Loading...
13-1079-009ABBREVIATIONS A, AMPS AMPERES AC,A /C ALTERNATING CURRENT, AIR CONDITIONING AFF. ABOVE FINISH FLOOR AFCI ARC FAULT CIRCUIT INTERRUPTER AHU AIR HANDLING UNIT AIC AMPERES INTERRUPTING CURRENT ANSI AMERICAN NATIONAL STANDARDS INSTITUTE ARCH ARCHITECT OR ARCHITECTURAL ATS AUTOMATIC TRANSFER SWITCH BFC BELOW FINISHED CEILING BLDG. BUILDING C CONDUIT CLG. CEILING CU COPPER, CONDENSING UNIT E EXISTING ELECTRICAL EQUIPMENT /DEVICE EF EXHAUST FAN ER EXISTING ELECTRICAL EQUIPMENT /DEVICE TO BE REMOVED. ERL EXISTING ELECTRICAL EQUIPMENT /DEVICE TO BE RELOCATED EWH ELECTRICAL WATER HEATER FBC FLORIDA BUILDING CODE FLA FULL LOAD AMPS, FLORIDA FT FEET G GROUND GFI GROUND FAULT INTERRUPT HP HORSEPOWER HZ. HERTZ (CYCLES) I.G. ISOLATED GROUND INC. INCANDESCENT KW KILOWATTS KWH KILOWATT HOUR LRA LOCKED ROTOR AMPS M MOTOR MCA MINIMUN CIRCUIT AMAPACITY MCB MAIN CIRCUIT BREAKER MLO MAIN LOAD ONLY MOCP MAXIMUN OVER CURRENT PROTECTION N NEW ELECTRICAL EQUIPMENT /DEVICE EQUIPMENT SHOWN WITHOUT ABBREVIATION IS TO BE CONIDERED AS NEW. NEC NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOC. NFPA NATIONAL FIRE PROTECTION ASSOCIATION NIC NOT IN CONTRACT NCL NON COINCIDENT LOAD NL NIGHT LIGHT NOM. NOMINAL N.T.S. NOT TO SCALE OSHA OCCUPATIONAL SAFETY & HEALTH ACT P POLE P.E. PROFESSIONAL ENGINEER PH. PHASE. P.O.S. POINT OF SALE PVC POLYVINYL CHLORINE R RELOCATED EXISTING EQUIPMENT DEVICE RECEP., REC. RECEPTACLE RLA RUNNING LOAD AMPACITY S/N SOLID NEUTRAL SWGR SWITCHGEAR XTR ELECTRICAL TRANSFORMER TYP. TYPICAL U.L. UNDERWRITERS LABORATORIES V VOLT VA VOLT AMPERES VP VAPOR PROOF W. WIRE, WATT, WIDE WP WATER PROOF ELECTRICAL NOTES 1- ALL WORK SHALL BE PERFORMED TO MEET THE REQUIREMENTS OF THE GOVERNING EDITION OF THE NATIONAL ELECTRICAL CODE (N.E.C. 2008), F.B.0 2010, LOCAL AND STATE CODES AND ANY OTHER APPLICABLE CODES AND STANDARS. 2- ALL WIRING SHALL BE COPPER (CU) THWN INSULATION. IF ALUMINUM WIRES ARE USED: A) TO PREVENT OVERHEATING AT CONNECTION POINTS USE OXIDE INHIBITING COMPOUND FOR STRIPPED PORTION OF CONDUCTORS INSIDE CONNECTORS. B) A PREVENTIVE MAINTENANCE PLAN IS NECESSARY TO ENSURE A RELIABLE SERVICE INCLUDING VISUAL INSPECTIONS AND TESTS FOR SPLICES AND CONNECTION POINTS (CORROSION AND TIGHTNESS PRINCIPALLY) INSPECTION INTERVALS OF 2 YEARS MAXIMUM ARE STRONGLY RECOMMENDED. 3- ALL CIRCUIT BREAKERS SHALL BE RATED AT MINIMUM OF 10,000 AIC. 4- PRIOR TO INSTALLATION OF ROUGH ELECTRICAL WIRING, CHECK NAMEPLATE DATA OF ALL EQUIPMENT FOR REQUIRED VOLTAGES, MINIMUM CIRCUIT AMPACITY, AND OVERCURRENT PROTECTION. 5- ELECTRICAL PLANS AND CALCULATIONS WERE BASED ON INFORMATION PROVIDED BY OWNER AGENT. ELECTRICAL CONTRACTOR TO FIELD VERIFY EXISTING CONDITIONS AND ADJUST ACCORDINGLY, CHANGES TO BE REFLECTED IN THE DRAWINGS. 6- THE ELECTRICAL DESIGN IS BASED UPON THE AVAILABLE INFORMATION AT DESIGN TIME AND THE CONTRACTOR SHALL REVIEW NAMEPLATE DATA AND MANUFACTURER SUPPLIED LITERATURE FOR ALL PIECES OF EQUIPMENT PRIOR TO ROUGH ELECTRICAL WIRING. THE CONTRACTOR SHALL CHECK ALL EQUIPMENT FOR PROPER VOLTAGE, PHASE AND AMP RATING PRIOR TO INSTALLATION. THE CONTRACTOR SHALL CONTACT ENGINEER PRIOR TO ANY FIELD ADJUSTMENT. 7- ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED. 8- ALL NEW CONDUCTORS SHALL BE RUN IN CONDUIT (METALLIC TYPE) UNLESS OTHER TYPES CAN BE USED AS PER NEC: A)- PVC SCH. 40 WHEN INSTALLED 12" UNDER SLABS ON GRADE OR WHEN EMBEDDED IN CONCRETE WALLS OR SLABS. B)- MC CABLE CAN BE INSTALLED ACCORDING TO NEC 330.10 AND 330.12. C)- IMC WHEN INSTALLED CONCELED IN MANSONRY WALLS, DRY WALLS OR SUSPENDED CEILINGS, ALSO WHEN INSTALLED IN INTERIORS EXPOSED UP TO 8' AFF. D)- EMT INTERORS EXPOSED ABOVE 8' AFF AND AT ANY HEIGHT IN ELECTRICAL, MECHANICAL AND TELECOMMUNICATION ROOMS 9- IF PVC CONDUITS ARE USED FOR UNDERGROUND FEEDERS, AN EQUIPMENT GROUND CONDUCTOR SIZED IN ACCORDANCE WITH N.E.C. 250 - 122 MUST BE INSTALLED AND CONDUIT SIZE INCREASED AS REQUIRED. 10- TYPEWRITTEN PANEL TALLY SHALL BE FURNISHED AFTER JOB IS COMPLETED REFLECTING ALL CHANGES AND ADDITIONS. 11- ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH THE MANUFACTURER CEILING, WALL OR POLE INSTALLATION SYSTEM. 12- RISERS ARE DIAGRAMMATIC ONLY. THEY DO NOT SHOW EVERY BEND REQUIRED FOR THE INSTALLATION. ELECTRICAL CONTRACTOR TO FIND BEST POSSIBLE ROUTE FOR ALL CIRCUITS. 13- THIS DRAWING IS A GUIDE FOR THE INSTALLATION OF ELECTRICAL SERVICE. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM. 14- CONTRACTOR TO VERIFY ADJUSTMENT FACTORS FOR MORE THAN THREE CURRENT - CARRYING CONDUCTORS IN A CONDUIT ACORDING TO TABLE 310- 15(b)(2)(a) NEC. 15- ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ARCHITECT /OWNER TO FIELD VERIFY INSTALLATION FOR OUTLETS, LIGHTING FIXTURES AND ELECTRICAL EQUIPMENT. 16- CONTRACTOR TO PROVIDE SIGNS ON ELECTRICAL PANELS AND DISCONNECTS: "ELECTRICAL EQUIPMENT WITH POTENTIAL ELECTRIC ARC FLASH HAZARDS ". 17 - OUTLETS IN OPPOSITE SIDES ON FIRE RATED WALLS TO BE 24" HORZ. APART (MIN). AND FIRE PROTECTED. 18 - ALL SMOKE OR CARBON MONOXIDE DETECTORS TO BE LOCATED 3' APART MIN. FROM A/C OUTLETS AND INTERCONNECTED FOR SIGNALING PURPOSE. CARBON MONOXIDE DETECTORS TO BE LOCATED 10' MAXIMUM FROM ANY SLEEPI?4,' AREA. ELECTRICAL LEGEND SWITCH ( +48" CL, AFF UNLESS OTHERWISE NOTED.) BLANK = SINGLE POLE 2 = DOUBLE POLE 3 = THREE -WAY 4 = FOUR -WAY X = EXPLOSION PROOF Mo= OCCUPANCY SENSOR DUPLEX RECEPTACLE, WALL. ( +18" CL, AFF UNLESS OTHERWISE NOTED.) "GFI" GROUND FAULT TYPE, "WP" WEATHER PROOF. DUPLEX RECEPTACLE, WALL. BOTTOM HALF SWITCHED. ( +18" CL, AFF UNLESS OTHERWISE NOTED.) DUPLEX RECEPTACLE. ( +48" CL, AFF UNLESS OTHERWISE NOTED.) TWO DUPLEX RECEPTACLES IN TWO GANG OUTLET BOX "D" DESIGNATION MEANSDEDICATED. ( +18" CL, AFF UNLESS OTHERWISE NOTED.) ® DUPLEX RECEPTACLE. FLOOR MOUNTED. �- SINGLE RECEPTACLE, WALL MOUNTED. ( +18" CL, AFF UNLESS OTHERWISE NOTED.) SPECIAL PURPOSE RECEPTACLE. NEMA CONFIGURATION AS NOTED. WALL MOUNTED. !� TELEPHONE OUTLET, WALL MOUNTED. Q DATA OUTLET, WALL MOUNTED. d COMB. DATA OUTLET- TELEPHONE OUTLET, WALL MOUNTED. B TV OUTLET, WALL MOUNTED. Q JUNCTION BOX. CEILING MOUNTED FLUORESCENT LIGHTING FIXTURE. O CEILING MOUNTED (RECESSED) INCANDESCENT, CIRCLE OR HID LIGHTING FIXTURE. -�- CEILING MOUNTED (SURFACE OR PENDANT) INCANDESCENT, CIRCLE OR HID LIGHTING FIXTURE. a-I WALL MOUNTED INCANDESCENT, CIRCLE OR HID LIGHTING FIXTURE. FAN MOTOR MOTOR CONNECTION. �a DISCONNECT SWITCH. "a "= PHASE, "b "= AMP FRAME, "c "= AMP. FUSE "F "= FUSIBLE. C =0 NOT FUSED J- GROUND CONNECTION. BRANCH CKT HOME RIJN. DENOTE NUM. OF UNGROUNDED SERVICE WIRE DENOTE NEUTRAL WIRE DENOTE GROUND WIRE l� ELECTRICAL METER 0 ELECTRICAL PANEL CEILING MOUNTED EXIT LIGHT SIGN. (PROVIDE ARROWS AS INDICATED ON DRAWINGS.) WALL MOUNTED EXIT LIGHT SIGN. (PROVIDE ARROWS AS INDICATED ON DRAWINGS.) SELF - CONTAINED EMERGENCY LIGHTING UNIT, WALL. 4iltJ� COMBO EXIT LIGHT SIGN AND SELF CONTAINED EMERGENCY LIGHTING UNIT. GENERAL NOTES, ABBREVIATION, SYMBOLS AND LEGEND - ELECTRICAL EXISTING ELECTRICAL PANEL SCHEDULE "A" TYPE EXISTING MAINS M.L.O. MOUNTING FLUSH BUS RATING 200 AMP LOCATION OFFICE VOLTAGE 120 /208V- 3PHASE -4WIRE ENCLOSURE NEMA 1 FEED FROM CBKR 150 AMPS DESCRIPTION WIRE & COND. SIZE LOAD (V.A.) POL TRIP CKT No. A B C CKT No. POL TRIP LOAD (V.A.) WIRE & COND. SIZE DESCRIPTION EXIST. PNL "B" EXISTING 18,200 /125[ 1 2 2,--2'0 1,200 #12 -1/2" LIGHTS 3 4 j,--2'0 1,200 #12 -1/2" LIGHTS 2 40 5,000 #8 -1/2" EXISTING AC 5 6 j,,--2-0- 1,200 #12 -1/2" LIGHTS 800 1 20 5 6 7 8 2,,-2'0 600 #12 -1/2" RECEPTACLE 800 7 8 9 10 1 20 1,200 #12 -1/2" RECEPTACLE SMALL APP. #12 -1/2" 11 12 1 20 1,000 #12 -1/2" RECEPTACLE COPY MACHINE #12-1/2" SPARE 1 20 800 1 20 13 14 1 20 1,000 #12 -1/2" RECEPTACLE SPACE SPARE 800 1 20 15 16 2 40 5,000 SPARE SPACE SPARE 800 1 20 17 18 SPARE SPACE SPACE 19 20 17 18 SPARE SPACE SPACE SPACE 21 22 19 20 SPACE SPACE SPACE SPACE 23 24 21 22 SPACE SPACE SPACE SPACE 25 26 23 24 SPACE SPACE SPACE SPACE 27 28 25 26 SPACE SPACE SPACE SPACE 29 30 27 28 SPACE SPACE SPACE SPACE 31 32 29 30 SPACE SPACE SPACE SPACE 33 34 31 32 SPACE SPACE SPACE SPACE 35 36 33 34 SPACE SPACE SPACE SPACE 37 38 35 36 SPACE SPACE SPACE SPACE 39 40 37 38 SPACE SPACE 41 42 39 SPACE SPACE SPACE 41 42 LOAD CALCULATION PANEL TOTAL CONNECTED LOAD = 33,000 VA CONTINUOUS LOAD AT 125% = 3,600 VA X 1.25 = 4,500 VA NON CONTINUOUS LOAD AT 100% = 29,400 VA TOTAL DEMANDED LOAD = 33,900 VA TOTAL DEMAND AMPS = 95 AMPS PER PHASE EXISTING ELECTRICAL PANEL SCHEDULE "B* TYPE EXISTING MAINS M.L.O. MOUNTING FLUSH BUS RATING 200 AMP LOCATION : OFFICE VOLTAGE 120 /208V- 3PHASE -4WIRE ENCLOSURE NEMA 1 FEED FROM PANEL "A" THRU 125A CBKR DESCRIPTION WIRE & COND. SIZE LOAD (V.A.) POL XTRIp CKT. No. A B C CKT. No. POL TRIP LOAD (V.A.) WIRE & COND. SIZE DESCRIPTION RECEPTACLE #12 -1/2" 800 1 20 1 2 SPACE RECEPTACLE #12 -1/2" 800 1 20 3 4 2 40 5,000 #8 -1/2" EXISTING AC RECEPTACLE #12 -1/2" 800 1 20 5 6 RECEPTACLE #12 -1/2" 800 7 8 2 30 4,000 #10 -1/2" EXISTING AC SMALL APP. #12 -1/2" __!,,-2-0- 1,500 1 20 9 10 COPY MACHINE #12-1/2" 1,500 1 20 11 12 1 20 1,000 SPARE SPACE 13 14 1 20 1,000 SPARE SPACE 15 16 1 20 1,000 SPARE SPACE 17 18 SPACE SPACE 19 20 SPACE SPACE 21 22 SPACE SPACE 23 24 SPACE SPACE 25 26 SPACE SPACE 27 28 SPACE SPACE 29 30 SPACE SPACE 31 32 SPACE SPACE 33 34 SPACE SPACE 35 36 SPACE SPACE 37 38 SPACE SPACE 39 40 SPACE SPACE 41 42 SPACE LOAD CALCULATION PANEL TOTAL CONNECTED LOAD = 18,200 VA CONTINUOUS LOAD AT 125% = 0 NON CONTINUOUS LOAD AT 100% = 18,200 VA TOTAL DEMANDED LOAD = 18,200 VA TOTAL DEMAND AMPS = 51 AMPS PER PHASE NOTE 1: ELECTRICAL CONTRACTOR TO FIELD VERIFY BRANCH CIRCUIT, POSITION AND CONNECTION. ALL PANELS SHALL HAVE UPDATED BRANCH CIRCUITS LABELS. NOTE 2: ALL CIRCUITS AND CIRCUIT MODIFICATIONS SHALL BE LEGIBLY IDENTIFIED AS TO PURPOSE OR USE ON A CIRCUIT DIRECTORY LOCATED ON THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A PANEL BOARD, AND AT EACH SWITCH ON A SWITCHBOARD. �2 ELECTRICAL PANEL SCHEDULES E -1 ELECTRICAL DEMOLITION NOTES 1. WHERE ELECTRIC LIGHTING FIXTURES, SWITCHES, RECEPTACLES, BOXES, CABINETS, DEVICES, ETC. ARE TO BE REMOVED, AND BOXES AND CONDUITS ARE TO REMAIN, ALL CONDUCTORS SHALL BE DE- ENERGIZED, DISCONNECTED AT BOTH ENDS, REVERSED INTO THE BOX, AND THE BOX PLUGGED WITH CEMENT PLASTER OR OTHER APPROVED MATERIAL AND THE WALL, FLOOR, CEILING AND THE LIKE, RESTORED TO MATCH THE SURROUNDING FINISH TO THE SATISFACTION OF THE OWNER. 2. WHERE ELECTRICAL FIXTURES, SWITCHES, OUTLETS, RECEPTACLES, BOXES, CABINETS, DEVICES, ETC. ARE TO BE REMOVED, AND THEIR REMOVAL AFFECTS THE OPERATION OF THE EQUIPMENT, FIXTURE, RECEPTACLES, ETC., THAT IS TO REMAIN (INCLUDING ITEMS THAT MAY NOT BE SHOWN IN THE DRAWINGS BUT ARE PRESENTLY EXISTING IN PLACE) THE CONTRACTOR SHALL RE- CIRCUIT THEM (INCLUDING BOXES, CONDUIT, WIRES, ETC.) TO RESTORE THEM TO THE ORIGINAL OPERATING CONDITION, ALL AT NO ADDITIONAL COST TO THE OWNER. 3. UNUSED OPENINGS IN BOXES, CABINETS, PANELBOARDS, ETC., WHERE CONDUIT IS REMOVED OR PREVIOUSLY EXISTED, SHALL BE PLUGGED OR BLANKED OUT BY APPROVED METHODS, IF THE OPENING IS TO REMAIN. 4. ALL EXPOSED CONDUIT, WIRES, OUTLETS, ETC. NOT TO BE REUSED IN THE NEW REMODELED LAYOUT, SHALL BE REMOVED. 5. EXISTING CONDUIT RUNS, STUBBING UP THRU FLOORS IN AREAS WHERE WALLS ARE TO BE REMOVED, SHALL HAVE THEIR CONDUCTORS DE- ENERGIZED AND REMOVED, CONDUIT CUT -OFF GROUND FLUSH WITH FLOOR AND PLUGGED WITH CEMENT MORTAR OR ANY OTHER APPROVED MATERIAL. THE SAME APPLIES WITH EXISTING CONDUITS THAT ARE STUBBING OUT OF WALLS AND FLOORS. 6. WHERE PRACTICAL, EXISTING CONDUCTORS AND WIRES THAT ARE IN GOOD CONDITION, MAY BE REUSED IN PLACE AND INCORPORATED IN THE NEW REMODELED LAYOUT PROVIDED, IT IS OF PROPER SIZE, TYPE OF CONDUCTOR AND WITH THE APPROVAL OF THE OWNER. 7. ABANDONED CIRCUIT CONDUCTORS IN PANELBOARDS, SHALL BE DISCONNECTED, TAPED AND IDENTIFIED. SALVAGED ITEMS SHALL BE RETURNED TO THE OWNER, AND DELIVERED WHERE DIRECTED BY HIM. ITEMS AND MATERIALS CONSIDERED UNSALVAGEABLE BY THE OWNER, SHALL BE DISPOSED OF AS DIRECTED BY THE OWNER. REMOVED WALL SWITCHES, RECEPTACLES AND LIGHTING FIXTURES SHALL NOT BE REUSED IN NEW CONSTRUCTION. 8. CONTRACTOR SHALL VISIT THE SITE, PRIOR BIDDING THIS WORK, TO FAMILIARIZE HIMSELF WITH THE STATUS OF THE SPACE, AND INCLUDE IN HIS BID, ALL THE REQUIRED DEMOLITION OR MODIFICATIONS (INCLUDING FIXTURES, OUTLETS, BOXES, PANELBOARDS, BREAKERS, TRANSFORMERS, ETC.) IN ORDER TO HAVE A COMPLETE FINISHED INSTALLATION. NO EXTRA CHARGES WILL BE ALLOWED BECAUSE OF FAILURE TO COMPLY WITH THESE REQUIREMENTS. 9. CONTRACTORS WORK SHALL BE FULLY COORDINATED WITH BUILDING SYSTEMS, AND ANY MODIFICATIONS, OR ADDITIONS THAT WILL ALTER THE BUILDING SYSTEM, SHALL BE MADE IN FULL COMPATIBILITY WITH THE SYSTEM. WORK ON THE SYSTEM SHALL BE COORDINATED WITH THE BUILDING MANAGER, AND WORK DONE IN NON- WORKING HOURS, IF REQUESTED, AT NO EXTRA COST TO THE OWNER. OFFICE EXISTING PN L "A" M.L.O. 5TH LEVEL EXISTING. PN L "B" M.L.O. EXISTING MAIN ELECTRICAL ROOM EXISTING O CBKR 150A EXISTING 2P HMETER _rL 1ST LEVEL EXISTING ELECTRICAL RISER DIAGRAM E -1 .REVISIONS 01 1F