13-1103R-003f. �i my FIRE PROTECTION --- GENERAL REMODELING NOTES 1. BEFORE COMMENCING WORK CONTRACTOR SHALL FIELD COORDINATE EXACT LOCATION AND POINT OF OF CONNECTION TO EXISTING SPRINKLER LINES WITH LANDLORD, FIRE MARSHAL, ORIGINAL DESIGN, AND EXISTING CONDITIONS AND DRAWINGS TO ASSURE INSTALLATION PER APPLICABLE STANDARDS. 2. RELOCATE HEADS AS PER EXISTING REFLECTED CEILING LAYOUT IN OFFICE SPACES. EXTEND PIPING AND PROVIDE HEADS AS REQUIRED. REFER TO ARMOVER DETAILS. 3. EQUIPMENT AND DEVICES SHALL BE UL AND FM APPROVED FOR SERVICE INTENDED. PIPING SHALL BE BLACK STEEL PIPE, SCHEDULE 40 ASTM A53 -78 GRADE A, SIZES 1" MIN AS SHOWN ON PLANS. LOCATE RECESSED HEADS IN CENTER OF CEILING TILES OR GRID SPACES. PIPE SIZING SHALL MAINTAIN VELOCITIES ESTABLISHED BY FM AND IN ACCORDANCE WITH NFPA 13, LOCAL AUTHORITIES, AND ORIGINAL BUILDING DESIGN. REFER TO ORIGINAL PERMIT BUILDING PLANS FOR DETAILS. 4. FIRE SPRINKLER SYSTEM TO BE TESTED AT 200 PSI FOR TWO HOURS MINIMUN 5. CONTRACTOR SHALL COORDINATE WITH TRADES TO RUN FIRE PROTECTION PIPING INSIDE CEILING SPACE AS CLOSE TO TOP OF SLAB AS POSSIBLE, WITHIN CEILING SPACES, TO CLEAR AIR CONDITIONING DUCTWORK, EXISTING PLUMBING AND TO AVOID CONFLICTS WITH OTHER TRADES. 6. CONTRACTOR SHALL PROVIDE A COMPLETE WORKING SYSTEM AS PER ORIGINAL BUILDING DESIGN. 7. CONTRACTOR SHALL NOT INSTALL ANY PIPING DIRECTLY ABOVE AN ELECTRICAL PANEL AS REQUIRED BY NEC. 8. SUBMIT SHOP DRAWINGS SIGNED AND SEALED BY A PROFESSIONAL ENGINEER IN THE STATE OF FLORIDA FOR APPROVAL OF ALL EQUIPMENT, MATERIALS, LAYOUTS AND HYDRAULIC CALCULATIONS IF REQUIRED PRIOR TO INSTALLATION. SPRINKLER HEAD SCHEDULE SYM DESCRIPTION TEMP MANUF. MODEL /SIN K ORIF. o SEMI- RECESSED PENDANT (STYLE 20 RECESSED ESCUTCHEON), QUICK RESPONSE, STANDARD COVERAGE 165 TYCO TY3221 5,g 1 /2" A. COORDINATE CLG. TYPE AND LOCATIONS WITH ARCH. AND TRADE PLANS. B. PROVIDE MANUFACTURER CHROME PLATED FINISH FOR ALL NON CONCEALED HEADS. SUPPLY LINE DESIGN CRITERIA AS PER NFPA 13 BUILDING AREA: 1,535SF OCCUPANCY TYPE MERCANTILE ORDINARY HAZARD GROUP 2 DENSITY : 0.2 GPM /SQFT OVER MOST REMOTE 1500SOFT MAXIMUN AREA COVERAGE PER HEAD: 130SQFT MAXIMUN SPACING : 15 FEET NSERT SUPPORT PER NFPA -13 " PIPE(MIN.) 1" x 1/2" REDUCER SEMI RECESSED PENDANT TYPE l— CEILING PER SPRINKLER HEAD IN RECESSED ARCHITECTURAL ESCUTCHEON. DRAWINGS SEMI — RECESSED PENDANT HEAD DETAIL N.T.S. HANGER SIZING TABLE PIPE SIZES MIN. HANGER ROD DIA. MIN. ANCHOR EMBEDMENT 1/28 - 1" 3/8" 1 9/16" 1" - 2" 3 /8" 1 9/16" 2 1/2" - 3" 1/2' 2" 4" - 5" 5/8" 2 16" 6" - a" 3/4" 2 S/1 fi" NOTE: POWDER ACTUATED STUDS SHALL BE USED IN STRICT ACCORDANCE WITH NFPA -13 AND SHALL BE LISTED FOR USE IN FIRE PROTECTION SYSTEMS. HANGER SPACING TABLE NOM. PIPE SIZES THRU 314" 1 1" 1 -1/4" 1 -1/2" 2" 2 -1/2" 3 " SCH. 40 STEEL (WATER) 7' j 7 7' 9' 10' 11' 12' F TES: FOR STRAIGHT HORIZONTAL RUNS OF PIPING SPACING SCHEDULED IS MAXIMUM SUPPORT SPACING IN FEET HANGER ROD FASTEN TO ROOF STRUCTURE PIPE HANGER DETAIL NTS NOTE: PROVIDE RESTRAINT AGAINST UPLIFT PER NFPA 13. IRE PROTECTION IPE EXIST. 1 —HR. FIRE —RATED DEMISING urns i see* 009 0 W.....__. -.�_., L ••• r • • • • L • • • Y t ••• •i• • b • • • f C: Y Y Y i • • 6 Y • Y • Y f ' • • • r arr. i • • • • RAFAL -D- 3ALCESTEROS, ARCHITECT 7431 SW 88 PLACE MIAMI, FLORDIA 33173 TEL. (305) 275 -0016 FAX (305) 275 -0018 CELL (305) 790 -1996 FLORIDA REGISTRATION # AR0016490 ___ ___ _- .__......_.... CONSULTANT: N o2 Fire Protection Ground Floor Plan Scale: %" = 1' -0" FIRE PROTECTION LEGEND SYM DESCRIPTION OE EXISTING SEMI - RECESSED HEAD r O `.) T U TO REMAIN ®RL EXISTING SEMI- RECESSED HEAD cy) TO BE RELOCATED EXISTING SEMI - RECESSED HEAD LL 00 (1) REMOVED o NEW SEMI - RECESSED HEAD — — — EXISTING FP PIPE TO REMAIN POINT OF CONNECTION cu o 0� TO EXISTING LINE NEW FP PIPE ....��. HANGER FP FIRE PROTECTION RL RELOCATED E EXISTING 0' it 5' 10' 15' SCOPE OF WORK AND EXISTING FIRE PROTECTION SYSTEM NOTES: 1. SCOPE OF WORK INCLUDES THIS TENANT REMODELING IN THIS EXISTING BUILDING AS SHOWN ON PLANS. REFER TO ARCHITECTURAL PLANS FOR ADDITIONAL DETAILS. 2. THE REMODELED AREA IS RE -USING EXISTING FP LINES TO PROVIDE COVERAGE TO THIS MEDICAL OFFICE. 3. CONTRACTOR TO VERIFY EXACT LOCATION OF EXISTING PIPING. COORDINATE WITH FIRE DEPARTMENT FOR ANY SYSTEM SHUT -DOWN AND FIRE WATCH AS REQUIRED. 4. CONTRACTOR SHALL PROVIDE COMPLETE SHOP DRAWINGS AND HYDRAULIC CALCULATIONS REFLECTING FINAL PIPING, HANGER, HEADS AND DETAILS. 5. BEFORE COMMENCING WORK CONTRACTOR SHALL COORDINATE WITH ARCHITECTURAL, MECHANICAL AND ELECTRICAL PLANS FOR CEILING TYPES, LIGHTING, A/C DIFFUSSERS, DUCTWORK TO AVOID CONFLICTS. 6. REFER TO FP NOTES FOR ADDITIONAL DETAILS. INTERIOR MODIFICATIONS ONLY (ANY EX'T'ERIOR MODIFICATION NIAY REQUIRE A 30ARD APPEARANCE) 12 2013 - 5975_01 I DATE: 9-27-13 q3 U r O `.) T U DRAWN: S. C CHECKED: cy) LL 00 (1) uj ,n "a cu o 0� '^''�' L ''y ❑ x u W cu LL W w L L.i 06 Z o z s W o E cn o C C 4t N r � � N � co 00 .- o 0-) �n cn z C) N a� © .-- cz co a� E so H Q) U UQ Q cy) � C LL. Cy) U) Cy) Q W ' L.L.I (f) > 0 LIJ LL U U) u W 0 (n J z Q = I = LLI O i O vJ - ----- -._.. _ ------------- ISSUE - DATE PERMIT SET 9 -27 -13 A OWNER REV 04/14/14 i PROJECT N0. 2013 - 5975_01 I DATE: 9-27-13 CADD FILE: DRAWN: S. C CHECKED: P y SEAL: : SHEET. FP -1 OF SHEETS