINTS BY CONTROLLING THE AIRFLOW THROUGH ONE OF THE FOLLOWING:
OCCUPIED:
• WHEN ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE DAMPER SHALL MODULATE BETWEEN THE MINIMUM
OCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM COOLING AIRFLOW (ADJ.) UNTIL THE ZONE IS SATISFIED.
• WHEN THE ZONE TEMPERATURE IS LESS THAN THE COOLING SETPOINT, THE ZONE DAMPER SHALL MAINTAIN THE MINIMUM REQUIRED
ZONE VENTILATION (ADJ.).
UNOCCUPIED:
• WHEN THE ZONE IS UNOCCUPIED THE ZONE DAMPER SHALL CONTROL TO ITS MINIMUM UNOCCUPIED AIRFLOW (ADJ.).
• WHEN THE ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE DAMPER SHALL MODULATE BETWEEN THE MINIMUM
UNOCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM COOLING AIRFLOW (ADJ.) UNTIL THE ZONE IS SATISFIED.
DISCHARGE AIR TEMPERATURE: THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
HIGH /LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER/LOWER THAN THE COOLING SETPOINT BY A USER DEFINABLE AMOUNT
(ADJ.).
G S
, --
Design Services
For The Built
Environment
U
Atlanta Birmingham
Cincinnati
Columbus Dallas
Fort Lauderdale
Knoxville Jackson
Jacksonville Louisville
Memphis Nashville
Richmond Tampa
n
G
R
E
S
H
CY)
A
M
S
M I
T
H
A
N
D
P
A
R
T
N
E
R
S
6030 Hollywood Blvd.
Suite 210
Hollywood, Florida 33024
954.981.9100
FIRM'S FLORIDA
CERT. NO.
AAP000034 /CA3806
1B26000797/LC26000381
DELTA AG'``C EWS M LTING
707 , t�. L3,� VE., UI 200 j-, '
FO$'PVD${2AL1~ 3304
(95 527 2
-CA 81
-13 � A
PJT. MGR: MICHAEL 6.0, \QQ
PROJECT #: 12071
' +'Ll�tlL ''•
0
REVISION
No. —
CZ
Al
CY)
TA e.zmft
e�
•�
Z3
f— m
w m
w
_
-�
�a
m
Cf)
N O
�a
C/) Q
Ln
X
LLI
O
++C(
07
GEORGE SANJUAN, P.E.
FLORIDA LICENSE #46100
DATE: 02/01/13
MECHANICAL
CONTROLS PLAN 2
M4m�
FILE:
PROJECT: 29080.00
DATE: 1 1 /29/201 2
REVISION
No. —
Date — Revision
Al
02/01/13 j Addendum #1
I
MECHANICAL
CONTROLS PLAN 2
M4m�
FILE:
PROJECT: 29080.00
DATE: 1 1 /29/201 2