Loading...
14-1037-009ROOF (3) #4 & (1) #8G -2 "i EXISTING PENTHOUSE I PENTHOUSE EXISTING CRAWL SPACE BELOW ELEVATOR PENTHOUSE WITH ACCESS PANEL i i I ' I I i i C RAW LS PACE — - - - - - - -- - - — - -- - - -� -- ► -- i �- - - - -- r', � tr -- - -- �1 - - -- - -- - - -- PROPOSED 200A GENERATOR PLUG 2ND FLOOR FPE 1200A SWITCHBOARD FPE 3000A, SECTION 120/208V, 30, 4W SWITCHBOARD (3) #3/0 & (1) #4G -2 "C O I EXISTING BUILDING WALL i SERVICE CORRIDOR PROPOSED 200 AMP DISCONNECT i (3)#3/0 & (1) #4G -2 "C I I I I ! I I I I I I I i i PROPOSED 200A METER IN I I ACCORDANCE WITH ELECTRIC UTILITY CO. REQUIREMENTS i PROVIDE 2P /200A CIRCUIT BREAKER IN EXISTING AVAILABLE SPACES IN SWITCHBOARD. CONTRACTOR TO TAP 2 OF THE 3 EXISTING BUSSES TO PROVIDE 120/208V, 10, 3W SERVICE TO VZW EQUIPMENT. CIRCUIT BREAKER TO MATCH EXISTING AIC RATING OF EXISTING CIRCUIT BREAKERS AND BE j COMPATIBLE WITH EXISTING SWITCHBOARD. GRADE/GROUND FLOOR I NOTE: ALL CONDUITS TO BE RGS ABOVE GRADE, SCH 80 PVC BELOW GRADE, UNLESS NOTED OTHERWISE. SINGLE LINE POWER DIAGRAM E -1 SCALE: NTS 4' -0" POST V.I.F. CONTRACTOR TO INSTALL TALLER RAIL POSTS TO AACCOMMMMODATE TELCO AND I `L P1000 UNISTRUT MOUNTED TO x PLATFORM HANDRAILS WITH , 1/2- U -BOLTS M?) c--'j -! o (CoNTpwm m I FIELD LOCATE) I c� +I+ 2" FIBER CONDUIT FROM BTS CABINET 3" FIBER CONDUIT FROM DEMARC WITH PULL STRING PROPOSED TELCO CABINET (BY CHARLES INDUSTRIES OR EQUAL) WITH HEAT EXCHANGER FOR FIBER 4' -0" TO POST (V.I.F. n t] 2" POWER CONDUIT TO ATS 2" POWER CONDUIT TO BTS /LTE CABINET TELCO /POWER BACKBOARD ELEVATION SCALE: 1" 1' -0' PROPOSED VERIZON WIRELESS PPC CABINET BY INTERSECT (MP -VW SERIES) (20" W x 39" H X 11" D) + z _J v_ 0 = o co N 0' n IY X11 ` CONDUIT TO GENERATOR r" POWER CONDUIT 0 BATTERY CABINET :" CONDUIT TO TELCO CABINE POWER CONDI " PPC 2" POWER CONDUI TO DISCONNECT J" CONDUIT TO GENERATOR FOR CONTROL CIRCUIT PANEL NAME: VERIZON WIRELESS LOCATION: AC PANEL PANEL RATING 200 AMPS PHASE 1 120/208 VOLTS WIRE 3 X MCB RATING 200 AMP MAIN LUG ONLY CKT N0. DESCRIPTION KVA AMP WIRE GND GND WIRE AMP KVA DESCRIPTION CKT NO. A B POLE POLE A B 1 SURGE SUPRESSO 3 40/2 1 #5 #6 #6 #2 100/2 10 4.0 BTS CABINET 2 3 - 3 10 4 5 LTE CABINET 8 60/2 #4 #8 #12 #12 20/2 1 EBRE 6 7 - 8 - 1 8 9 GFCI RECEPTACLE 1 - 20/1 #12 #12 80/2 SPARE 10 11 GENERATOR BLOCK HEATER - 1 20/1 #10 #10 12 13 GENERATOR BATTERY CHARGER 1 - 20/1 #10 #10 SPACE 14 15 SPACE SPACE 16 17 SPACE SPACE 18 19 SPACE SPACE 20 21 SPACE SPACE 22 23 SPACE SPACE 24 SUB TOTAL KVA (CONT) 9 9 11 11 SUB TOTAL KVA (CONT) SUB TOTAL KVA (NON -CONT) 4 3 0 0 SUB TOTAL KVA (NON -CONT) TOTAL KVA NON -CONT + 125% CONT. 29.0 139.4 TOTAL AMPS M EC HAN I CAL ROOM PROPOSED GENERAC 200A ATS WITH (2) INTEGRAL TVSS UNITS & (1) #4G -2 "C (4) #10 & (1) #10G -3/4 "C 1 #4/0 & (1) #2G -2 1/2 "C * PRE WIRED AT FACTORY (3) #3/0 & (1) #4G -2 "C PROPOSED GENERAC 200A MTS PROPOSED 50KW GENERATOR " C WITH CATS CABLE f1�AMl.M •A"f11�1A ►� UM•1n PY.l� NOTE: FASTEN CABINETS TO WALL PER MANUFACTURER SPECIFICATIONS 4 MTS ATS ELEVATION E -1 SCALE: 1" a 1' -0" 2A PANEL SCHEDULE E -, SCALE: NTS F I F PROPO� CONDUI F FIBER SERVICE PROPOSED 3" ^SED �BINET oor�POSED CABINET �F F PROPOSED FIBER SOURCE AT 8TH FLOOR MECHROOM (BY FPL FIBERNET) VNER CONDUIT 3ENERATOR PLUG 'OWER CONDUIT GENERATOR EXISTING FLOOR SLAB CONDUIT FOR FIBER SERVICE PROPOSED TELCO CABINET (BY CHARLES INDUSTRIES OR EQUAL) WITH HEAT EXCHANGER FOR FIBER NOTE: ALL CONDUITS TO BE RGS UNLESS NOTED OTHERWISE. 2 SINGLE LINE TELCO DIAGRAM 11L1 SCALE: WS RGS CONDUIT NOTE ALL RGS CONDUITS HOUSING WIRING FOR PLATFORM MOUNTED EQUIPMENT SHALL BE ROUTED ON THE UNDERSIDE OF THE PROPOSED PLATFORM. CONDUIT SHALL BE FASTENED TO STRUCTURAL STEEL OR GRATING WITH GALVANIZED STEEL CONDUIT STRAPS OR BEAM CLAMPS. FINAL LOCATION OF CONDUITS TO BE DETERMINED IN FIELD BY CONTRACTOR. UTILITY SERVICE NOTES 1. PROPOSED POWER AND FIBER CONDUITS SHALL BE CORED THROUGH EXISTING ROOF AND FLOOR SLABS AS NECESSARY TO ROUTE TO CLOSEST AVAILABLE POWER AND TELCO DEMARCS WITH SUFFICIENT CAPACITY TO ACCOMMODATE THE PROPOSED EQUIPMENT. CONTRACTOR TO VERIFY ROUTING WITH FACILITIES MANAGER PRIOR TO CONSTRUCTION. CONTRACTOR SHALL REUSE EXISTING CONDUITS TO THE GREATEST EXTENT POSSIBLE. 2. CONDUIT PENETRATION LOCATION SHALL BE PRECEDED BY AN X -RAY SCAN OF THE ROOF AND FLOOR SLABS TO ENSURE SLAB REINFORCING IS NOT COMPROMISED DURING CORING. 0 No r— --- --- - ^; verryonwimim 777 YAMATO DRIVE, SUITE 600 BOCA RATON, FL 33431 • PLANNING . ENGINEERING • SURVEWNG • CONSTRUCTION MANAGEMENT TECTONIC Engineering & Surveying Consultants P.C. 36 British American Blvd., Suite 101 Latham, NY 12110 Phone: (518) 783 -1630 Fax: (518) 783 -1544 www.tectonicengineering.com PRELIMINARY /CONSTRUCTION RF ENG. DATE: EQPT. ENG. DATE: OPERATIONS DATE: CONST. MGR. DATE: NETWORK ENG. DATE: REAL ESTATE DATE: 4 12/30/13 WORK ORDER NUMBER DRAWN RY 6097.68304A TJH j NO_ DATE ISSIJF 0 6/10/13 FOR COMMENT 1 7/11/13 PER COMMENTS 2 7/19/13 FOR PERMIT 3 9/3/13 FOR CONSTRUCTION 4 12/30/13 REVISED GENERATOR FOR CONSTRUCTION 5 3/17/14 REVISED EQUIPMENT FOR CONSTRUCTION I RELEASED BY DATE t��Ouaar pea '�. °OOo iq ° °e ,�^G O 07 ^``2 V• e O O P O o lx� � /� rp �+ m STAT O •ooeoe0 0INA 1,��o�o� UNAUTHORIZED ALTERATION OR ADDITIONS TO A PLAN BEARING THE SEAL OF A LICENSED ENGINEER OR LAND SURVEYOR IS A VIOLATION OF ACCEPTED ENGINEERING PRACTICES IN THE STATE OF FLORIDA PURSUANT TO SECTION 471 FLORIDA STATUTES. COPIES OF THIS DOCUMENT WITHOUT A FACSIMILE OF THE SIGNATURE AND AN ORIGINAL EMBOSSED SEAL OR ORIGINAL STAMP IN BLUE OR RED INK OF THE PROFESSIONAL ENGINEER OR LAND SURVEYOR SHALL NOT BE CONSIDERED VALID COPIES. 0 1 2 3 ORIGINAL SIZE IN INCHES �II�ICf1�Jii;d�lll��l' SUNSET STATION 5975 SUNSET DRIVE CITY OF SOUTH MIAMI MIAMI DADE COUNTY FL 33143 JFitt I I I I L.t SINGLE LINE DIAGRAMS & DETAILS i SHEET NUMBER E�l