14-848-0081ST FLUOR BATTERY CALCULATION BPS -1 DROP VOLT. CALL. EE STR 75CD W (mA) STR 110CD W (mA) STR 75CD C (mA) STR 116CD C (mA) SPK/STR 75CD W (mA) I SPKISTR 110CD W (mA) TOTAL Length Wire Vdrop Last Device Output Circuit (mA) E QTY Sub -Tot (mA) 68N31 QTY Sub -Tot (mA) 135N34 75CD QTY Sub -Tot (mA) FP QTY Sub Tot (mA) 75CD QTY Sub -Tot (mA) NAC #3 QTY Sub -Tot (mA) (feet) AWG V Voltage(V) STR. # 1 165 x 0 0 220 x 0 0 189 x 0 0 300 x 0 0 165 x 3 495 220 x 0 0 495 1000 14 3.039 17.361 STR. # 2 165 x 4 660 220 x 1 220 189 x 0 0 300 x 0 0 165 x 4 660 220 x 0 0 1540 268 14 2.534 17.866 STR. # 3 165 x 6 990 220 x 0 0 189 x 0 0 300 x 0 0 165 x 0 0 1 220 x 1 220 1210 297 14 2.207 18.193 STR. # 4 165 x 9 1485 220 x 0 0 189 x 0 0 A 300 x 0 0 165 x 2 330 1 220 x 0 0 18-1-571 815 493 12 1 3.132 17.268 BOOSTER #8 PANEL "X" CKT BREAKER 20A, 1P, 120V, CKT. 21 3X12THHN PER CKT. BOOSTER #7 PANEL "L" CKT BREAKER 20A, 1P. 120V, CKT 3 3X12THHN PER CKT. BOOSTER #6 PANEL "C" CKT BREAKER 20A, 1 P, 120V, CKT. 30 3X12THHN PER CKT. BOOSTER #5 PANEL "K" CKT BREAKER 20A, 1P. 120V, CKT 18 3X12THHN PER CKT. BOX TION C S p E �EOL NAC #4 (0.109A) NAC #4 � ' I 138N4-1 A L1 S23 L1 S24 L1 S25 L1 S21 I U M95 L1 M96 L1 M97 L ., -%� F 01 F 4-%, F i1 f—r f-1 r .. CS N IINIIIIIIINII NAC #1 = 0 BPS #8 IINIIIIIIINII 1 #12THHN GREEN CS FP E ELEVATOR CONTROL E E EE E NAC #3 (0.545A) p E E 2-:9- B6N2- 7B6N2-8 86N2-9 -1 75CD -2 -5 75CD 75CD 75CD 75CD -6 75CD J E 68f�5 E E E E E B6N1 -3 B63 B6N1 -4 B6NN1 -5 66NL__aE N1 -6 75CD 75CD 75CD 75CD 68N31 68N 2 B8N3 -3 B8N3 4 135N34 75CD E FP E n n E E FP 75CD 75CD 75CD 75CD 75CD NAC #3 67N3 -1 B7NN3 -2 137N3 -3 67N34 137N3 -5 67N3 -6 B7N3 -7 137N3 -8 75CD 75CD 75CD 75CD 75CD 75CD 75CD 75CD B7N3 -9 75CD 75CD C S (5E �E p E oil p E E E� E E EE Eli AXE E E E AN E '.,EOL NAC #2 (1,100A) - B8N21 - B8N2 2 B -3 B8N2 67N1 -8 75CD -4 BBN2 -5 B8N2 -6 B8N2 -7 B8N2 -8 B -9 B-10 B8N2 -11 75CD 75CD 75CD 75CD 75CD 75CD 75CD 75CD 75CD 75CD 75CD C_(5E oil JE E �E E Switch Wiring Connected to Main Fire Alarm Panel NAC #1 (0.954A) 68N1 -1 138N1 -2 110CD B8N1 -3 75CD B8N1 -4 75CD B8N1 -5 138N1 -6 75CD 110CD B8N1N1 -77 138N1 -8 75CD 75CD 68NNI -9 75CD o 0 (0 A L1 M59 L1 M60 L1 S17 L1 S18 L1 S19 L1 S20 L1 M61 L1 M62 JUNCTION BOX E� �E �E E P NAC #2 (0.986A) �E �E &N P 2 p E E 2-:9- B6N2- 7B6N2-8 86N2-9 -1 75CD -2 -5 75CD 75CD 75CD 75CD -6 75CD J E �E X __ E E E E E B6N1 -3 B63 B6N1 -4 B6NN1 -5 66NL__aE N1 -6 75CD 75CD 75CD 75CD l36N1 -7 75CD 136N1 -8 136N1 -9 66NNI -10 66N1 -11 66N1 -12 110CD 75CD 75CD 75CD 75CD FP E 135N34 75CD E FP E n n E E FP E ,,EOL NAC #2 (0.794A) NAC #2 B C S JE p E E � E E� E E E �EOL NAC #3 (1,012A) NAC #3 67N3 -1 B7NN3 -2 137N3 -3 67N34 137N3 -5 67N3 -6 B7N3 -7 137N3 -8 75CD 75CD 75CD 75CD 75CD 75CD 75CD 75CD B7N3 -9 75CD 75CD C S (5E �E p E oil p E E E� E �- EOL NAC #2 (0.794A) NAC #2 B7N2 -1 B7N2 -2 87N2 -3 110CD 75CD 67NN224 B7N2 -5 B7N2 -6 B7N2 -7 67N2 -8 75CD 75CD 75CD 75CD 75CD dedicated for elevator shunt shall pE CS Eli EE E E E B Vti E EOL NAC #1 (0.903A) NNNNNNIII - # 1 B7N1 -1 N1 1 75CD 75CD 75CD B�NAC 7N5 t3 7 110CD 75CD 75CD 75CD 67N1 -8 75CD UL'- F Q J Q j O Elevotor Disconnect Switch 0 BPS #7 With Shunt -Trip INNNINNIII � #12THHN GREEN S Q 2 Elevator Fire Fighters' Service Recall Wiring 9 A L1 M55 L1 M56 U S15 L1 S16 L1 M57 L1 M58 O3 "Optional" Fire Sprinkler -Shut -Off Valve. Tamper F CTION P P e J E E E r—, E r---n E rnnn E CS INNNIIIIIIII NAC #1 - 0 BPS #6 INNNIIIIIIII 1 #12THHN GREEN JUNCTION A BOX CIsPt�E E� �E �E E �E NAC #2 (0.986A) �E �E &N B6N2 B6N2 B�N2-3 B6N2-4 BA 6612 2-:9- B6N2- 7B6N2-8 86N2-9 -1 75CD -2 -5 75CD 75CD 75CD 75CD -6 75CD 75CD 75CD 75CD — 4 E p E �E X __ �E JE JE �E �E j - EOL NAC #1 (1.258A) B6NN11 -1 66N1 -2 110CD B6N1 -3 B63 B6N1 -4 B6NN1 -5 66NL__aE N1 -6 75CD 75CD 75CD 75CD l36N1 -7 75CD 136N1 -8 136N1 -9 66NNI -10 66N1 -11 66N1 -12 110CD 75CD 75CD 75CD 75CD L1 M48 L1 M49 L1 M52 US13 US14 L1 M50 L1 M51 L1 M53 L1 M54 n n n n n ` E J E E r, E r, E n " C S E 141 i ® E E E (E E EOL NAC #4 (1.134A) NAC # B5N4 -1 B5N3 -2 B5N3 -3 135N34 1350-5 B5N3 -6 75CD 75CD 75CD 75CD 75CD 75CD CS Ek( WP �E E WP j E WP WP WP WP EE ELff -EOL NAC #3 (0.872A) NAC #3 B5N3 -1 75CD B5N3 -2 75CD B5N3 -3 75CD 135N34 75CD B5N3 -5 B5N3- 6— B5NN3 -7 B5N3 -8 75CD 75CD 75CD 75CD CS E E E Ex( E ,,EOL NAC #2 (0.794A) NAC #2 B B5N2 1340-3 B5N24 13, 5 1315NN12 -6 B5N2 -7 -1 110CD -2 75CD 75CD 75CD 75CD 75CD 75CD CS �1E (11)E pE � E � E E ��E ��- EOL NAC #1 (0.986A) IINIIIINIIIII NAC #1 135N1 -1 B5N1 -2 B5N1 -3 135N14 135N1 -5 B5N1 -6 B5N1 -7 135N1 -8 65N1 -9 110CD 75CD 75CD 75CD 75CD 75CD 75CD 75CD 0 BPS #5 INNNINIIIII � #12THHN GREEN A BOX TION L1 M41 L1 M42 L1 M45 L1 S11 L1 S12 L1 M43 L1 M44 L1 M46 L1 M47 Smoke detectors in elevator lobbies, shaft and or elevator machine room shall: 1— Initiate on alarm condition in the building dor evacuation purposes. ;- 2— Initiate the recall of the elevator cars as follows in accordance with NFPA 72 (2008 edition), chapter 5:'16;3 -- _- B— Phase I recall: Any elevator lobby smoke detector located on the floors 2 and above and /or any smoke detector in the elevator machine or elevator shaft sholl initiate phase I recall which will bring the elevator car to the 1st floor and lock the doors in the open position. C— Phase II recall: Any elevator lobby smoke detector located on the 1st floor shall initiate recall which will bring the elevator car to the 2nd floor and lock the doors in the open position. E E E E E J r� E — rr E r--r E r—r E n n n rs N0 8TH FLOOR 7TH FLOOR 6TH FLOOR 5TH FLOOR ELEVATOR RECALL- SEQUENCE OF OPERATION ; ; ; --- - - - ,- A- Smoke detectors in elevator lobbies, shaft and or elevator machine room shall: 1— Initiate on alarm condition in the building dor evacuation purposes. ;- 2— Initiate the recall of the elevator cars as follows in accordance with NFPA 72 (2008 edition), chapter 5:'16;3 -- _- B— Phase I recall: Any elevator lobby smoke detector located on the floors 2 and above and /or any smoke detector in the elevator machine or elevator shaft sholl initiate phase I recall which will bring the elevator car to the 1st floor and lock the doors in the open position. C— Phase II recall: Any elevator lobby smoke detector located on the 1st floor shall initiate recall which will bring the elevator car to the 2nd floor and lock the doors in the open position. D— Elevator warning lights: Actuation of any elevator machine room smoke detector or elevator smoke detector shall also initiate the elevator warning lights to alert emergency personnel that the elevators are not safe 'for use as required CL in NFPA 72 (2008 edition) Chapter 6.16.3.12.3 E— Shunt —Trip heat detectors: Heat detectors dedicated for elevator shunt shall be connected where required and activate a control shunt to disconnect the elevator power upon activation. The shunt power source shall be monitored by the fire alarm control panel as required in NFPA 72 (2008 edition) Chapter 6.16.4.4 UL'- F Q J Q j O Elevotor Disconnect Switch With Shunt -Trip 5 S Q 2 Elevator Fire Fighters' Service Recall Wiring 9 Top of Elevator Hoistway 0 no) 00 O3 "Optional" Fire Sprinkler -Shut -Off Valve. Tamper 4th Floor Lobby Switch Wiring Connected to Main Fire Alarm Panel O J ® Elevator Machine Room, Lobby & Top of Hoistway System Smoke Detectors. Connected to Activate o 0 (0 e Fire Fighters' Service.; Recall ' , Q System Heot Detector(135 Deg. F) Located 0� Whitin 24" of Sprinkler Head 3rd Floor Lobby © Fire Alarm System Wiring to Heat Detectors 0 J 07 Shunt -Trip Control Power Monitor .E U LL_ S ® Shunt -Trip Power Connected to Auxiliary Contacts 1 F of System Heat Detectors & Shunt -Trip In W ^ prinkler Head Q Disconnect Switch for Elevator Shut -Down 2nd Floor Lobby 5 7 (TYp•) ^ \ Q Line Voltage Wiring to l`~J� P J Elev. Machine Room 0 Elevator iseonnect n Switch 11E2 c to 0 1st Floor Lobby Elevator Hoistway levotor Fire Alarm ontrol Pon Cabinet E I\ c c Sprinkler Head S 9 0 v _ Power 1ST FLOOR BATTERY CALCULATIONS 13PS -1 ITEM DESCRIPTION QTY STANDBY STANDBY ALARM ACTIVATED BOTH CURRENT CURRENT CURRENT CURRENT CURRENTS PER UNIT SUES -TOTAL PER UNIT SUET -TOTAL TOTAL (AMPS) (AMPS) (AMPS) (AMPS) 1 STROBE (75CD) (W) 19 0 0 0.165 3.135 3.135 2 STROBE (110CD) (VII) 1 0 0 0.22 0.22 0.22 3 STROBE (75CD) (CE) 0 0 0 0.189 0 0 4 STROBE (115CD) (CE) 0 0 0 0.3 0 0 5 SPK/STROBE (75CD) (W) 9 0 0 0.165 1.485 1.485 6 SPK/STROBE (110CD) (W) 1 0 0 0.22 0.22 0.22 - 8 9 PS-8 1 0.075 IF 0.075 0.105 0.105 0.18 0 TOTAL F 0.075 IF 5.165 REQUIRED OPERATING TIME OF SECONDARY POWER SOURCE FROM NFPA 72 STANDBY 24 HOURS ALARM 5 MINUTES X 1/ 60 F 0.083 HOURS REQUIRED TOTAL SYSTEM REQ. STANDBY REQUIRED TOTAL SYSTEM REQUIRED ALARM STANDBY TIME STANDBY CURRENT CAPACITY ALARM TIME ALARM CIRCUIT CAPACITY (HOURS) (AMPS) (AMP- HOURS) (HOURS) (AMPS) (AMP- HOURS) 24 0.075 1.8 0.083333333 F 5.165 0.4304 REQ. STANDBY REQUIRED ALARM TOTAL REQ. OPTIONAL REQ. BATTERY CAPACITY CAPACITY CAPACITY FACTOR OF CAPACITY (AMP- HOURS) (AMP - HOURS) (AMP- HOURS) SAFETY (AMP- HOURS) 1.8 r 0.4304 r 2.2304 1.2 2.6765 1 7.0 AIR Supplied l h 44 %+ CLUCi.PEP' ( nC 1 7j _ SUPPF:c 3 I ' N SPE AIAARM SYSTEM TO BE pSTA1 f Li)1N e�i:i;'J� i%r CE WTIH NFPA 72; 70;101 ALEMANY dUiLllit� EF20000803 PH 786 350 6909 21iU� ' a) (D ai v cam. 0` cl cat M -v M c v E Y Q L: - L: 0 Q) Q) v C 0 �•C:�•° -' Urnccn4- a) �c000= <bi00 )0 w M D Z M O Lei >o of W ~t0 O W Z D Q (n ]� L / J T 01:D U') O (n W Q Z W J LL. Z a) W V to C -- CL ILA o -j UL'- c 0 no) 00 :3:2 00 o 0 (0 00 �0 0� 4 .E U LL_ W ^ cV •� to m� 0 0 n c to 0 E I\ c c a�0•c 0 v a) (D ai v cam. 0` cl cat M -v M c v E Y Q L: - L: 0 Q) Q) v C 0 �•C:�•° -' Urnccn4- a) �c000= <bi00 )0 w M D Z M O Lei >o of W ~t0 O W Z D Q (n ]� L / J T 01:D U') O (n W Q Z W J LL. Z a) W V to C ILA -a 4 a) (D ai v cam. 0` cl cat M -v M c v E Y Q L: - L: 0 Q) Q) v C 0 �•C:�•° -' Urnccn4- a) �c000= <bi00 )0 w M D Z M O Lei >o of W ~t0 O W Z D Q (n ]� L / J T 01:D U') O (n W Q Z W J LL. Z a) W V