13-718-006H . V. A. C. GENERAL NOTES:
1. THE WORK THAT IS TO BE DONE UNDER THIS HEADING INCLUDES THE
FURNISHING OF ALL LABOR, MATERIALS, EQUIPMENT, PERMITS, FEES
INSPECTIONS, TESTS, INSURANCE, ETC, REQUIRED FOR THE
COMPLETION OF THE AIR CONDITIONING SYSTEM SHOWN ON THE
DRAWINGS AND/ OR LISTED BEL ❑W,
2. VENTILATION DUCTWORK SHALL BE GALVANIZED STEEL WITH GAUGES,
DUCT CONSTRUCTION, BRACING AND SUSPENSION IN ACCORDANCE WITH
THE REC❑MMENDATI ❑NS SET FORTH IN THE LATEST EDITION OF THE
A,S,H,R,A,E, GUIDE AND S,M,A.C,N,A, STANDARDS, DUCT SIZES SHOWN
ARE "INSIDE' DIMENSI ❑NS, VERIFY EXACT LOCATION OF DUCT WITH
RESPECT TO STRUCTURE BEFORE FABRICATI ❑N,
3. FLEXIBLE DUCT SHALL BE STEEL HELIX WIRE ON 7/8" CENTERS,
ENCAPSULATED IN A CONTINUOUS SOFT VINYL FILM, JOINED BY MOLECULAR
WELDING TO FORM AN AIR TIGHT INNER CORE, THE CORE IS TO BE
INSULATED WITH FIBERGLASS INSULATION (R -6), AND SHEATHED IN A
REINFORCED, ALUMINUM METALIZED POLYESTER VAPOR BARRIER JACKET,
PROVIDE SPIN COLLAR WITH DAMPER AND EXTRACTOR WHERE FLEXIBLE
DUCT IS CONNECTED TO RECTANGULAR DUCTWORK, DAMPER ACTUATOR
SHALL BE EXTENDED OUTSIDE INSULATION,
4, AIR CONDITIONING SUPPLY AND RETURN DUCTWORK SHALL BE 1 -1/2"
(R =6 MIN,) FIBERGLASS U,L. 181 LISTED, CLASS I AIR DUCT,
DUCTWORK SHALL BE FABRICATED IN ACCORDANCE WITH S,M,A,C,N,A,
STANDARDS, (R -6 TOP LEVEL, R -42 IN OTHER LEVELS),
5. TEMPERATURE CONTROL SHALL BE A ROOM THERMOSTAT FOR
HEATING / CO ❑LING WITH STAGES AS REQUIRED,
6. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AV ❑ID
INTERFERENCE WITH THE PROGRESS OF CONSTRUCTI ❑N AND IN STRICT
COMPLIANCE WITH ALL APPLICABLE CODES AND STANDARDS,
7, MECHANICAL CONTRACTOR SHALL VERIFY DIRECTION OF EXISTING
STRUCTURE BEFORE INSTALLATION OF EQUIPMENTS AND DUCTWORK
SHOULD ANY DISCREPANCIES BE FOUND CONTACT ARCHITECT /ENGINEER
8 VIBRATI ❑N ISOLATION., ALL EQUIPMENT AS PER MANUFACTURER
REC ❑MMENDATI ❑NS TO ELIMINATE ANY EQUIPMENT NOISE FROM BEING
HEARD,
9, GUARANTEES:
A. ALL COMPRESSOR MOTORS ON NEW EQUIPMENT FURNISHED UNDER
THIS CONTRACT SHALL HAVE A 5 YEARS PRODUCT GUARANTEE FROM
DATE OF START -UP,
B. CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP
FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN A 1 YEAR
FROM DATE OF ACCEPTANCE,
10, TESTING:
A. ALL REFRIGERANT HIGH SIDE PIPING TO 300 PSIG, LOW SIDE
TO 150 PSIG. AFTER TESTING, EVACUATE SYSTEM TO 28%
MERCURY GAUGE PRESSURE WITH VACUUM PUMP, HOLD FOR 25
HOURS WITH PUMP OFF, BREAK VACUUM WITH REFRIGERANT,
B. BALANCE AIR SYSTEM TO DELIVER QUANTITIES AT EACH OUTLET
WITHIN 57. USING A.A,B,C, PROCEDURES AND TESTS, SUBMIT
AIR BALANCE TEST RESULTS FOR APPROVAL PRIOR TO FINAL
INSPECTION,
11. REFRIGERATION SUCTI ❑N PIPING SHALL BE INSULATED WITH 3 1/4
INC❑AFLEX ARMAFLEX INSULATION MAY ONLY BE USED IN NON- PLENUM
AREAS, FINISHED WHERE EXPOSED WITH 2 COATS OF WHITE LATEX PAINT
ALL A PER MANUFACTURER'S INSTRUCTION,
12, ALL REFRIGERANT PIPING SHALL BE TYPE "K" HARD COPPER, TOGETHER
WITH WROUGHT COPPER SOLDER FITTINGS, JOINTS SHALL BE MADE WITH
SILVER SOLDER OR "SILFOS ', ALL CONDENSATE DRAIN PIPING TO BE
SCHEDULE 40 TYPE II HIGH IMPACT PVC WITH SLIP JOINT FITTING OF THE
THE SAME MATERIAL WITH AN APPROVED SOLVENT INSTALLED IN A
MANNER RECOMMENDED BY THE FITTING MANUFACTURER,
HVAC DESIGN REQUIRES
YES
NO
DUCT SMOKE DETECTOR
MODEL NUMBER
V/
FIRE DAMPER
z
V/
SMOKE DETECTOR
Q
✓
FIRE RATED ENCLOSURE
�-
✓
FIRE REATED ROOF CELING ASSEMBLY
OCEILING
B
✓
FIRE STOPPING
FAN SPEED RPM
✓
SMOKE CONTROL
o
✓
A/C EQUIPMENT SCHEDULE
SYMBOL
UNIT NUMBER
AHU— 1
MODEL NUMBER
AREA SERVED
SEE FLR, PLAN
z
TOTAL SUPPLY AIR CFM
1350
Q
OUTSIDE AIR CFM
—
�-
EXTERNAL STATIC PRESS, Hz❑
0.35
OCEILING
B
FAN MOTOR HP /FLA
1/3 /8.3
FAN SPEED RPM
ELEC, CHAR, V /Z /ti
208/230/1/60
o
COOL, COIL CAP, BTU /HR
40000
TOTAL STATIC PRESS, H2O
0.25
0.25
OPENING REQUIRED IN.
TOTAL SENS, HEAT BTU /HR
28550
Lo
65 WATTS
135 WATTS
J
ENT, AIR TEMP, F' DB /° F WB
80/67
MANUFACTURER
MODEL NUMBER CFM
—
MODEL NUMBER
UNIT MANUFACTURER
RHEEM
NOTES:
MODEL NUMBER
RHSL— HM4221
2, ALL AIR DISTRIBUTI ❑N DEVICES SHALL BE OF EXTRUDED
ALUMINUM CONSTRUCTI ❑N, FURNISH WITH OPPOSED
BLADE DAMPERS AND CONCEALED MOUNTING FRAME
Q
WEIGHT LBS.
51 "X21 "X22/190
a
°
REMARKS; REF, PIPING RS /RL
7/8"
U
UNIT NUMBER
CU -1
0
J
O
M
m
LOCATI ❑N
SEE FLR, PLAN
z
AMBIENT TEMP, OF
95
z
REFRIGERANT R
R — 410A
A
z
COMP, /C ❑ND, FAN FLA
17.9 / 2,8
°
ELEC, CHAR, V /,O /ti
208/230/1/60
w
MANUFACTURER
RHEEM
cm
0
M ❑DEL NUMBER
RAPM- 042JEZ
Lj
WEIGHT LBS,
4 "X32 "X45 " /25
�
REMARKS SEER/NOTES
14.5
z
UNIT MTD, ELEC, HEAT CAP, KW
8.0 KW
STEPS OF ELEC, HEAT NO,
1
ELEC, CHAR, V /,B /ti
208/1/60
MODEL NUMBER
NOTE: INSTALL AHU -1 WITH PROGRAMMABLE THERMOSTAT,
AIR DISTRIBUTION SCHEDULE
SYMBOL
NECK SIZE
MFGR,
MODEL NUMBER
REMARKS
O
SEE FLR,
TITUS OR
CEILING DIFFUSER
S/A REG,
EXH,
PLAN
EQUAL
SERIES 250
CEILING
OCEILING
B
DIRECT
DIRECT
FAN SPEED RPM
1200
OR WALL
RETURN 50F
R/A GR,
100
200
TOTAL STATIC PRESS, H2O
0.25
0.25
OPENING REQUIRED IN.
-
-
FAN MOTOR HP
65 WATTS
135 WATTS
ELECTRICAL CHAR. V /9 /ti
115/1/60
115/l/60
MANUFACTURER
Al
LOREN COOK
MODEL NUMBER
GC,240
GC,340
NOTES:
1, REFER TO PLAN FOR QUANTITY, L ❑CATION AIR THROW
PATTERN AND SIZES,
2, ALL AIR DISTRIBUTI ❑N DEVICES SHALL BE OF EXTRUDED
ALUMINUM CONSTRUCTI ❑N, FURNISH WITH OPPOSED
BLADE DAMPERS AND CONCEALED MOUNTING FRAME
FOR ACOUSTICAL OR PLASTER CEILING INSTALLATI ❑N,
FAN SCHEDULE
UNIT NUMBER
EF.1 & 2
EF -3
AREA SERVED
TOILET ROOM
GARAGE
L ❑CATION
CEILING
CEILING
DUTY SUPPLY /EXH,
EXH,
EXH,
FAN TYPE
CEILING
CEILING
DRIVE BELT /DIRECT
DIRECT
DIRECT
FAN SPEED RPM
1200
1610
AIR QUANTITY CFM
100
200
TOTAL STATIC PRESS, H2O
0.25
0.25
OPENING REQUIRED IN.
-
-
FAN MOTOR HP
65 WATTS
135 WATTS
ELECTRICAL CHAR. V /9 /ti
115/1/60
115/l/60
MANUFACTURER
L❑REN COOK
LOREN COOK
MODEL NUMBER
GC,240
GC,340
WEIGHT LBS,
25
30
REMARKS S❑NES
1,5
4.3
NOTES: 1- INSTALL EF -1 INTERLOCK WITH LIGHT FIXTURE,
2- INSTALL EF -2 WITH CARBON MONOXIDE SENSOR,
REVISIONS
Nib. i
THESE DRAWING do SPECIFICATIONS
ARE INSTRUMENTS OF SERVICE AND
SHALL REMAIN THE PROPERTY OF
RUBEN JUAN PUJOLWNETHER THE PROJECT
FOR WHICH THEY WERE PREPARED
IS EXECUTED OR NOT, THEY ARE NOT
TO BEUSED IN ANY MANNER ON OTHER
PROJECTS OR EXTENSIONS TO THIS
PROJECT EXCEPT BY AGREEMENT IN
WRITING AND WITH THE APPROPRIATE
COMPENSATION TO RUBEN JUAN PUJOL
do ASSOCIATES
�/
Q
CL
w
C�
W
C�
LL
Q
I-
LJ
LLJ O
r- —
o
Cn
N _
w0-) I-
°o Oy
a Lo 0
V)
F_
Q
z =
a
o LLI
z J
tr W Q
o U
o
cr
J
00
L0
N
ti
0
�
M
N
CL
�
o
CL
zv
W
<w
9�
Lg
tLo
�
w
W
M
co
N
ap
Z
_
=°
o
_
F-
�
a
°
co
W
U
�
N
>
0
J
O
M
m
¢
v,
L
w
D
�QQ
Q
M
T�
Q
O
a
DATE 04/04/2013
DRAWN BY: GPC
CHECKED BY: R.P.
SCALE: AS SHOW
M -1
SHEET 6 OF 7