10-338-019SPLIT AC UNIT SCHEDULE
UNIT DESIGNATION
AHU -2
PROGRAMMABLE.
AREA SERVED
SEE PLANS
PROVIDED
LOCATION
A/C CLOSET
ACCESSORIES
OPERATING WEIGHT, LBS
143
SUPPLY
DESIGN MANUFACTURER
RHEEM
TITUS
MODEL NUMBER
RBHM17J11
DIFFUSER
SEER / MIN.
16.1
8" SA
RETURN
TOTAL AIR, CFM
800
TITUS 317
z
VENT AIR, CFM
0
o
EXTERNAL STATIC PRESSURE, IN OF WATER
0.5
WALL GRILLE
FAN MOTOR HP. (NON - OVERLOAD)
1/3
AIR
z
ELECTRICAL SERVICE AVAILABLE
230/l/60
NOTE: ALL AIR DISTRIBUTION SHALL BE FINISHED WHITE BAKED ENAMEL.
MIN. CIRC. AMP
4
MAX. CIRC. PROT.
15
FACE VELOCITY - FPM
- --
J
DESIGN AIR ACROSS COIL, CFM.
800
®
GRAN TOTAL CAPACITY, BTU /HR
25,000
TOTAL SENSIBLE CAPACITY, BTU /HR
17,600
ENTERING AIR TEMP., F° DB /WB
80/67
COIL MODEL NO.
RCQD2417A
TYPE & THICKNESS
CLEANABLE 1"
QUANTITY AND SIZE
1/16X20
FACE VELOCITY FPM. MAX.
n'
HEAT COIL TYPE
ELECT.
LU
ELECTRICAL SERVICE AVAILABLE
230/1/60
AUXILIARY ELECTRIC HEAT, KW
4.9
=
STAGES & KW PER STAGE
1/4.
UNIT DESIGNATION
CU -2
z
TYPE OF FAN
PROP.
NO. OF FANS AND AMPS
1/0.8
z
AMBIENT AIR TEMP. 'F DB
95
Cn
CONDENSING TEMP. 'F DB
- --
Z
w
NO. OF COMPRESSORS TYPE
1 /SCROLL
Z
COMPRESSORS F.L.A. /L.R.A. EACH
10.3/52
o
CAPACITY REDUCTION.
0 -50% -100%
°w
MIN. CIRC. AMP
14
-'
MAX. CIRC. PROT.
20
oELECTRICAL
SERVICE AVAILABLE
230/l/60
OPERATING WEIGHT, LBS
200
�c
DESIGN MANUFACTURER
RHEEM
MODEL NUMBER
RARL024JEZ
REFRIGERANT PIPE SIZE, SUCTION /LIQUID
3/4" - 5/16"
NOTES:
1. ALL THERMOSTATS
SHALL BE
PROGRAMMABLE.
2. FAN
COIL UNIT SHALL BE
PROVIDED
WITH FACTORY INSTALLED CIRCUIT BREAKER.
AIR DISTRIBUTION SCHEDULE
1" WIDE HANGER 72 GA
�VD
MANUAL VOLUME DAMPER
MFG` &
SYM50L
USE
TYPE
ACCESSORIES
MODEL NO.
/��\
SUPPLY
CEILING
O.B.D.
TITUS
`-�'
AIR
DIFFUSER
WITH DUCT
SEALER &
250 -AA
8" SA
RETURN
CEILING
O.B.D.
TITUS 317
O
AIR
GRILLE
SUPPLY AIR
SUPPLY
WALL GRILLE
AIR
O.B.D,
TITUS 350E
NOTE: ALL AIR DISTRIBUTION SHALL BE FINISHED WHITE BAKED ENAMEL.
PROVIDE SWITCH IN UNIT
OVERFLOW OUTLET WIRED TO
SHUT DOWN UNIT WHEN
WATER IS SENSED
2 "X 2 "X 1/2" NEOPRENE
NEOPRENE PADS AT ALL
CORNERS
2" x 2" x 1/4 STEEL
ANGLE FRAME SHALL BE RUST
PRIME PAINTED.
3X3X3/16" STEEL ANGLE PLATE.
PROVIDE 4 CLEAR
ALL AROUND UNIT
-� PROVIDE 3' -0" CLEAR
IN FRONT OF FC UNIT
AHU AND HEATER.
20" MIN.
VERTICAL AHU MOUNTING DETAIL
1. GENERAL
A. ALL WORK SHALL BE DONE in accordance with the Florida
Building Code and with all applicable regulations.
B. DRAWINGS: Refer to all drawings for coordination of the HVAC work.
C. ARRANGE AND PAY for all permits licenses, inspections and tests.
Obtain the required certificates and present to owner.
D. GUARANTEE: The completed installation shall be fully guaranteed
against defective materials and /or improper workmanship for a
minimum of one year for material and labor. All compressors
shall be guaranteed for 5 years minimum.
2. SHOP DRAWINGS: Contractors shall submit for approval, within 30 days
after signing contract, a minimum of five copies of fully descriptive
literature, including but not limited to: fans, air conditioning units,
air outlets. No work shall proceed without approval of these submittals.
3. DESIGN PARAMETERS:
A. Indoor design temperature (Summer): 78 °F DB
B. Indoor design temperature (Winter): 70'17 DB
4. ALL THERMOSTATS SHALL hove heating mode maximum setting of 75 F, and
cooling made minimum setting of 70 F. The thermostat shall be arranged
to prevent the simultaneous operation of heating and cooling.
5. ELECTRICAL CONTROLS AND POWER WIRING: Under electrical contract.
6. EQUIPMENT SPECIFIED BY manufacturer's number shall include all
accessories, controls, etc., listed in the catalog as standard with the
equipment. Optional or additional accessories shall be furnished as
specified.
7. MATERIALS:
A. REFRIGERANT PIPING: Shall be type L soft drawn, copper tubing,
dehydrated for refrigerant use. Sized as shown on drawings or as
per air conditioning equipment manufacturer's recommendations.
B. INSULATION: Refrigerant suction piping shall be insulated with
1/2" thick foamed plastic insulation, fire retardant type.
Insulation shall be installed in piping before assembly. No split
insulation will be acceptable. Seal joints with manufacturer's
approved adhesive and grey tape.
C. DUCTWORK:
a. All supply air ductwork shall be 1 1/2" thick fiberglass
ductboard, fabricated and installed as per latest edition of
SMACNA "Fibrous Glass Duct Manual ". R -6.0 MIN.
b. All toilet exhaust ductwork shall be galvanized sheet
metal duct not lighter than 24 gage.
C. All duct dimensions are clear inside dimensions.
d. Flexible insulated ductwork with 1 1/2" thick fiberglass
insulation with FRK vapor barrier. R -6.0 MIN.
8. CONTROLS: Air conditioning units shall be started and stopped thru
individual thermostat. Individual programmable thermostats shall start /stop
supply fans and activate cooling /heating systems as selected.
9. TEF -1 50 CFM at .1" TSP 1.5 sones max. Broan 670, provide
BDD and service switch. 55 Watts at 120V -1 -60.
10, TEST AND BALANCE: Contractor shall test and balance all ventilation and
air conditioning systems. Submit four copies of Test and Balance Report,
to owner for approval.
DUCTWORK SYMBOLS
HVAC_ SCHEDULES & DETA L S
SCALE: N.T.S.
IK
I
\ - -- --------------------- �. -------- - - - - -- i-
- - - -- - _ -� ----------------- - - - - -- -- \ - - - - -- i,
- -- -
l
I
{ I
........ -. .......... ...... _ - ------ .. _ ----- 18X6
L_.
400 CFM
w
- -, _.
\ - - ---- -
,r -� �- i 1.
10n�I
- \ \, ---------- - ---- - - - - - -- -
- -- _
----------------------
/ Uc
H
o i
Q�,i ►��Q►�lO�Pi�i�l�l�1 � I' ;w ! �l � l���l�l�l�l�l�l��0�1�01�1�1t1��
12X12
�— -0---
0
_6X6
A. nru
0 4
HVAC KEY NOTES
1O REF. PIPES UP IN WALL AND TO CEILING AND FAN COIL UNITS
CONDENSING UNIT ON 4" CONCRETE PAD,
3 4 "0 TOILET EXHAUST, 6 "0 DUCT UP TO ROOF JACK W /WMS.
® 20X10 R/A DUCT DOWN TO FULL SIZE RETURN AIR PLENUM
THERMOSTAT
® 3/4" SCHEDULE 40 PVC CONDENSATE DRAIN PIPE ABOVE GROUND, RUN TO
DRYWELL OR GRASSY AREA, 2" UNDERGROUND TO GOOSENECK. SEPARATE MIN
12" FROM WALL PROVIDE "P" TRAP AT UNIT CONNECTION, INSULATE WITH
1/2" ARMAFLEX A.G.
O FULL SIZE DISCHARGE PLENUM
® AIR DISTRIBUTION PLENUM.
EXISTING AC DIFFUSERS & DUCTS IN THIS AREA TO REMAIN. RELOCATE AS
NECESSARY, COORDINATE W/ ARCHITECT.
HVAC PART AL PLAN-
.
SCALE. 4 -V-0"
1" WIDE HANGER 72 GA
�VD
MANUAL VOLUME DAMPER
(� OR CFM
CUBIC FEET PER MINUTE
UC
UNDERCUT DOOR
DG
-V
DOOR GRILLE
DL - -- p
DOOR LOUVER (WITH VOLUME DAMPER AT AC CL.)
DUCT. SUPPORT AT
SUPPLY OR OUTSIDE AIR DUCT
EVERY 5-0" (MAX.)
TO AVOID SAG.
RETURN OR EXHAUST AIR DUCT
WITH DUCT
SEALER &
FLEXIBLE DUCT
8" SA
LETTER [A] DENOTES AIR DISTRIBUTION DEVICE TYPE
A 200 CFM
NUMBER [8] DENOTES TERMINAL NECK SIZE
BAND
NUMBER [200] DENOTES SUPPLY AIR QUANTITY
- -� - - --
RETURN AND EXHAUST AIR
SUPPLY AIR
To
THERMOSTAT
HVAC_ SCHEDULES & DETA L S
SCALE: N.T.S.
IK
I
\ - -- --------------------- �. -------- - - - - -- i-
- - - -- - _ -� ----------------- - - - - -- -- \ - - - - -- i,
- -- -
l
I
{ I
........ -. .......... ...... _ - ------ .. _ ----- 18X6
L_.
400 CFM
w
- -, _.
\ - - ---- -
,r -� �- i 1.
10n�I
- \ \, ---------- - ---- - - - - - -- -
- -- _
----------------------
/ Uc
H
o i
Q�,i ►��Q►�lO�Pi�i�l�l�1 � I' ;w ! �l � l���l�l�l�l�l�l��0�1�01�1�1t1��
12X12
�— -0---
0
_6X6
A. nru
0 4
HVAC KEY NOTES
1O REF. PIPES UP IN WALL AND TO CEILING AND FAN COIL UNITS
CONDENSING UNIT ON 4" CONCRETE PAD,
3 4 "0 TOILET EXHAUST, 6 "0 DUCT UP TO ROOF JACK W /WMS.
® 20X10 R/A DUCT DOWN TO FULL SIZE RETURN AIR PLENUM
THERMOSTAT
® 3/4" SCHEDULE 40 PVC CONDENSATE DRAIN PIPE ABOVE GROUND, RUN TO
DRYWELL OR GRASSY AREA, 2" UNDERGROUND TO GOOSENECK. SEPARATE MIN
12" FROM WALL PROVIDE "P" TRAP AT UNIT CONNECTION, INSULATE WITH
1/2" ARMAFLEX A.G.
O FULL SIZE DISCHARGE PLENUM
® AIR DISTRIBUTION PLENUM.
EXISTING AC DIFFUSERS & DUCTS IN THIS AREA TO REMAIN. RELOCATE AS
NECESSARY, COORDINATE W/ ARCHITECT.
HVAC PART AL PLAN-
.
SCALE. 4 -V-0"
INSULATED & VAPOR
SEALED COLLAR & DIFFUSER
BACK PANEL
DIFFUSER
AIR
FLOW
2"X1.5 " - -22 GA. CHANNEL
AT 6' -- -0" O.C. MAX.
SEAL JOINT WITH DUCT
SEALER & TAPE
1-✓
FLEXIBLE DUCT CONNECTION DETAIL
N.T.S.
TEF -1
�0
- - - --
TEF -1
1' -0" MIN.
t<+
CU -2
CONDENSIP
UNIT SECURED
W/ 3) # 14 c
INSERTS EACH
FBC 301.13.1.
PROVIDE 4" C
POWER & CONTROL
CONNECTIONS
REFRIGERANT
SUCTION & LIQUID
LINES
NOTES:
1. EQUIPMENT SHALL BE SECURED AS TO RESIST WIND PRESSURES IN FBC -2004 BUILDING.
2. EQUIPMENT SHALL BE MOUNTED ABOVE BASE FLOOD ELEVATION.
3. CONDENSING UNIT SECURED TO CONCRETE PAD TO WITHSTAND 500 Ib PULL OUT FORCE.
a ,
LEQNARD0 NAVEIRAS, INC.
'CONSULTING ENGINEERS"
• r O Leonardo Naveiras P.M. CA# 25830
z t_ Julio C. Vidal P.E. PE# 52792
:1P8 Harrison St. # 207 Hollywood, FL 33020
........ ' 54 �' V'� 822 ax:- 954 2416650-
— r'ITOTiC. J'
E -mail: hvacleo @aol.com
131hr
Caroline
7 i c L, A
1" WIDE HANGER 72 GA
TO STRUCTURE ABOVE AS
PER SMACNA STANDARDS.
LOW VELOCITY SUPPLY
AIR DUCT (SEE PLAN VIEW)
INSULATED FLEXIBLE
DUCT. SUPPORT AT
EVERY 5-0" (MAX.)
TO AVOID SAG.
SEAL JOINT 1.5" WIDE STRAP SADDLE—
WITH DUCT
SEALER &
SUPPORTED TO STRUCTURE
TAPE
ABOVE WITH 12 GA. HANGER
WIRE.
DRAW
BAND
AIR
FLOW
INSULATED & VAPOR
SEALED COLLAR & DIFFUSER
BACK PANEL
DIFFUSER
AIR
FLOW
2"X1.5 " - -22 GA. CHANNEL
AT 6' -- -0" O.C. MAX.
SEAL JOINT WITH DUCT
SEALER & TAPE
1-✓
FLEXIBLE DUCT CONNECTION DETAIL
N.T.S.
TEF -1
�0
- - - --
TEF -1
1' -0" MIN.
t<+
CU -2
CONDENSIP
UNIT SECURED
W/ 3) # 14 c
INSERTS EACH
FBC 301.13.1.
PROVIDE 4" C
POWER & CONTROL
CONNECTIONS
REFRIGERANT
SUCTION & LIQUID
LINES
NOTES:
1. EQUIPMENT SHALL BE SECURED AS TO RESIST WIND PRESSURES IN FBC -2004 BUILDING.
2. EQUIPMENT SHALL BE MOUNTED ABOVE BASE FLOOD ELEVATION.
3. CONDENSING UNIT SECURED TO CONCRETE PAD TO WITHSTAND 500 Ib PULL OUT FORCE.