System No, F -A -2031
F Rating - 2 Hr
T Rating -1 Hr
L Rating At Ambient - Less Than 1 CFM /sq ft (See Item 3B)
L Rating At 400 F - Less Than 1 CFM /sq ft (See Item 3B)
W Rating - Class 1 (See Items 1, 3A and 315)
Section A -A
1. Floor Assembly - Min 2 -1/2 in. (fro mm) thick reinforced lightweight or normal weight (100 -150 pcf or 1600 -2400 kg /m3)
concrete floor. Max diam of opening is 6 in. (203 mm). For W Rating, the min concrete thickness is 4 -1/2 in. (114 mm).
Floor may also be constructed of min 6 in. (152 mm) thick hollow core UL Classified precast Concrete Units *. Max diam
of opening in precast floors is 7 in. (178 mm).
See precast Concrete Units (CFTV) category in Fire Resistance Directory for names of manufacturers.
2. Through penetrants - One nonmetallic pipe or conduit to be installed either concentrically or eccentrically within the
firestop system. The annular space between the pipe or conduit and the periphery of the opening shall be min 314 in. (19
f floor r wall. As an option,
i r conduit to be rigidly supported an both sides o 00 0
mm) to a max of 2 -3/4 in. (70 mm). The pipe o g y pp
the pipe or conduit may be cast or grouted into the floor. The following types and sizes of pipes or conduit may be used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular or solid core PVC
pipe for use in closed (process or supply) or vented (drain, waste, or vent) piping systems.
B. Rigid Nonmetallic Conduit (RNC)+ - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVC conduit installed
in accordance with the National Electrical Code (NFPA No. 70).
C. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR13.5 CPVC pipe for
use in closed (process or supply) piping systems.
D. Acrylonitrile butadiene Styrene (ASS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular or
solid core ASS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
3. Firestep System - The firestop system shall consist of the following:
A. Packing Material - Min 2 in. (51 mm) thickness of min 4 pcf (64 kg /m3) mineral wool batt insulation firmly
required
' I t e recessed from to surface of floor as
anent form. Packing material o b q
packed into opening as a perm g P
to accommodate the required thickness of fill material. To achieve W Rating, min packing material depth
increased to 4 in. (102 mm). In floors constructed of hollow core precast concrete units, packing material to
extend throughout thickness of floor flush with bottom of floor assembly.
7Z S eced Technolo ies Inc. 210 Evans Way Somerville NJ 08876
Reproduced courtesy of Underwriters Laboratories, Inc. u
Created or Revised: January 23, 2009 rti
STI F-A -2031
(800)992 -1180 • (908)526 -8000 •FAX (908)231 -1415 • E- Mailaechsery @stifirestop.com • We6site:wwwstifirestop.com FAGS 1 OF 2
B. Fill, Void or Cavity Material* - Sealant - (Optional) - Min 1/2 in. (13 mm) thickness of fill material applied within
the annulus, flush with top surface of floor.
SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, Pensil 300 Sealant
or SpecSeal Series SIL300 Sealant for floors or walls and Pensil 300 S/L Sealant or SpecSeal Series SIL300SL
Sealant for floors only.
W Rating applies only when a min 112 in. (13 mm) depth of Pensil 300, SpecSeal Series SIL300, Pensil
300 S1L or SpecSeal Series SIL300SL Sealants are used.
L Ratings apply only when sealant is used.
C. Steel Cover Plate - Two piece cover plate fabricated from min 0.022 in. (0.6 mm) thick galy steel. Cover plate
shall be cut to fit the outer circumference of the through penetrant and installed on bottom surface of floor. Steel
cover plate shall lap a min of 2 in. (51 mm) beyond the periphery of the opening and onto the bottom surface of
the concrete floor. Seams of cover plate shall overlap itself a min 2 in. (51 mm) and secured together by means
of two No. 8 by 3/4 in. (19 mm) long sheet metal screws. Cover plate shall be secured to bottom surface of the
concrete floor with min 114 in. (6 mm) diam by min 1 -1/4 in. (32 mm) long steel concrete screws in conjunction
with min 1 in. (25 mm) diam steel fender washers, spaced a max 6 in. (152 mm) OC.
D. Fill, Void or Cavity Material* - Wrap Strip - Nom 1/4 in. (6 mm) thick by 1 -1/2 in. (38 mm) wide (RED), nom 1/8
in. (3.2 mm) by 1 -1/2 in. (38 mm) wide (RED2), nom 3/16 in. (4.8 mm) thick by 2 in. (51 mm) wide (BLU) or nom
118 in. (3.2 mm) thick by 2 in. (51 mm) wide (111-1.12) intumescent strips faced on both sides with a plastic film.
For nom 1 -1/2 and 2 in. (38 and 51 mm) diam pipe, one layer wrapped around the through penetrant with the
ends butted and held in place with tape. For nom 2 -1/2 through 4 in. (64 through 102 mm) diam pipe, two layers
of wrap strips are individually wrapped around the through - penetrant with the ends butted and held in place with
masking tape. Butted ends in successive layers shall be offset. The wrap strips are wrapped around
through - penetrant on underside of steel cover plate.
SPECIFIED TECHNOLOGIES INC - SpecSeal RED Wrap Strip, SpecSeal RED2 Wrap Strip, SpecSeal BLU
Wrap Strip or SpecSeal BLU2 Wrap Strip
E. Steel Collar - Nam 1 -1/2 in. (38 mm) or 2 in. (51 mm) deep collar, dependent upon wrap strip width, with 1 in.
(25 mm) wide by 2 in. (51 mm) long anchor tabs for attachment to concrete and min 3/4 in. (19 mm) wide
retaining tabs tapering down to 1/4 in. (6 mm) wide and located opposite the anchor tabs. Steel collar fabricated
from 0.022 in. (0.6 mm) gal v steel. Steel collar, with anchor tabs bent outward 90 deg, wrapped tightly around
wrap strip layers with min 1 in. (25 mm) overlap at seam. Retainer tabs to be bent 90 deg toward pipe to lock
wrap strips in position. Anchor tabs to be pressed tightly against floor or wall surface(s), and collar to be secured
in place using a min of three No. 8 by 1/4 in. (6 mm) long steel screws. Collar to be secured to concrete surface
with 114 in. (6 mm) diam by min 1 -1/4 in. (32 mm) long steel concrete screws in conjunction with min 1 -1/4 in. (32
mm) diam steel fender washers. Collar to be secured to steel cover plate with No. 8 by 314 in. (19 mm) long steel
sheet metal screws. The number of fasteners is dependent upon the nom diam of the nonmetallic sleeve
Min
two fasteners, symmetrically located, are required for nom 1 -1/2 in. (38 mm) and 2 in. (51 mm) diam nonmetallic
sleeves. Min three fasteners, symmetrically located, are required for nom 2 -1/2 in. (64 mm) and 3 in. (76 mm)
diam nonmetallic sleeves. Min four fasteners, symmetrically located, are required for nom 3 -1/2 in. (89 mm) and
4 in. (102 mm) diam nonmetallic sleeves.
4. Firestop Device* - (Not Shown) - As an alternate to Items 3D and 3E, a firestop device consisting of a gals steel collar
lined with an intumescent material sized to fit the specific diam of the nonmetallic sleeve may be used. Device shall be
installed around nonmetallic sleeve in accordance with the accompanying installation instructions. Device incorporates
anchor tabs for securement to bottom surface of floor assembly. Collar to be secured to concrete surface with 1/4 in. (6
mm) diam by min 1 -1/4 in. (32 mm) long steel concrete screws in conjunction with min 1 -1/4 in. (32 mm) diam steel
fender washers. Collar to be secured to steel cover plate with No. 8 by 3/4 in. (19 mm) long steel sheet metal screws.
SPECIFIED TECHNOLOGIES INC - SpecSeal LCC Collar
+Bearing the UL Listing Mark
*Bearing the UL Classification Marking
Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876
Reproduced courtesy of Underwriters Laboratories, Inc. u
Created or Revised: January 23, 2009 m � F -A -2031
STI (800)992 -1180 • (908)5264000 • FAX (908)231 -8415 • E- Mail:techserv@stiflrestop.com • Website:www.stiflrestop.cem PAGE 2 OF 2
SYSTEM NO. F -A -2031 SCALE: N.T.S.
AT FLOOR OR WALL ASSEMBLY - 8" OR SMALLER PVC, CPVC, RNC, ABS
System No. C -AJ -2159
F Rating - 2 Hr
T Ratings - 0 and 1 Hr (See Item 3C)
L Rating At Ambient - Less Than 1 CFM /sq ft
L Rating At 400 F - Less Than 1 CFM /sq ft
W Rating - Class 1 (See Item 315)
I-00- "
U
A
1. Floor or Wall Assembly -Min 2 -1/2 in. (64 mm) thick reinforced lightweight orgiff "i*1 00 -150 pcf or 1600 -2400
k /m3 concrete floor or min 3 in. 76 mm thick reinforced lightweight or normal weight concrefe wall. Wall may also be
g ) ( )
constructed of any UL Classified Concrete blocks *. Diam of opening to be min 1/8 in. (3 mm) to max 1 -1/2 in. (38 mm)
larger than outside diam of through penetrant. Max diam of opening is 6 in. (152 mm).
See Concrete blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Through Penetrants - One nonmetallic pipe or conduit to be centered within the firestop system. The annular space
within the firestop system is dependent upon the max diam and type of through penetrant used as tabulated in Item 3C.
The following types and sizes of nonmetallic pipes and conduits may be used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular or solid core PVC pipe
for use in closed (process or supply) or vented (drain, waste, or vent) piping systems.
B. Acrylonitrile Butadione Styrene (ASS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 cellular or solid
core ASS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
C. Rigid Nonmetallic Conduit+ - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVC conduit installed in
accordance wth Article 347 of the National Electrical Code, (NFPA No. 70.)
D. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR 13.5 CPVC pipe for use
in closed (process or supply) piping systems.
3. Firestop System - The firestop system shall consist of the following:
Specified Technologies Inc. 210 Evans W2Y Somerville NJ 08876
Reproduced courtesy of Underwriters Laboratories, Inc. �`
Created or Revised: January 2, 2009 D C -AJ -2159
STI T (800)992 -1180 • (902)526 -8000 - FAX (908)231 -8415 • E- Mail:techsery @stifirestep.com • Website:www.stifirestep.com PAGE 1 OF 2
A. Packing Material - Min 2 in. (51 mm) thickness of 4 pcf (64 kg /m3) mineral wool firmly packed into opening as a
permanent form. Packing material to be recessed from top surface of floor or both surfaces of wall as required to
accommodate the required thickness of fill material. The use of the packing material within the firestop system is
dependent upon the max diam and type of the through penetrant as tabulated in 3C.
B. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. (13 mm) thickness of fill material applied within the annulus,
flush with top surface of floor or with both surfaces of wall. - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant,
Pensil 300 Sealant or SpecSeal Series SIL300 Sealant for floors or walls and Pensil 300 S/L Sealant or SpecSeal
Series SIL300SL Sealant for flors only.
W Rating applies only when Pensil 300, SpecSeal Series SIL300, Pensil 300 S/L or SpecSeal Series SIL300SL
Sealants are used.
C. Fill, Void or Cavity Material* - Wrap Strip . Nam 1/8 in. (3.2 mm) or 1/4 in. (6 mm) thick intumescent material faced
on both sides with a plastic film, supplied in 1 -1/2 in. (38 mm) wide strips. The layers of wrap strip are individually
wrapped around the through - penetrant with the ends butted and held in place with masking tape. Butted ends in
successive layers may be aligned or offset. The edge of the wrap strips shall abut the surface of the concrete floor or
wall. In floor assemblies, the wrap strips are installed on the bottom side of the concrete floor. In wall assemblies, the
wrap strips are installed on each side of the concrete wall. The T Rating of the firestop system is dependent upon the
max diam and type of through penetrant, nom annular space within the firestop system, the use of the packing
material within the firestop system and the number of wrap strips required as tabulated below:
Max Diam of Through
Type of Through
Nom Annular
Use of Packing
Layers of
T Rating
Penetrant, In. (mm)
Penetrant
Space In. (mm)
Mat'I
Wrap Strip
Hr
2 (51)
PVC Pipe, RNC Conduit
1/16(2)
Optional
1
0
Or CPVC Pipe
O
2 (51)
PVC Pipe, RNC Conduit,
3/4 (19)
Required
1
1
CPVC Pipe or ABS Pipe
<
4 (102)
PVC Pipe, RNC Conduit,
3/4(19)
Required
2
1
SPECIFIED TECWN0I.
CPVC Pipe or ABS Pi e
ES INC - SMOGS*-,
Z
`
D. Stool Collar - Collar fabricated from coils of precut 0.016 in. (0.4 mm) thick galv sheet steel available from wrap strip
manufacturer. Collar shall be nom 1 -1/2 in. (38 mm) deep with min 1 in. (25 mm) wide by 2 in. (51 mm) long anchor
tabs for securement to the concrete floor or wall. Retainer tabs, 3/4 in. (19 mm) wide tapering down to 3/8 in. (10 mm)
wide and located opposite the anchor tabs, are folded 90 degrees toward through - penetrant surface to maintain the
annular space around the through - penetrant and to retain the wrap strips. Steel collar wrapped around wrap strips
and through penetrant with a 1 in. (25 mm) wide overlap along its perimeter joint. Steel collar tightened around wrap
strips and through penetrant using min 1/2 in. (13 mm) wide by 0.028 in. (07 mm) thick stainless steel hose clamp
installed at midheight of the collar. As an alternate to the steel hose clamp, the steel collar can be secured together by
means of three No. 8 by 1/4 in. (6 mm) long steel sheet metal screws, Collar secured to concrete surface with min 1/4
in. (6 mm) diam by 1 -1/4 in (32 mm) long steel concrete screws in conjunction with min 1 in. (25 mm) diam steel
fender washers. The number of fasteners used is dependent upon the nom diam of the through penetrant. Two
fasteners symmetrically located, are required for nom 1 -1/2 in. (38 mm) and 2 in. (51 mm) diam through penetrants.
Three fasteners symmetrically located, are required for nom 2 -1/2 in. (64 mm) and 3 in. (76 mm) diam through
penetrants. Four fasteners symmetrically located, are required for nom 3 -1/2 in. (89 mm) and 4 in. (102 mm) diam
through penetrants. In floor assemblies, one collar is used on the bottom side of the concrete floor. In wall
assemblies, a cellar is used on each side of the concrete wall.
+Bearing the UL Listing Mark
*Bearing the UL Classification Marking
Specified Technologies Inc. 210 Evans Way Somerville NJ 08876
Reproduced courtesy of Underwriters Laboratories, Inc. u�
STI Created or Revised: January 2, 2009
c -AJ -2159
(800)992 -1180 • (908)526 -8000 • FAX (908)231 -8415 • E- Mail:techserv@stifirestop.com • Websitew.www.stifirestop.com PAGE 2 OF 2
SYSTEM NO. C -AJ -2 1 59 SCALE: N.T.S.
AT FLOOR OR WALL ASSEMBLY - 6" OR SMALLER PVC, CPVC, RNC, ABS
System No. W -L -2241
F Ratings -1 and 2 Hr (See Item 1)
T Ratings - 0, 1/4, 1 and 1 -3/4 Hr (See Item 2)
L Rating At Ambient - Less Than 1 CFM /sq ft
L Rating At 400 F - Less Than 1 CFM /sq ft
n
L A
Section A -A
1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board /stud wall assembly shall be constructed of the materials and in the
manner specified in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall
include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51
by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3 -1/2 in. (89 mm) wide and spaced max 24 in.
(610 mm) OC.
B. Gypsum board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition
Design.Diam of opening to be 1 in. to 1 -1/8 in. (25 to 29 mm) larger than outside diam of pipe.
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is
installed.
2. Through Penetrant - One nonmetallic pipe, conduit or tube to be installed eccentrically or concentrically within the firestop
system. Pipe, conduit or tube to be rigidly supported on both sides of the wall assembly, The following types and sizes of
nonmetallic pipes, conduits and tubes may be used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use
in closed (process or supply) or vented (drain, waste or vent) piping systems. Annular space shall be min 0 in. ( 0 mm, point
contact) to max 1 in. (25 mm).
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) SDR 13.5 or Schedule 80 CPVC pipe
for use in closed (process or supply) piping systems. Annular space shall be min 0 in. ( 0 mm, point contact) to max 1 in. (25
mm).
+ - accordance with
C. Rigid Nonmetallic Conduit Nom 2 in. (51 mm) diam (or smaller) Schedule 40 PVC conduit installed in a nce
Article 347 of the National Electrical Code (NFPA 70). Annular space shall be min 0 in. ( 0 mm, point contact) to max 1 in.
(25 mm).
=7- _: n Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876
Reproduced courtesy of Underwriters Laboratories, Inc. S STI Created or Revised: June 17, 2010 W L -2241
(800)992 -1180 • (908)526 -8000 • FAX (902)231 -8415 * E- Mail:techserv@stifirestep.com • Website:www.stifirestop.com PAGE 1 OF 2
D. Electrical Nonmetallic Tubing+ - Nom 2 in. (51 mm) diam (or smaller) PVC tubing installed in accordance with Article 331
of the National Electrical Code (NFPA 70). Annular space shall be min 0 in. ( 0 mm, point contact) to max 1 in. (25 mm).
E. Cross Linked Polyethylene (PEX) Tubing - Nom 1 in. (25 mm) diam (or smaller) SDR9 PEX tubing for use in closed
(process or supply) piping systems. Annular space shall be min 0 in. (0 mm, point contact) to max 1 in. (25 mm).
F. Acrylonitrile Butadiene Styrene (ASS) pipe - Nom 1 -1/2 in. (38 mm) diam (or smaller) Schedule 40 solid -core or cellular
core ASS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems. Annular space shall be
min 114 in. (6 mm) to max 3/4 in. (19 mm).
G. Polyvinyl Choride (PVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in
closed (process or supply) or vented (drain, waste or vent) piping system. Annular space shall be min 0 in. (0 mm, point
contact) to max 1 in. (25 mm).
H. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) SDR 17 CPVC pipe for use in closed
(process or supply) piping system. Annular space shall be min 0 in. (0 mm, point contact) to max 1 in. (25 mm).
When Item 2A or 25 Is used, the T Rating is 114 hr. When Item 2C, 2D, or 2E is used, the T Rating is 1 hr and 1 -3/4 hr
for 1 hr and 2 hr fire rated walls, respectively. When Item 2F is used, T Rating is 0 hr.
3. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both
surfaces of wall assembly. At point contact location, min 1/4 in. (6 mm) diam bead of fill material applied at nonmetallic
pipe /gypsum board interface on both surfaces of wall
SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant or Type WF300 Firestop Caulk (for wood studs only)
*Bearing the UL Classification Mark
Specified Technologies Inc. 210 Evans Way Somerville NJ 081176
Reproduced courtesy of Underwriters Laboratories, Inc, �`
STICreated or Revised: June 17, 2010 ) W-L-2241
(900)992 -1180 • (908)526 -8000 • FAX (908)231 -8415 • E- Maif:techsery @stifirestop.com • Website:www.stiflrestop.com FADE 2 OF 2
SYSTEM NO. W -L -2241 SCALE: N.T.S.
AT WALL ASSEMBLY - 3" OR SMALLER PVC, CPVC, RNC, ABS, PEX
Svstem No. C -AJ -2575
F Rating - 3 Hr
T Rating - 3 Hr
L Rating At Ambient - Less Than 1 CFM /sq °t
L Rating At 400 F - Less Than 1 CFM /sq P
W Rating - Class 1 (See Item 43)
3
48 1
2 3 A
Ill A.
4
4B 4
2 4
A
Section A -A
1. Floor or Wall Assembly - Min 4 -1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 -150 pcf or 1600 -2400 kg /m3)
concrete floor or min 5 in. (127 mm) thick reinforced lightweight or normal weight (100 -150 pcf or 1600 -2400 kg /m3) concrete wall .
Wall may also be constructed of any UL Classified Concrete blacks *, Floor may also be constructed of any 6 in. (152 mm) thick UL
Classified hollow core precast Concrete Units. Max diam of opening is 4 in. (102 mm).
See Concrete blacks (CAZT) and Precast Concrete Units* (CFTV) categories in the Fire Rev'A&Ince Directory for names of
manufacturers.
2. Steel Sleeve - (Optional) Nom 4 in. (102 mm) diam (or smaller) Schedule 40 (or heavier) steel pipe or nom 4 in. (102 mm) diam (or
smaller) No. 26 GA (0.022 in. or 0.56 mm thick) sheet metal sleeve with square flange spot welded to the sleeve at approx mid- height
and sized to be a min of 2 in. larger than the sleeve diam cast or grouted into floor or wall assembly cast or grouted into floor or wall
assembly, flush with floor or wall surfaces.
3. Through penetrants - One nonmetallic pipe to be installed either concentrically or eccentrically within the firestop system. The
annular space between pipe and sleeve (Item 2) shall be min 114 in. (6 mm) to max 1 -3 /8 in. (35 mm). When steel sleeve (Item 2) is
not provided, the annular space between pipe and periphery of opening shall be min 0 in. (point contact) to max 1 -5 /9 in. (41 mm).
Pipe to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of nonmetallic pipes may be used:
A. polyvinyl Chloride (PVC) pipe - Nom. 2 in. (51 mm) diam (or smaller) Schedule 40 solid -core or cellular core PVC pipe for use in
closed (process or supply) or vented (drain, waste or vent) piping system.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. (51 mm) diam (or smaller) SDR17 CPVC pipe for use in closed (process
or supply) or vented (drain, waste or vent) piping systems.
C. Rigid Nonmetallic Conduit+ - Nom 2 in. (51 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article
347 of the National Electrical Code (NFPA 70).
D. Cresslinkeol Polyethylene (PEX) Tubing - Nom 2 in. (51 mm) diam (or smaller) SDR 9 PE`' tubing for use in closed (process or
supply) piping systems.
4. Firestop System - The firestop system shall consist of the following:
A. Packing Material - Min 4 in. (102 mm) thickness of min 4 pcf (64 kg /m3) mineral wool batt in4 ulation firmly packed into opening as
a permanent form. Packing material to be recessed from top surface of floor or both surfaces of wall to accommodate the required
thickness of fill material. When precast concrete units are used, packing material to be recessed from top surface of floor to
accommodate the required thickness of fill material and to be installed flush with bottom surface of floor.
B. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. (13 mm) thickness of fill material appiicd within the annulus, flush with top
surface of floor or both surfaces o f wall assembly. Additionally, nom 1/2 in. ( 13 mm ) bead of fill material applied betwee n concrete
e
and penetrant interface.
SPECIFIED TECHNOLOGIES INC - SpecSeal LCI Sealant, SpecSeal Series SSS Sealant, Pensil 300 Silicone Sealant, or
SpecSeal Series SIL300 Sealant for floors or walls and Pensil 300 S/L Silicone Sealant or SpecSeal Series SIL300SL Sealant for
floors only,
W Ratings apply when Pensil 300, SpecSeal Series SIL300, Pensil 300S /L SpecSeal aer:ss SIL300SL Sealants are used.
*bearing the UL Classification Mark
Specified Technologies Inc. 210 Evans Way Somerville,_NJ 08876
Reproduced courtesy of Underwriters Laboratorios, Inc. �`
Created or Revised: January 2, 2009 m C AJ 2578
STI 800 992 - 1180.908 526 -8000 • FAX 902)231 -8415 i E- Mail:techsery stlflrestop.ccm • Webs': "; :w�rnw.stifiresto .com
t ) ( ) ( @ - p PAGE 1 OF 1
SYSTEM NO. C -AJ -2578 SCALE: N.T.S.
AT FLOOR OR WALL ASSEMBLY - 2" OR SMALLER PVC, CPVC, RNC, PEX
0
re
J_
Q
W
D
Z
_O
W
Z
W
1-.
W/
100
LL
J
U
F_
#ray• wVW
• C W
# E W
• W • W
•1r -v�U •
r
rc�u�r•�
v
W
# G i rr• Y CV i•
• • 4 W • r •
W G N W W •
U V W W W
u 4' # WOO Q k •
�J r
LanMar
DESIGN GROUP
Architecture e Planning
2450 Southwest 137th Avenue
Suite # 212
Miami, Florida 33175
305.226.1340
Fl. registration:
AA:26- 001927
IB :26- 001183
W
07,15.13
Scale:
As Shown
Job No.
U
Drawn by:
L.G.H.
Checked by:
H.O.A.
U_
U_
O
O
<
U
r
Z
`
CV
W
o
Q
C:
-
'
co
CT
4r!
_O
L7
CT
E
2
o
co
W
LO
�.
Q
V)
�.J
a -
t
Seal:
•r
Rey Martinez, Architect
AR 11555
Revisions:
No. Date Dept /Section By
1
2
3
4
5
b
Date:
07,15.13
Scale:
As Shown
Job No.
13 -1007
Drawn by:
L.G.H.
Checked by:
H.O.A.
A -6
r
r
0