13-1103-015FIRE PROTECTION — GENERAL REMODELING NOTES
1. BEFORE COMMENCING WORK CONTRACTOR SHALL FIELD
COORDINATE EXACT LOCATION AND POINT OF OF CONNECTION TO
EXISTING SPRINKLER LINES WITH LANDLORD, FIRE MARSHAL,
ORIGINAL DESIGN, AND EXISTING CONDITIONS AND DRAWINGS TO
ASSURE INSTALLATION PER APPLICABLE STANDARDS.
2. RELOCATE HEADS AS PER EXISTING REFLECTED CEILING LAYOUT
IN OFFICE SPACES. EXTEND PIPING AND PROVIDE HEADS AS
REQUIRED. REFER TO ARMOVER DETAILS.
3. EQUIPMENT AND DEVICES SHALL BE UL AND FM APPROVED FOR
SERVICE INTENDED. PIPING SHALL BE BLACK STEEL PIPE,
SCHEDULE 40 ASTM A53 -78 GRADE A, SIZES 1" MIN AS SHOWN
ON PLANS. LOCATE RECESSED HEADS IN CENTER OF CEILING
TILES OR GRID SPACES. PIPE SIZING SHALL MAINTAIN VELOCITIES
ESTABLISHED BY FM AND IN ACCORDANCE WITH NFPA 13, LOCAL
AUTHORITIES, AND ORIGINAL BUILDING DESIGN. REFER TO ORIGINAL
PERMIT BUILDING PLANS FOR DETAILS.
4. FIRE SPRINKLER SYSTEM TO BE TESTED AT 200 PSI FOR TWO
HOURS MINIMUN
5. CONTRACTOR SHALL COORDINATE WITH TRADES TO RUN FIRE
PROTECTION PIPING INSIDE CEILING SPACE AS CLOSE TO TOP OF
SLAB AS POSSIBLE, WITHIN CEILING SPACES, TO CLEAR AIR
CONDITIONING DUCTWORK, EXISTING PLUMBING AND TO AVOID
CONFLICTS WITH OTHER TRADES.
6. CONTRACTOR SHALL PROVIDE A COMPLETE WORKING SYSTEM AS
PER ORIGINAL BUILDING DESIGN.
7. CONTRACTOR SHALL NOT INSTALL ANY PIPING DIRECTLY ABOVE
AN ELECTRICAL PANEL AS REQUIRED BY NEC.
8. SUBMIT SHOP DRAWINGS SIGNED AND SEALED BY A
PROFESSIONAL ENGINEER IN THE STATE OF FLORIDA FOR
APPROVAL OF ALL EQUIPMENT, MATERIALS, LAYOUTS AND
HYDRAULIC CALCULATIONS IF REQUIRED PRIOR TO INSTALLATION.
SPRINKLER HEAD SCHEDULE
SYM
DESCRIPTION
TEMP
MANUF.
MODEL- /SIN
K
ORIF.
O
SEMI-RECESSD PENDANT (S 20 RECESSED
ESCUTCHEON), QUICK RESPONSE STANDARD COVERAGE
165
TYCO
TY3221
5.6
1/2"
A. COORDINATE CLG. TYPE AND LOCATIONS WITH ARCH. AND TRADE PLANS.
B. PROVIDE MANUFACTURER CHROME PLATED FINISH FOR ALL NON CONCEALED HEADS.
SUPPLY LINE
DESIGN CRITERIA AS PER NFPA 13
BUILDING AREA: 1,535SF
OCCUPANCY TYPE MERCANTILE
ORDINARY HAZARD GROUP 2
DENSITY : 0.2 GPM /SQFT OVER MOST
REMOTE 1500SQFT
MAXIMUN AREA COVERAGE PER HEAD 130SQFT
MAXIMUN SPACING : 15 FEET
NSERT
SUPPORT PER
NFPA -13
" PIPE(MIN.)
1" x 1/2" REDUCER
SEMI RECESSED PENDANT TYPE L-CEILING PER
SPRINKLER HEAD IN RECESSED ARCHITECTURAL
ESCUTCHEON. DRAWINGS
SEMI — RECESSED PENDANT HEAD DETAIL
N.T.S.
HANGER SIZING TABLE
PIPE SIZES
MIN. HANGER
ROD DIA.
MIN. ANCHOR
EMBEDMENT
1/2" - 1"
3/8"
1 9/16-
1" - 2"
3/80'
1 9/16'
2 1/2" - 3"
1/2"
2"
4' - 5"
5/80
1 2 9/16w
6" - 8"
3/4"
1 2 9/16"
NOTE: POWDER ACTUATED STUDS SHALL BE USED IN STRIC'r'ACCORDANCE WITH
NFPA -13 AND SHALL BE LISTED FOR USE IN FIRE PROTECTION SYSTEMS.
HANGER SPACING TABLE
NOM. PIPE SIZES
THRU 3/4"
1 1"
11 -1/4"
1 -1/2"
1 2"
2 -1/2"
3" -6"
SCH. 40 STEEL (WATER)
7'
7'
1 7'
9'
10'
11'
1 12'
NOTES:
1. FOR STRAIGHT HORIZONTAL RUNS OF PIPING
2. SPACING SCHEDULED IS MAXIMUM SUPPORT SPACING IN FEET
HANGER ROD FASTEN TO
ROOF STRUCTURE
PIPE HANGER DETAIL
NTS
NOTE: PROVIDE
RESTRAINT
AGAINST UPLIFT
PER NFPA 13.
RE PROTECTION
IPE
EXIST. 1 —HR.
FIRE —RATED
DEMISING
is N
P-',D A!• . '(JNCEPTUAT t t;,-�O� QN:[ j'
FIR PROTEC,470v ` ONTRACTORIS
R ORKING PLA'' . AS PER NFPA 13
AFJST BE SUBMIT TE�p) TO AND APPROVED B ;.
THE MTAN,.I D _ DE FIRE DEPARTMENT
4`FFORE ANY FiltE PROTECTION SYSTEM
TS INSTALLED OR REMODE, >✓J�
BV
" ar
Fire Protection Ground Floor Plan
Scale: %4" = 1' -0"
FIRE PROTECTION LEGEND
SYM
DESCRIPTION
OE
EXISTING SEMI - RECESSED HEAD
A '°
TO REMAIN
®RL
EXISTING SEMI - RECESSED HEAD
TO BE RELOCATED
EXISTING SEMI - RECESSED HEAD
REMOVED
O
NEW SEMI - RECESSED HEAD
— — —
EXISTING FP PIPE TO REMAIN
POINT OF CONNECTION
TO EXISTING LINE
NEW FP PIPE
�L—
HANGER
FP
FIRE PROTECTION
RL
RELOCATED
E
EXISTING
0' it 5' 10' 15'
SCOPE OF WORK AND EXISTING
FIRE PROTECTION SYSTEM NOTES:
1. SCOPE OF WORK INCLUDES THIS TENANT
REMODELING IN THIS EXISTING BUILDING AS
SHOWN ON PLANS. REFER TO ARCHITECTURAL
PLANS FOR ADDITIONAL DETAILS.
2. THE REMODELED AREA IS RE -USING EXISTING
FP LINES TO PROVIDE COVERAGE TO THIS
MEDICAL OFFICE.
3. CONTRACTOR TO VERIFY EXACT LOCATION OF
EXISTING PIPING. COORDINATE WITH FIRE
DEPARTMENT FOR ANY SYSTEM SHUT -DOWN
AND FIRE WATCH AS REQUIRED.
4. CONTRACTOR SHALL PROVIDE COMPLETE SHOP
DRAWINGS AND HYDRAULIC CALCULATIONS
REFLECTING FINAL PIPING, HANGER, HEADS
AND DETAILS.
5. BEFORE COMMENCING WORK CONTRACTOR
SHALL COORDINATE WITH ARCHITECTURAL,
MECHANICAL AND ELECTRICAL PLANS FOR
CEILING TYPES, LIGHTING, A/C DIFFUSSERS,
DUCTWORK TO AVOID CONFLICTS.
6. REFER TO FP NOTES FOR ADDITIONAL
DETAILS.
F
..
00000
000 .. . . .
.......... ........................... . . .. s .
n�
A�
3
r
M
�t
qr
�y
a
A
• RAr`AEL Fl.,19ALIfSTFPGS,,ARCHITECT o
7431 SW 88 PLACE
MIAMI, FLORDIA 33173
TEL. (305) 275 -0016
A '°
FAX (305) 275 -0018
CELL (305) 790 -1996
FLORIDA REGISTRATION # AR0016490
CONSULTANT. _
Y
ATE
(0
(0 O
r _ U
0
cM4a�'
Fn J O N
c LL
>
Lu LO
�
0 U O M
y
U N
LL
'
LLJ
~�
Z C,
(_ v
D c
z
W v O E
N LO 0
* N 0
r
U. r a) CM
M 'a• CL
C@J r
1
,n CO
o C3) �LcLo
O •—
Z N M
..a
C)
Q
CCOO W
P .
ti
UQ
0
U)
r
J
Q
_j
2
W
W
�a
�
w
LL
LL Z
LL
O 'L^ )
V
Ze x•«.
1
'
IUD a W
z LO ~
�_
o C D
a G LL LO U)
v
----------------------------------------------------------- ........ .--- ------------------------
ISSUE DATE
g
---------------------------------------------------- - - - - -- --------------------------- - - - - --
PERMIT SET 9 -27 -1 �
e"
f•
�.
-------------------------------------- -- -------- ------- --- ---------------- - - - - --
PROJECT NO. 2013- 5975 -01
DATE: 9-27-13
CADD FILE:
DRAWN: SIC
CHECKED: P.V
SEAL:
.. L'°
.
J Jr
"
'0
PABLO J. tiITERI
PE# 59535
................................................................... ...............
SHEET TITLE:
.......... . . . . ..
Fire Protection Plan
---------------------------------------------------------------------------------------
SHEET'
---------
r,
FP-1
OF SHEETS
*V=41