Loading...
13-96 (2)-0361 ❑A DAMPER OPEN /CLOSE (:H) I CONSTANT VOLUME AHU SEQUENCE OF OPERATIONSi CV AHU CONTROL DIAGRAM a DOCOMP STAGES SF STATUS SF ON /OFF SA HEATING STAGES SCHNEIDER ELECTRIC SE7000 COMMUNICATING THERMOSTAT RUN CONDITIONS — SCHEDULED: THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES: -OCCUPIED MODE: OA DAMPER SHALL OPEN AND THE UNIT SHALL MAINTAIN: A 74'17 (ADJ.) COOLING SETPOINT A 70F (ADJ.) HEATING SETPOINT. *UNOCCUPIED MODE: OA DAMPER SHALL CLOSE AND THE UNIT SHALL BE DISABLED ZONE SETPOINT ADJUST: THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SETPOINTS AT THE ZONE SENSOR. COOUNG /HEATING STAGES: THE CONTROLLER SHALL MEASURE THE ZONE AIR TEMPERATURE AND STAGE THE COOUNG/HEATING TO MAINTAIN THE SPACE AIR TEMPERATURE SETPOINTS.TO PREVENT SHORT CYCLING,THERE SHALL BE A USER DEFINABLE (ADJ.) DELAY BETWEEN STAGES, AND EACH STAGE SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME. ALARMS —HIGH SPACE AIR TEMPERATURE —FAN FAILURE DX VAV SPLIT SYSTEM CONTROL DIAGRAM FIRE ALARM ®Y OT DO aunty M SVW/aor IUMY sae Teffeaaas SA SA 4MIM xp wwsweW a mo VARIABLE AIR VOLUME SPUT SYSTEM: RUN CONDITIONS — SCHEDULED: THE UNIT SHALL RUN BASED UPON AN OPERATOR ADJUSTABLE SCHEDULE IN ONE OF THE FOLLOWING MODES: • OCCUPIED MODE: OUTSIDE AIR DAMPER SHALL BE OPENED,AND UNIT SHALL BE ENABLED. • UNOCCUPIED MODE: OUTSIDE AIR DAMPER SHALL BE CLOSED, AND UNIT SHALL BE DISABLED. EMERGENCY /SMOKE DETECTION SHUTDOWN (BY FIRE ALARMi: THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN EMERGENCY /SMOKE DETECTION SIGNAL. SUPPLY AIR DUCT STATIC PRESSURE CONTROL: THE CONTROLLER SHALL MEASURE DUCT STATIC PRESSURE AND MODULATE THE SUPPLY FAN VFD SPEED TO MAINTAIN A DUCT STATIC PRESSURE SETPOINT. THE SPEED SHALL NOT DROP BELOW 30% (ADJ.). ALARMS SHALL BE PROVIDED AS FOLLOWS: • HIGH/LOW SUPPLY AIR STATIC PRESSURE • SUPPLY FAN VFD FAULT. SUPPLY AIR TEMPERATURE SETPOINT — FIXED: DURING OCCUPIED MODE,THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND SHALL MAINTAIN A FIXED SUPPLY AIR TEMPERATURE SETPOINT OF 55F (ADJ.). COOLING. STAGES: THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND STAGE THE COOUNG TO MAINTAIN ITS SETPOINT. TO PREVENT SHORT CYCLING, THERE SHALL BE A USER DEFINABLE (ADJ.) DELAY BETWEEN STAGES, AND EACH STAGE SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.ALARMS SHALL BE PROVIDED AS FOLLOWS: • HIGH/LOW SUPPLY AIR TEMPERATURE FILTER DIFFERENTIAL PRESSURE MONITOR: THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FILTER.ALARMS SHALL BE PROVIDED AS FOLLOWS: • FILTER DIRTY. TYPICAL WIRING SCHEMATIC CARBON MONOXIDE DETECTION SYSTEM SEQUENCE OF OPERATION A.IN NORMAL CONDITIONS MODE (NO CO DETECTOR ACTIVATED),THE EXHAUST FAN SHALL BE OFF. B.IF ONE CO DETECTOR IS ACTIVATED, THE EXHAUST FAN SHALL RUN TO MAINTAIN CO CONCENTRATION SETPOINT. C.WHEN ALL CO DETECTORS ARE DE— ACTIVATED, THE FAN WILL RETURN TO RUN AS IN NORMAL CONDITIONS MODE. E.DETECTORS SHALL HAVE A SETPOINT OF 25 PARTS PER MILUON (PPM) OF CARBON MONOXIDE. F.CO DETECTORS SHALL BE LOCATED BETWEEN 4' AND 5' HEIGHT. BASIS OF DESIGN AMERICAN AUTO— MATRIX: APPROVED EQUAL, KAL —TECH CONTROLS / DAVE DOWUNG / 954- 464 - 6922. 1 CO SYSTEM SERVING 1ST FLOOR GARAGE EF -1 STR Dj FAN STATUS 0 FAN ON /OFF I G S & P Design Services For The Built Environment Atlanta Birmingham Cincinnati Columbus Dallas Fort Lauderdale Knoxville Jackson Jacksonville Louisville Memphis Nashville Richmond Tampa 0 G R E S H A M S M I T H A N D P A R T N E R S 6030 Hollywood Blvd. Suite 210 Hollywood, Florida 33024 954.981.9100 FIRM'S FLORIDA CERT. NO. AAP000034 /CA3806 1B26000797/LC26000381 la °® w M w¢ elf 00 o x `n LLJ o GEORGE SANJUAN, P.E. FLORIDA LICENSE #46100 DATE: 02/01/13 REVISION EN GIN ,•y�l ,, 707 N.E: FORT:L Q�0 04 (954); CA(J0PJT. . qD � MGR: MICHAEL H00 PROJECT #: 120717 �Es^ °® w M w¢ elf 00 o x `n LLJ o GEORGE SANJUAN, P.E. FLORIDA LICENSE #46100 DATE: 02/01/13 REVISION No. — Date — Revision Q02/01/13 Addendum #1 i MECHANICAL CONTROLS PLAN 1 ky, E*0 FILE: PROJECT: 29080.00 DATE: 11/29/2012