13-1103R-004
DX SPLIT SYSTEM SCHEDULE UNIT DESIGNATION AHU -2 LOCATION CEILING AREA SERVICE PHARMACY UNIT TYPE HORIZONTAL NOMINAL TONS 2.0 EER /SEER 13.85/16.0 OUTSIDE AIR (CFM) 160 OUTSIDE ENTERING AIR TEMP.('F) SUMMER /WINTER 80 *DB/67'WB/95'DB WEIGHT (LBS) 82 ®� TOTAL AIR, (CFM) 850 w TYPE CENTRIFUGAL t EXTERNAL STATIC PRESSURE (IN. WC) 0.4" 8P x 5CFM /P + 591SF x 0.18CFM /SF = FAN MOTOR SIZE (HP) 1/3 SUPPLY CEILING DIFFUSER. CEILING MOUNTED MOTOR DRIVE TYPE DIRECT -� TOTAL CAPACITY, (MBH) 25,6 U SENSIBLE CAPACITY, (MBH) 19.1 z ENTERING AIR TEMPERATURE (OB /WB'F) 80.0/67.0 o LEAVING AIR TEMPERATURE (DB/WB'F) -/- AIR PRESSURE DROP (MAX.) IN. WC - PER SCHEDULE TOTAL CAPACITY (MBH) - = KW 3.0 = NO. OF HEATING STEPS 1 A.H.0 TYPE 1" TA CONDENSING UNIT AREA (SF) - M.V.D. EFFICIENCY (X) MERV 8 ELECTRICAL SERVICE (V /PH /Hz) 208/1/60 MCA/MOCP 17/20 MANUFACTURER RHEEM MODEL NUMBER RHKL- HM2417JA DIMENSIONS INCHES (WxDxH) 17.5x21.6x42.5 UNIT DESIGNATION CU -2 LOCATION PLATFORM UNIT TYPE AIR COOLED SIDE DISCHARGE WEIGHT (LBS) 199.5 of NUMBER /TYPE 1 m CAPACITY STEPS 1 C) RLA/LRA (EACH) 13.5/58.3 r TYPE PROPELLER U- NUMBER 1 z MOTOR (HP /FLA) -/1.1 L) DRIVE DIRECT REFRIGERANT 410 -A ELECTRICAL SERVICE (V /PH /Hz) 208/1/60 MCA/MOCP 18/30 MANUFACTURER RHEEM MODEL NUMBER RAMP- 024JEZ DIMENSIONS INCHES WxDxH 44.3x31.5x29.0 NOTES AND ACCESORIES SEE BELOW): ALL BELOW 1. PROVIDE FACTORY MOUNTED CIRCUIT BREAKER. 2. PROVIDE PROGRAMMABLE THERMOSTAT ACCUSTAT ES -U 55 -80. 3. PROVIDE FACTORY INSTALLED HEATER. 4. REFRIGERANT LINES SHALL BE TYPE "L" SEAMLESS COPPER. INSULATE SUCTION LINE WITH ARMAFLEX 3/4-,ABOVE 50' USE MANUFACTURER'S CAPACITY MULTIPLIERS AND BALANCE LINE SIZING INSTRUCTIONS. HVAC LEGEND SYMBOL DESCRIPTION — — — — EXISTING SUPPLY DUCT, SIZE AS NOTED — — — — EXISTING RETURN DUCT, SIZE AS NOTED 12 x10 SUPPLY DUCT, SIZE AS NOTED 1478" RA RETURN DUCT, SIZE AS NOTED 8 "D EXH EXHAUST DUCT SIZE AS NOTED 15P x 5CFM /P + 927SF x 0.06CFM /SF = • RIGID DUCT WITH MANUAL VOLUME DAMPER TOTAL REQUIRED = • (MVD) BRANCH TAP AT SUPPLY ®� TYPE 1 CEILING MOUNTED 3(LAY -IN) FLEXIBLE DUCT WITH MANUAL VOLUME TYPE 1 (SURFACE), TYPE 3(LAY -IN) trl DAMPER (MIN.D.) BRANCH TAP AT ALUMINUM FINISH 26 (WHITE) D SUPPLY. 8P x 5CFM /P + 591SF x 0.18CFM /SF = 146 CFM SUPPLY CEILING DIFFUSER. CEILING MOUNTED ®CD --" DISCHARGE PATTERN AS NOTED 1W, 2W, 3W, 4W -'w- © RETURN AIR GRILL (RAG), CEILING MOUNTED R.A. TOTAL PROVIDED 150CFM E.G. EEXHAUST AIR GRILL (EG) CEILING MOUNTED POINT OF CONNECTION - — --- - TO EXISTING LINE UT PROGRAMMABLE THERMOSTAT REFRIGERANT LINES, SIZES AS - PER SCHEDULE ' MANUAL VOLUME DAMPER A FD FIRE DAMPER R.A.G. RETURN AIR GRILL C.D. CEILING DIFFUSER A.H.0 AIR HANDLERS UNIT C.0 CONDENSING UNIT R.A. RETURN AIR M.V.D. MANUAL VOLUME DAMPER E.A EXHAUST AIR E.G EXHAUST GRILL B.D. BACK DRAFT DAMPER E EXISTING RL RELOCATED DN DN F/B FROM BELOW OH OVERHEAD SUPPLY AIR DISTRIBUTION SCHEDULE No. SYMBOL FACE OR CEILING BORDER TYPE MANUFACTURER MODEL No. CONSTRUCTION REMARK SMOKE DAMPERS -0018 MODULE SIZE FIRE RATED ENCLOSURE 15P x 5CFM /P + 927SF x 0.06CFM /SF = • FIRE RATED ROOF /FLOOR CEILING ASSEMBLY TOTAL REQUIRED = • Z RA ®� TYPE 1 CEILING MOUNTED 3(LAY -IN) 24 "X24" OR AS TYPE 1 (SURFACE), TYPE 3(LAY -IN) T1TUS TDCA -AA ALUMINUM FINISH 26 (WHITE) NECK SIZE TO MATCH CFM'S AG L/ 8P x 5CFM /P + 591SF x 0.18CFM /SF = 146 CFM NOTED ON PLANS CEILING MOUNTED TOTAL REQUIRED = 150 CFM DIFF O.B.D., AG -75, -95 RETURN AIR DISTRIBUTION SCHEDULE No. SYMBOL FACE OR CEILING BORDER TYPE MANUFACTURER MODEL No. CONSTRUCTION REMARK SMOKE DAMPERS -0018 MODULE SIZE FIRE RATED ENCLOSURE 15P x 5CFM /P + 927SF x 0.06CFM /SF = • FIRE RATED ROOF /FLOOR CEILING ASSEMBLY TOTAL REQUIRED = • Z RA 24"X24" TYPE 1 CEILING MOUNTED 3(LAY -IN) TITUS 350 FL ALUMINUM FINISH 26 (WHITE) NECK SIZE TO MATCH DUCT SIZE m REQUIRED NOTED ON PLANS 8P x 5CFM /P + 591SF x 0.18CFM /SF = 146 CFM GRILL WITH BORDER, 3/4" SPACING MECHANICAL SCOPE OF WORK AND NOTES: 1. SCOPE OF WORK INCLUDES THIS TENANT REMODELING IN THIS EXISTING BUILDING AS SHOWN. COMPLY WITH FBC 2010 AND ADDENDUMS. 2. EXISTING SPACE BEING SERVED BY TWO AIR HANDLER UNITS, ONE EXISTING AHU -1 (4 TONS) TO REMAIN AND ADEQUATE TO HANDLE THIS REMODELING AND ANOTHER AHU -2 (2 TONS) TO SERVE PHARMACY SPACE. 3. NO COMBUSTIBLE MATERIALS ALLOWED IN CEILING RETURN PLENUM. 4. BEFORE COMMENCING WORK CONTRACTOR SHALL VERIFY EXISTING CONDITIONS. 5. CONTRACTOR TO COORDINATE WITH ARCH /CLIENT FOR FINAL DIFFUSER AND GRILL MANUFACTURER AND MODEL SELECTION. 6. REFER TO ARCHITECTURAL PLANS FOR CEILING TYPES, COORDINATE DUCTWORK WITH EXISTING CEILING CONDITIONS. 7. REFER TO GENERAL NOTES FOR ADDITIONAL DETAILS NO MEDICATION PREPARATION UNDER THESE PREMISES. HVAC DESIGN REQUIRES YES NO DUCT SMOKE DETECTOR ASHRAE STANDARD 62 -2004 • FIRE DAM ER(S) AHU -1 • SMOKE DAMPERS -0018 • FIRE RATED ENCLOSURE 15P x 5CFM /P + 927SF x 0.06CFM /SF = • FIRE RATED ROOF /FLOOR CEILING ASSEMBLY TOTAL REQUIRED = • FIRE STOPPING TOTAL PROVIDED 150CFM • SMOKE CONTROL AHU -2 • Ke Plan ...h N 02 ` . N NTS 0' it 5' 10' 15' 02 E TO CONNECT u•YU CvIC'9"IAI/+ I V UUNNLU I WI I N CU -2 IN 2ND FL. orrre rn VVY or ♦Kr LAi,D 1. FIRE -RATED nFKnigrnir, Wei i Coot ••• • • • o • r • ••• ••• • •U •U • p n Ali w> AREA OF CU'S Mechanical Floor Plan Scale: 4" = 1' -0" F —_, F -- 1 I Cu I I Qu I (E) I I (E) I L - -J L —..._J r - --i QL I (E) I L - -J r -----1 QL I (E) I L - _. J F ` `- OUTSIDE AIR CALCULATIONS ORE COMMENCING WORK CONTRACTOR MIAMI, FLORDIA ASHRAE STANDARD 62 -2004 LL VERIFY EXISTING CONDITIONS FOR (E) I AHU -1 INSTALLATION OF CU -2 AREA -0018 REQUIRED SPACE 15P x 5CFM /P + 927SF x 0.06CFM /SF = 130 CFM r — — TOTAL REQUIRED = 130 CFM TOTAL PROVIDED 150CFM PERMIT FOR DETAILS. W M T- V �. am AHU -2 c*) H 00 j AREA m REQUIRED PHARMACY 8P x 5CFM /P + 591SF x 0.18CFM /SF = 146 CFM z TOTAL REQUIRED = 150 CFM L TOTAL PROVIDED 150CFM m Ke Plan ...h N 02 ` . N NTS 0' it 5' 10' 15' 02 E TO CONNECT u•YU CvIC'9"IAI/+ I V UUNNLU I WI I N CU -2 IN 2ND FL. orrre rn VVY or ♦Kr LAi,D 1. FIRE -RATED nFKnigrnir, Wei i Coot ••• • • • o • r • ••• ••• • •U •U • p n Ali w> AREA OF CU'S Mechanical Floor Plan Scale: 4" = 1' -0" F —_, F -- 1 I Cu I I Qu I (E) I I (E) I L - -J L —..._J r - --i QL I (E) I L - -J r -----1 QL I (E) I L - _. J F ` `- (E) L I (E L Condensing Unit Plan NTS E ORE COMMENCING WORK CONTRACTOR MIAMI, FLORDIA H LL VERIFY EXISTING CONDITIONS FOR (E) I --0016 INSTALLATION OF CU -2 (E) L I (E L Condensing Unit Plan NTS I (E) I L - -J CU-, __z (PLATFORM) F — I REF LINE F/B S.LL I II TO CONNECT (E) I II NTH lLZ L .... — J id "A'k INTERIOR MODIFICATIONS ONLY (ANY EXTERIOR MUD1F(CA'TICIN MAY REQUIRE 1 A 19OARD APPEARANCE) �• • o • •Iw � c • u yRAFAEL D +F�ALLtSTEROS, ARCHITECT 7431 SW 88 PLACE THE EXISTING CONDENSING MIAMI, FLORDIA 33173 UNIT AREA ACCESS AND (E) I --0016 PROTECTION (RAILING) IS FAX (305) 275 -0018 BEING REPAIRED UNDER A L — — J SEPARATE PERMIT r — — CONSULTANT- #13 -1280. REFER TO THIS T- E �(.00 PERMIT FOR DETAILS. I (E) I L - -J CU-, __z (PLATFORM) F — I REF LINE F/B S.LL I II TO CONNECT (E) I II NTH lLZ L .... — J id "A'k INTERIOR MODIFICATIONS ONLY (ANY EXTERIOR MUD1F(CA'TICIN MAY REQUIRE 1 A 19OARD APPEARANCE) �• • o • •Iw � c • u yRAFAEL D +F�ALLtSTEROS, ARCHITECT 7431 SW 88 PLACE MIAMI, FLORDIA 33173 TEL. (305) 275 --0016 FAX (305) 275 -0018 CELL (305) 790 -1996 FLORIDA REGISTRATION # AR0016490 CONSULTANT- T- E �(.00 W M T- V �. am c*) H 00 j v 8 z L W IU LL! ZL. 0 u © E W LO 0 � N U) T yJ W> I ' 5: AU CC) LO Gn cY) ° a) E Cz co U U~ Q Q M Q Va M � J W Q 0 Q ...7 w _y CO j O w� Y U 0 _ U� LL Z �• � _ C 0 U) Q _I Z Q U D .: U) W z Z n/ L.I_ LO F_ D NCCO rn 0 C L Lr) W U) ISSUE DATE PERMIT SET 9 -27 -13 Q BLDG. DEPT. 1/16/14 ® OWNER REV 04/14/14 PROJECT NO. 2013 - -5975 -01 DATE: 9 -27 -13 CADD FILE: DRAWN: S. C CHECKED: P. V SEAL: a, d u PABLO J. VITERI PE #a ":59535 SHEET TITLE: Mechanical Plan SHEET: M -1 OF SHEETS