13-1103-013MECHANICAL H VAC NOTES
1. GENERAL
A. ALL WORK TO BE DONE IN ACCORDANCE WITH NFPA 90 —A; ASHRAE GUIDE AND SMACNA DUCT CONSTRUCTION
STANDARDS AS WELL AS WITH FBC 2010 AND ADDENDUMS, ALL STATE AND LOCAL CODES HAVING
JURISDICTION. CONTRACTOR SHALL VERIFY ALL SPACE CONDITIONS AT JOB SITE PRIOR TO SUBMITTING BID
PROPOSAL.
2. WORKMANSHIP
A. ALL WORK SHALL BE PERFORMED BY A LICENCED AIR CONDITIONING CONTRACTOR. WORK SHALL BE DONE IN A
FIRST CLASS MANNER, FULLY OPERATIVE, AND TO THE ACCEPTANCE OF THE ARCH ITECT/EN GINNER.
CONTRACTOR SHALL PROVIDE FOR ALL NECESSARY LABOR AND MATERIAL REQUIRED FOR COMPLETION OF THE
WORK INCLUDING BUT NOT LIMITED TO CONNECTIONS TO RELATED WORK SUCH AS CONNECTION TO EXISTING
SYSTEM, EXCAVATIONS AND BACKFILLING.
3. PERMITS AND INSURANCE
A. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL INSURANCE, PERMITS, FEE, TAXES, INSPECTIONS, TEST, FINES
AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF COMPLETE AIR CONDITIONING SYSTEM AS OUTLINED
HEREIN AND SHOWN ON PLANS. PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY
AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
4. DUCTWORK
A. ALL METAL DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED STEEL IN ACCORDANCEWITH THE LATEST
INDUSTRY STANDARDS, PUBLISHED BY THE SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL
ASSOCIATION, INC. (SMACNA) "HVAC DUCT CONSTRUCTION STANDARD" MANUAL AND THE LATEST ASHRAE
HANDBOOKS.IF APPROVED BY OWNER, ALL AIR CONDITIONING AND VENTILATION AIR DUCTS SERVING UNITS TO
BE MINIMUM 1" THICK (R -4.2 MIN), FIBERGLASS WITH VAPOR BARRIER. FABRICATION AND INSTALLATION OF
FIBERGLASS DUCTWORK SHALL BE IN COMPLETE ACCORDANCE WITH THE LATEST REQUIREMENTS OF DUCT
CONSTRUCTION MANUAL BY SMACNA LATEST EDITION AND ASHRAE.DUCT DIMENSIONS ARE IN INCHES AND
CORRESPOND TO INSIDE DIMENSIONS WIDTH x HEIGHT. PROVIDE TURNING VANES AT ALL ELBOWS.
B. ALL INTERIOR EXPOSED SUPPLY AIR CONDITIONING DUCTWORK SHALL BE LINED WITH 1" THICK, TYPE 300 GLASS
FIBER, ACOUSTIC THERMAL DUCT LINER IN ACCORDANCE WITH THE SMACNA DUCT LINER APPLICATION
STANDARD.
C. EXPOSED DUCTWORK MATERIALS: WHERE DUCTWORK IS INDICATED TO BE EXPOSED TO VIEW IN OCCUPIED
SPACES, PROVIDE MATERIALS WHICH ARE FREE FROM VISUAL IMPERFECTIONS INCLUDING PITTING, SEAM MARKS,
ROLLER MARKS, OIL CANNING, STAINS AND DISCOLORATIONS, AND OTHER IMPERFECT —IONS, INCLUDING THOSE
WHICH WOULD IMPAIR PAINTING.
D. FLEXIBLE DUCT. FACTORY INSULATED FLEXIBLE DUCTWORK SHALL BE SIMILAR TO OWENS— CORNING MODEL #
INL -25 OR AS APPROVED EQUAL WITH RESILIENT CORE OF CONTINUOUS INNER AIR BARRIER AND JACKETED
WITH A REINFORCED VAPORT JACKET. FIRE HAZARD CLASSIFICATION SHALL HAVE A FLAME SPREAD OF 25,
SMOKE RATING OF 50, IN ACCORDANCE WITH ASTM, C518 -70, ASTM E -84, AND UL 723 STANDARDS. FLEXIBLE
DUCT SHALL BE INDEPENDENTLY SUPPORTED TO PREVENT SAGGING AND KINKING.
E. PROVIDE BALANCING DAMPERS AT EACH BRANCH TAKE —OFF FROM MAIN DUCTS AND OTHER LOCATIONS AS
REQUIRED TO PROPERLY BALANCE THE SYSTEM.
5. INSULATION
A. ALL INTERIOR SUPPLY AND RETURN AIR CONDITIONING DUCTWORK (INSIDE CEILING SPACE) SHALL BE
INTERNALLY INSULATED WITH 1 INCH MINIMUM THICKNESS OF 1" P.C.F. DENSITY FIBERGLASS INSULATION WITH
VAPOR SEAL FACING. ALL JOINTS SHALL BE COATED WITH ADHESIVE.
6. DRAWINGS
A. CONTRACTOR SHALL VERIFY ALL CEILING SPACE CONDITIONS AT SITE BEFORE FABRICATION AND INSTALLATION
OF DUCTWORK.
B. CONTRACTOR SHALL THOROUGHLY CHECK REFLECTED CEILING PLANS AND CEILING HEIGHTS TO COORDINATE
FINAL LOCATION OF AIR DEVICES AND DUCT RUNS.
C. CONTRACTOR SHALL INSTALL ALL DIFFUSERS AND DUCTWORK AS SHOWN ON A/C DRAWING. IF THERE ARE
SPACE CONDITION PROBLEMS DUE TO STRUCTURAL MEMBERS, THE ARCHITECT /ENGINEER SHALL BE NOTIFIED
IMMEDIATELY AFTER ARCHITECT /ENGINEER APPROVAL TO COMPLETE THE INSTALLATION.
D. THE DUCTWORK LAYOUT INDICATED IN THE DRAWINGS ARE DIAGRAMMATIC AND DOES NOT SHOW ALL OFFSETS,
DEVIATIONS OR TRANSFORMATIONS THAT FIELD CONDITIONS MAY REQUIRE TO AVOID INTERFERENCES WITH SOME
OBSTRUCTIONS.
E. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY CHANGES IN DUCTWORK TO AVOID INTERFERENCES WITH THE
WORK OF OTHER TRADES, STRUCTURAL ELEMENTS OR ANY OTHER EXISTING OBSTRUCTION WITHOUT ANY
ADDITIONAL CHARGE TO THE OWNER.
F. DUCTWORK SIZES SHOWN ARE INSIDE DIMENSIONS.
7. GRILLES, REGISTERS AND DIFFUSERS
A. ALL GRILLES, REGISTERS, DIFFUSERS SHALL BE OF ALUMINUM CONSTRUCTION AND SHALL BE FURNISHED AND
INSTALLED WITH ALL SPECIFIED ACCESSORIES AS SHOWN ON THE SCHEDULE, FINISHED COLOR BY ARCHITECT.
B. MANUFACTURERS: TITUS, AIR GUIDE, NAILOR.
8. FILTERS
A. THROWAWAY TYPE LOCATED IN AIR HANDLING UNIT OR AT RETURN AIR GRILLE UNLESS OTHERWISE NOTED.
FURNISH ONE (1) SPARE SET TO OWNER.
10. CONDENSATE DRAIN LINE
A. CONDENSATE DRAIN PIPING TO BE COPPER PIPING INSULATED WITH 1" ARMAFLEX. PROVIDE PLENUM RATED
ARMAFLEX IN PLENUMS AND MECHANICAL ROOM.
11. CONTROLS
A. PROVIDE A THERMOSTAT WITH SUB —BASE AND LOCKING THERMOSTAT COVER 5' -6" AFF. SUB —BASE SHALL
HAVE MANUAL CHANGEOVER FOR HEATING AND COOLING AND ON —AUTO —FAN SWITCH. THERMOSTAT SHALL BE
COMPATIBLE WITH UNIT MANUFACTURER.
13. TEST AND BALANCE
A. THE ENTIRE HVAC SYSTEM SHALL BE TESTED, ADJUSTED AND BALANCED TO DELIVER THE AIR QUANTITIES
SHOWN ON DRAWINGS. TEST AND BALANCE SHALL BE DONE BY AN INDEPENDENT THIRD PARTY CERTIFIED TEST
AND BALANCE COMPANY.
14. GUARANTEE
A. ALL MATERIALS, EQUIPMENT AND WORKMANSHIP SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM
THE DATE OF ACCEPTANCE OF THIS PROJECT.
B. ALL WORK FOUND TO BE DEFECTIVE SHALL BE REPAIRED OR REPLACED BY THE CONTRACTOR WITHOUT ANY
CHARGE TO THE OWNER.
PRO DE 36' SERVICE SUPPLY
CLEARANCE FOR ALL
ACCESS PANELS.
ELECTRIC
HEATING COIL
12 GA. CHANNEL
PRIMED & PAINTED
(TYPICAL 4 PLACES)
DOUBLE NUTS &
LOCK WASHERS
(TYPICAL 4 PLACES)
FOAM RUBBER ISOLATION BETWEEN
CHANNEL & UNIT OR AUXILARY
PAN (TYPICAL)
Y DEEP AUXILIARY DRAIN PAN EXTEND
3' BEYOND UNIT PROVIDE 3/4'
AUXILIARY FOR SWITCH DEVICE
CONNECTION AS PER FMC 307
PROVIDE CEILING ACCESS SAME
SIZE AS UNIT AS PER FMC
COORDINATE WITH STRUCTURAL ENGINEER
AND OR ARCHITECTON HOW TO FASTEN
TO TRUCTURE (TYPICAL).
-VIBRATION ISOLATORS (TYPICAL)
FAN SECTION ACCESS PANEL
FLEXIBLE CONNECTION (TYPICAL)
r-FILTER ACCESS i-0 /A
COIL SECTION
ACCESS PANEL
IS&R, CWS&R OR
RIGERANT LINES
HORIZONTAL AIR HANDLING UNIT DETAIL
N.T.S.
CONDENSING UNIT — ,
SECURE TO CHANNEL
FRAME WITH 1/4" S.S.
BOLTS, FLAT S.S.
WASHERS ON EACH SIDE
AND NUT W/PRESSURE /
WASHER.-
UNIT BOLTED TO
ALUMINUM SUPPORTS
THRU "ISOMODE"
ISOLATORS
3 "x3 "x1 /4" S.S.
PLATE WELDED TO
PIPE
ALUMINUM PIPE
SUPPORT r
CONCRETE SLAB OR
ROOF STRUCTURE
MVD
DUCTWORK HANGING DETAILS
NTS
3/16-BRAIDED STAINLESS
STEEL CABLE ACROSS UNIT
(2 REQUIRED) PROVIDE
URETHANE TUBING OVER
CABLE AT UNIT.
�— S.S. TURNBUCKLE
4 "x4 "x1 /4" ALL WELDED
ALUMINUM SUPPORT
(FACING DOWN)
3/16 "x 1 "0 EYE BOLT
3'0 ALUMINUM PIPE
SEE ARCH. DWGS. FOR
24' —► FLASHING DETAIL
180
FILL W /GROUT
a; 6 "X6 "Xl /4" GALV.
REFRIGERANT LINES. RACK ON STEEL PLATE FASTENED
GALV. UNISTRUT. (MULTIPLE TO STRUCTURE
UNITS USE.)
NOTES:
1. CU'S SHALL BE ANCHORED AND SUPPORTED AS SHOWN TO WITHSTAND LIVE AND
DEAD LOADS AS PER FMC 301.13 AND FBC 1619.2. WIND LOADS OF 175MPH
SHALL APPLY.
2. PRE—MANUFACTURED CU STANDS DADE COUNTY PRODUCT APPROVED.
MANUFACTURER: F &L AL Parts, NOA #11- 0824.01. REFER TO MANUFACTURER APPROVED
SHOP DWG'S FOR DETAILS.
PRE - MANUFACTURED ROOF MOUNTED
CONDENSING UNIT SUPPORT DETAIL NOA #11- 0824.01
4�onssn(f�s�
0
!s en`
CAJ 5121
F— RATING = 2 HR.
1 PRE —RATED CONCRETE FLOOR OR WALL ASSEMBLY = MIN. 4-1/2" THICKNESS
A. METALLIC PIPE: COPPER TUBING— NOM. 4" DIAM. (OR SMALLER) TYPE L (OR
HEAVIER) COPPER TUBING.
B. COPPER PIPE — NOM. 4" DIAM. (OR SMALLER) REGULAR (OR HEAVIER) COPPER
PIPE.
C. STEEL PIPE— NOM. 4" DIAM. (OR SMALLER) SCH. 10 (OR HEAVIER) STEEL PIPE.
D. IRON PIPE — NOM. 4" DIAM. (OR SMALLER) CAST IRON PIPE.
PIPE COVERING — FIBERGLASS INSULATION, SEE TABLE BELOW FOR THICKNESS AND
ANNULAR SPACE.
MAX. PIPE PIPE COVERING ANNULAR PACKING MATERIAL MIN.
SEALANT F— RATING T— RATING IN. DIAM., THICKNESS, IN. SPACE IN.
THICKNESS, IN. THICKNESS, IN. HR. HR.
4 1 1/2 TO 1 0 1 2
1/2
4 2 1/2 TO 1 -1/2 3 -1/2 1 2 1
PACKING MATERIAL : MINERAL WOOL INSULATION (MIN. 4.0 PCF) FIRMLY
PACKED INTO OPENING TO THE MINIMUM REQUIRED THICKNESS IN
THE TABLE ABOVE.
TREMSTOP IA: MIN. THICKNESS OF SEALANT AS SPECIFIED IN TABLE ABOVE,
APPLIED WITHIN OPENING FLUSH WITH TOP SURFACE OF FLOOR OR BOTH
2SLIH09R gIRELLRATLOWC91IRI @1319IIQ•P@1LfPRATION FIRESTOP FOR
SINGLE INSULATED METAL PIPE THROUGH CONCRETE FLOORS
AND WALLS.
3/8 "X3 ESPANSION INSERT (TYP.)
-SHEET METAL OR FIBERGLASS
DUCTWORK
EXTERNAL OR INTERNAL INSULATION
'318' ALLTHREAD ROD (TYP.)
ClX2Xl x1/8' SUPPORT CHANNEL (TYP,)
REFER TO HANGING DETAIL FOR
STRAP AND HUNGER SIZES
PROVIDE SUPPORTING FOOT
IF "L" EXCEEDS 12" OR
BOTTOM OF MAIN AND
BRANCH DUCTS ARE NOT
ON THE SAME PLANES
SCREW
AIR FLOW
TYPICAL BRANCH DUCT TAKEOFF DETAIL
N.T.S.
EXTRACTOR
HANGING ROD
SUPPORT FROM ANGING ROD
ROOF OR JOIST
STRUCTURE ADJUSTABLE
GALVANIZED STEEL CLEVIS PIPE
ROD HANGER
TYPICAL PIPE HANGER DETAIL
N.T.S.
CONCRETE SLAB,
ROQF STRUCTURg, ;
• , : , : , : OA CEILING J01t50. , : �► e
—5' MAX--
2"
EXPANSION NAIL
itAAX AG: 24 GA. HANGER STRAP
1/2" PER FT FLEXIBLE DUCT
OF SUPPORT
1 -1/2" BAND
CLAMP
NOTE: SUPPORT SYSTEM SHALL NOT DAMAGE DUCT
OR CAUSE OUT OF ROUND SHAPE
FLEXIBLE DUCT SUPPORT DETAIL
N.T.S
HANGER STRAP
\—CHANNEL
T S ADDLE HARGINGHANGING
DETAIL
1�1 .l
HANGER STRAP
TRANSVERSE
REINFORCEMENT
TYPICAL CHANNEL
AND STRAP DUCT
HANGING DETAIL
a
RAFAEL 0. -eALLES7EROS, AR"9!TECT
7431 SW 88 PLACE
MIAMI, FLORDIA 33173
TEL. (305) 275 -0016
FAX (305) 275 -0018
IANNEL CELL (305) 790 -1996
FLORIDA REGISTRATION # AR0016490
NOTE:
SHEET METAL OR FIBROUS GLASS DUCTS SHOULD BE SUPPORTED BY TRAPEZE TYPE HANGERS ON MAXIMUM CENTERS
OF 8' -0" WITH A MINIMUM OF 1 "x2 "x1" CHANNELS, 18 GAUGE OR HEAVIER. THEY SHOULD BE SUPPORTED BY 1/4"
DIAMETER RODS OR 1 "x18 GAUGE OR HEAVIER STRAPS ATTACHED TO ROOF OR JOIST STRUCTURE. WHEN TRANSVERSE
REINFORCING MEMBERS OCCUR WITHIN THE MAXIMUM HANGER SPACING 1 "x22 GAUGE OR HEAVIER SHEET METAL STRAPS
MAY BE BOLTED TO THE STEMS OF THESE MEMBERS TO SUPPORT THE FIBROUS GLASS DUCT.
FLEX —DUCT SHALL BE EXTENDED AND SUPPORTED AT INTERVALS NOT GREATER THAN 5'. HANGERS, SADDLES AND
ANY SUPPORT MATERIAL SHALL BE MINIMUM 1 -1/2" WIDTH AS PER FMC 603.5.6.6
DUCT HANGING DETAILS
NOT TO SCALE
MAIN DUCT
INSULATION
SPIN —IN
45' TAP —IN
SCOOP ! • ll
AIR FLOW
DO NOT KINK r
FLEX. DUCT (SEE
PLANS FOR SIZE)
LDAMPER BLADE INSULATED
W/LOCK HANDLE 0 FLEX DUCT CEILING DIFFUSER
MAIN DUCT ELEVATED DIAL F (SEE CEILING
INSULATION DIFFUSER DETAIL)
ROUND DUCT CONNECTION DETAIL
N.T.S.
BOLTS ATTACHED TO EXISTING METAL JOIST.
REFER TO HANGING DETAIL FOR STRAP AND
HUNGER SIZES
6 7 0 O.[ 0711 1� LA N T 12
DOUBLE PORT
SIGHT GLASS
THERMAL EXP.
VALVE W/
EXTERNAL
EQUALIZER
DUCT HANGING DETAIL
N.T.S.
4
FLEX CONN
SUCTION LINE
AIR COOLED LIQUID LINE
COND. UNIT / / PITCH
CHARGING
VALVE
DX C01 �
AIR HANDLING UNIT PI�
ANGLE VALVE
REFRIGERANT PIPING DIAGRAM
N.T.S.