09-860-019GENERAL NOTE5 - ELECTRICAL . I.-DO NOT SCALE ELECTRICAL DRAWINGS, REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT AND CONFIRM WITH OWNERS' REPRESENTATIVE. 2- ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION OF THE NEC THE NFPA 10 4 SHALL COMPLY WITH THE CURRENT FLORIDA BUILDING CODE, AND ALL STATE AND LOCAL RULES AND ORDINANCES. 3: MINIMUM WIRE SIZE SHALL BE NO, 14 AWG, EXCLUDING CONTROL WIRING, UNLESS OTHERWISE INDICATED, ALSO, UNLESS OTHERWISE INDICATED, ALL CONDUCTORS SHALL BE COPPER WITH THW OR THH AUM INSULATION FOR SIXES NO.6 AND SMALLER CONDUCTORS LARGER THAN NO.6 SHALL HAVE TYPE T14W NO.8 AND LARGER SHALL BE STRANDED. ALL RACEWAYS AND PIPES PLACED IN OR THROUGH ANY CONCRETE SLAB SHALL BE SPACED A MINIMUM OF 3 DIAMETERS OF THE LARGEST CONDUIT OR PIPE OF ANY OTHER SERVICE :(WHEN APPLICABLE) 4.- ALL RACEWAYS UNDERGROUND AND /OR LARGER THAN 2 INCHES IN DIAMETER SHALL BE GALVANIZED RIGID STEEL. PVC PIPE SCH. 40 WILL BE ACCEPTABLE IF APPROVED BY LOCAL REGULATIONS, CONTRACTOR TO VERIFY. ALL OTHER RACEWAYS 2 INCHES AND SMALLER IN DIAMETER MAY BE EXT. WHEN ABOVE GROUND 5.- OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, AND CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCATIONS (4" x 4" MINIMUM $IZE). 6.- DISCONNECT SWITCHES SHALL BE HORSEPOWER RATED, HEAVY DUTY, QUICK -MAKE, QUICK- BREAK, N NEMA } OR 3R ENCLOSURE AS REQUIRED BY EXPOSURE. 1: IT IS NOT THE INTENT OF THESE PLANS TO SHOO) EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM, AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED N PROPER WORKING ORDER 8. MOTOR STARTERS SHALL BE MANUAL OR MAGNETIC WITH THREE OVERLOAD RELAYS. 9.- THE ELECTRICAL SYSTEM SHALL BE FULLY OPERATIONAL AND TESTED, AS WELL AS COMPLETELY GROUNDED AS REQUIRED BY THE N.E.C. 10- LOAD DATA IS BASED ON INFORMATION GIVEN TO THE ENGINEER AT THE TIME OF DESIGN. VERIFY ALL EQUIPMENT CONDUCTOR SIZE, PROTECTION, ETC. REQUIREMENTS PRIOR TO ORDERING PANEL BOARDS, OR PRIOR TO INSTALLATION. II: ALL MATERIALS, DEVICES OR APPLIANCES SHALL BE LISTED AND BEAR WITH THE STANDARDS OF UNDERWRITERS LABORATORIES (UL) OR ANY APPROVED NATIONALLY RECOGNIZED LABORATORY 12: ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS WORCMANLIKE MANNER THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTANCE BY ENGNEERIARC 41TECT MUST BE A CONDITION OF THE CONTRACT. 13.- ALL WOW SHALL BE C 0RDINIATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH PROGRESS OF CONSTRICTION. 14.- CONTRACTOR SHALL GUARANTEE ALL MATERIALS, EQUIPMENT AND WORKMANSHIP ARE FREE OF DEFECT FOR A PERIOD OF NO LESS THAN ONE YEAR FROM THE DATE OF ACCEPTANCE, ELECTRICAL LEGEND SURFACE MOUNTED INCANDESCENT OR FLUORESCENT LIGHT FIXTURE I2OV, IOOW MAX. 0 RECESSED INCANDESCENT LIGHT FIXTURE 120V, }OOW MAX. • RECESSED INCANDESCENT LIGHT FIXTURE 120V, 5OW MAX. WALL MOUNTED INCANDESCENT FIXTURE OUTLET. MOUNTING HEIGHT TO BE VERIFIED WITH ARCHITECT AND /OR OWNER. DUPLEX RECEPTACLE 3 POLE, 3 WIRE, 125V, 20A, MOUNTED AT IS" APP. DUPLEX RECEPTACLE 3 POLE, 3 Win, 125Y, 20A, WITH ARC -FAULT INTERRUPTER PROTECTION MOUNTED AT IS" APP. SINGLE POLE TOGGLE SWITCH 20A, 120V MOUNTED 48" AFF. 3 -WAY TOGGLE SWITCH 20A, 120V MOUNTED 48" APP. D DIMMER SWITCH LUTRON NOVA SERIES 120V,150OW OR EQUIVALENT, MOUNTED AT 48" APP. T TELEPHONE OUTLET, WALL MOUNTED AT 18" APP. CEILING OR WALL MOUNTED JUNCTION BOX WITH COVER, TO SUIT LOCATION. n TV /CABLE OUTLET, WALL MOUNTED AT 18" APP. T® EF EXHAUST FAN MOTOR CONNECTION (FRACTIONAL HORSEPOWER) DISCONNECT SWITCH TYPE AND SIZE AS SHOILN sD SMOKE DETECTOR 120V TYPE WITH BATTERY BACKUP (SEE PLAN NOTES) - - -- CONDUIT MINI CONCEALED N CEILING OR WALLS. CONDUIT RUN UNDERGROUND, N OR BELOW FLOOR SLAB. IQI ELECTRICAL PANEL SIZE AND RATING AS SHOWN (SEE SCHEDULES) GF.I. INDICATES GROUND FAULT INTERRUPTER. W.P. INDICATES WEATHERPROOF, NEMA 3R ENCLOSURE. E INDICATES EXISTING EQUIPMENT TO REMAIN. ER INDICATES EXISTING EQUIPMENT RELOCATED AS SHOW F INDICATES FUTURE: ELECTRICAL EQUIPMENT NOT INSTALLED UNDER THIS CONTRACT. 15.- CONTRACTOR SHALL REMOVE ALL DEBRIS AND UNUSED FIXTURES AND RETURN TO OWNER OR DISPOSE OF PROPERLY IF $O DIRECTED BY OWNER I&.- CONTRACTOR SHALL INCLUDE IN HIS PRICE, PERMIT, TAXES AND /OR IMPACT FEES, INSURANCE, ETC. AND ENGINEERING FEES FOR PREPARATICN OF AS -BUILT DRAWINGS. Il: IT IS SUGGESTED THAT THE CONTRACTOR CONFER WITH LOCAL UTILITY TO LOCATE THE ELECTRIC METER TO COMPLY WITH FEMA REQUIREMENTS 18.- ALL CONTROL WIRES AND CONNECTIONS REQUIRED FOR ALL ELECTRICAL APPLIANCES, AIR CONDITIONING AND VENTILATING EQUIPMENT OPERATION SHALL BE PROVIDED AND TESTED FOR A FULLY OPERATIONAL SYSTEM. }9.- MAINTAIN 12" MINIMUM SEPARATION BETWEEN OUTLET BOXES ON OPPOSITE SIDES OF SOUND INSULATED WALLS 20: CLAIMS FOR EXTRA WORK DUE TO MEETING CODE REQUIREMENTS WILL NOT BE CONSIDERED. 2I. -ALL LIGHTING FIXTURES COLOR FINISH SHALL BE SELECTED BY ARCHITECT OWNER REPRESENTATIVE BEFORE ORDERING. 22.- CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND VERIFY EXACT LOCATIONS PRIOR TO BIDDING THE PROJECT. 23.- VERIFY AT FIELD WITH ARCHITECT OWNER REPRESENTATIVE EXACT LOCATION OF SIGNAL OUTLETS, LIGHT FIXTURES CONTROL SWITCHES AND WALL FIXTURES MOUNTING HEIGHT BEFORE ROUGHING -IN. 24.- COORDINATE W/ OUTER TYPE OF DATA PROVIDER BEFORE INSTALLATION OF OUTLETS. 25 -ALL DUPLEX RECEPTACLES SHALL BE 125V- 15A -2P -3W GROUNDED, STANDARD GRADE, COLOR SELECTED AND APPROVED BY ARCHITECT. 26- ALL LIGHT SWITCHES SHALL BE 1 POLE TOGGLE 125V RATED 20A, COLOR SELECTED AND APPROVED BY ARCHITECT. 21 -ALL RECEPTACLES SHALL BE WIRED N ACCORDANCE WITH N.E.C. TO ENDURE CORRECT POLARITY. 28.- CIRCUIT NUMBERS SHOWN ARE FOR IDENTIFICATION ONLY. IT SHALL BE THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO COMPLETE PHASE PANEL BOARD (BALANCE LOAD). 29. -ALL JUNCTION AND PULL -BOXES SHALL BE ACCESSIBLE ALL THE TIME. 30. -ALL RACEWAY ROUTED, INSULATED CONDUCTORS SYSTEM SHALL BE COLOR CODED AS FOLLOWS: 120/240V SYSTEM PHASE "A ": BLACK PHASE "B ": RED NEUTRAL : WHITE GROUND : GREEN 3I. -ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL BE WEATHER - PROOF. LOAD SUMMARY PANEL 'A' AIR CONDITIONING LOAD AHU -1 ------------------ ------ ----- --- ------- - - - - - -- -},244 VA AHU -2 ----------------------------------------- - - - - -- 6,984VA OTHER LOADS (1) GENERAL LIGHTING 2,7190 Sl:.e 3W /SF - - - - - - - - - - 8,310 SMALL APPLIANCES 2 x 1500W -------- - - ---- 3,000 GAS COOKTOP/FAN UNIT -------------- - - - - -- 1,000 D5L -OVEN UNIT ------------------------------ 3,200 MICROWAVE -------------------------- - - - - -- 1,500 DISH WASHER ------- -- -------- ---- -- - - - - - -- 1,500 GARB DISP. ---------------------------- - 1,100 REF/ COOLER--------------------------- - - - - -- I,600 EWH---------- ----------- --- --- ----- - - - - - -- 4,500 WASHER ------------------------------- - - - - -- 1,300 DRYER ---------- --- -- --- ----- --- ---- --- - -- 5,000 OTHER LOADS TOTAL - 32,0'10 -- 32,010 VA 46,298VA 46,298 VA / 240V = 192.9 AMPS (ESTIMATED LOAD) EXISTING A 200 A SERVICE WITH 303/0 THW CU IN 2'G (FULL NEUTRAL) TO REMAIN. ------------------------------------------------------------ NOTES: (1) AIR CONDITIONING FLOOR AREA PER NEC 22030(5X2) EXISTING 2,480 60-FT PLUS NEW AREA ADDED 310 60-FT TOTAL OF 2,7190 80 -FT. LOAD SUMMARY PANEL 'B' AIR CONDITIONING LOAD AC -I ----------------------------------------- - - - - -- 6,120 VA AC -2 ----------------------------------------- - - - - -- 5,568 VA NEW AC -3 (DUCTLESS) -------- ------ ---------- - - - - - -- 1,440 VA OTHER LOADS POOL PUMP --------------------------- - - - - -- 2,300 POOL EQ. ---------------------------- - - - - -- 4,200 POOL LTS. ----------------------------- - - - - -- 500 OTHER LOADS TOTAL 1,000 VA -1000 VA 20,'128 VA 20,126 VA / 240V = 86.4 AMPS (ESTIMATED LOAD) EXISTING 100 A SERVICE WITH 303 THW CU IN 1 -1/4 "C (FULL NEUTRAL) TO REMAIN. FEEDER AND SERVICE LOAD CALCULATION PER N.E.C. ARTICLE 22030 (MAIN FEEDER) AIR CONDITIONING LOAD (PER N.E.G. OPTIONAL CALC. 22030(CX4)) AC UNIT 01 --------------------------------------- - - - - -- '11244 VA AC UNIT 02 --------------------------------------------- 6,984 VA AC UNIT 03 (NEW) --------------------------------- - - - - -- 1,440 VA OTHER LOADS PANEL 'A' ---------------------------- - - - - -- 32,010 PANEL'B' ---------------------------- - - - - -- 1000 SPRINKLER PUMP ----- ------ --- ------- - - - - -- 1,900 OTHER LOADS TOTAL 40,910 VA FIRST 10,000 VA AT 1009s 10000 VA ----------------- 10,000 VA NEXT 30,910 VA AT 40516 12,386 VA ----- ---- -- -- - -- - -- 12,385 VA 38,056 VA / 240V = 158.6 AMPS (ESTIMATED LOAD) 38,056 VA EXISTING A 200 A SERVICE WITH 303/0 THW CU IN 2'C (FULL NEUTRAL) TO REMAIN WITH NEW 104 THW CU SERVICE GROUND WIRE. PROVIDE NEW GROUND SERVICE (REFER TO RISER DIAGRAM) NOTES: (1) PER N.E.G. ART 310.15 (5X6) SINGLE -PHASE DWELLING SERVICES AND FEEDERS. 11, (1) (1) (2)(5 (2)l3 (2)l3 (1) ll) 11) FEED WITH: EXISTING 303/0 THW CU IN VC TO REMAIN. TYPE: SIEMENS LOAD CENTER MODIFICATION: -- VOLTAGE 120/24OV, IPH, 3W I I I ENCLOSURE: NEMA 1, RECESSED MAINS: 225 A MLA. ���� LOCATION: CORRIDOR AREA A.I.C.S.: 10,000 (EXISTING TO REMAIN) FED FROM: MAIN "A"-METER/F.P.L. Co. DESCRIPTION WIRE AND CONDSIZE LOAD (VA) POLE TRIP CT. No VOLTAGE 120/24OV, IPH, 3W WV PANEL CT. No POLE TRIP LOAD (VA) WIRE AND CONDSIZE DESCRIPTION GAS /STOVE -FAN UNIT EXIST 500 2 30 1 2 2 50 1600 EXIST OVEN UNIT POLE CT. 500 3 4 1600 WIRE AND 1T0NN AHU -2 EXIST 3492 2 .50 5 6 2 60 3622 EXIST AHU -1 CONDSIZE 3492 7 8 3622 2 1 LTS 4 REC EXIST 3W /6F 1/20 9 10 y3o 2250 EXIST EWH 1 LTS 4 REC EXIST 3W /SF 1/20 11 12 2250 to LIVING RM 4 PORCH EXIST 3W/SF 1/20 13 14 1/20 3W /SF EXIST BEDROOM HALLWAY POOL EQ DRYER EXIST 2500 2 30 15 18 I/20 3W /SF EXIST LTS 4 REC 8 2500 17 18 1/20 3W /SF EXIST MASTER BEDROOM 145 9 LTS 4 REC EXIST 3W /SF 1/20 19 20 1/20 3W /SF EXIST CAROLYN'S BATHROOM !! d12 LTS 4 MC EXIST 3W /SF 1/15 21 22 1/20 3W /SF EXIST MASTER BATH 4 HALLWAY CLO LTS 4 REC EXIST 3W /SF 1/15 23 24 1/20 1300 EXIST WASHER KITCHEN/FAM RM LTS EXIST 3W /SF 1/15 25 28 I/20 3W /SF EXIST LTS 4 REC LTS 4 REG EXIST 3W /SF 1/15 27 28 1/20 3W /SF EXIST GUEST BATHROOM 0 LTS 4 REC EXIST 3W /6F 1/20 29 30 1/15 3W /SF EXIST NEW HALLWAY, GUEST BR, LAUN GARB DISP. EXIST 1100 1/20 371 32 1/15 3W /SF EXIST LTS 4 REC FAM RM REC/U1ALL TV EXIST 3W /SF 1/20 33 34 Z 20 1204 EXIST REFRPGERATOR DISHWASHERMICROWAVE OVEN EXIST 2830 1/1 /20 35 38 1200 PROP BED ROOM 14,1/2" 3W/SF 1/15 37 381 3W /SF 12,1/2" LTS t REC /NEW COV tERR PROP BED ROOM 14,1/2" 3W/SF I/S 39 40 Ag 3W /SF 014,1/2" HALLWAY CLO / NEW CORK -EXT APPLIANCE /APPLIANCE EXIST 13000 U911-2-01411 42 it AS I 3W /SF EXIST LTS 4 REC / LTS 4 REG PHASE A: _� -NVA PHASE B: _�___VA TOTAL: __- VA_f 4) ._._AMPS. t II VtKIPT AT FIELD EXISTINCx CIRCUIT TO REMAIN. CONTRACTOR SHALL LABEL ALL CIRCUIT BREAKERS AT THIS PANEL ACCORDINGLY TO THE LOAD SERVED, PROVIDE TYPEWRITTEN PANEL BOARD DIRECTORIES, NO HAND WRITTEN LABELS (2) CIRCUIT UNDER THIS CONTRACT. PROVIDE NEW CIRCUIT BREAKER AND WIRING SIZE AS SHOWN. (3) PROVIDE A NEW CIRCUIT BREAKER ARC -FAULT INTERRUPTER TYPE TO COMPLY WITH N.E.C. ART 210.12$ (4) SEE LOAD CALCULATION THIS DRAWING. (5) PROVIDE NEW TAMDEM BREAKER SIZE AS SHOWK RELOCATE EXIST LOAD AND OR WIRE NEW LOAD AS SHOUT.. (6) ALL NEW CIRCUIT BREAKERS SHALL MATCH EXISTING PANEL TYPE MODEL AND MANUFACTURER FEED WITH: EXISTING 303 THW CU IN 1 -1 /4 "G t0 REMAIN. TYPE: SIEMENS LOAD CENTER x,65 q MODIFICATION: -- VOLTAGE 120/24OV, IPH, 3W WV PANEL 11511 ENCLOSURE: NEMA 3R, SURFACE MAINS: 125 A M.L.O. 0 u LOCATION: EXTERIOR CU AREA A.I.C.S.: 10,000 (EXISTING TO REMAIN) FED FROM: MAIN "B"-METER/F.P.L. Co. DESCRIPTION WIRE AND LOAD POLE CT. A P CT, POLE LOAD WIRE AND 1T0NN DESCRIPTION CONDSIZE (VA) TRIP No No TRIP (VA) CONDSIZE W CU -1 EXIST 3360 2 1 2 2 2184 EXIST ul Lu CU-2 ti r cl 1 3360 50 3 4 0 2184 to POOL PUMP EXIST 1150 2 5 8 Ao 2100 EXIST POOL EQ t 0 1150 ZO 7 8 210 0 m POOL LIGHTS EXIST 3W /SF 145 9 1/20 1440 312,1/2" NEW AC03 (DUCTLESS) SPACE -- -- } !! d12 I -- -- SPACE PHASE A: __ ----VA. PHASE B: _N_VA TOTAL: __- __VA_f3) --- AMPS. cI/ VtrarT AI t-ItLV tXItP IIMI G:I WIT'TO XF-MAIN. CONTRACTOR SHALL LABEL ALL CIRCUIT BREAKERS AT THIS PANEL ACCORDINGLY TO THE LOAD SERVED, PROVIDE TYPEWRITTEN PANEL BOARD DIRECTORIES, NO HAND WRITTEN LABELS (2) CIRCUIT UNDER THIS CONTRACT. PROVIDE NEW CIRCUIT BREAKER AND WIRING SIZE AS SHOWN. (3) SEE LOAD CALCULATION THIS DRAWING. (4) ALL NEW CIRCUIT BREAKERS SHALL MATCH EXISTING PANEL TYPE MODEL AND MANUFACTURER (1) �5xz) (1) (2)(4) EXISTING CORRIDOR AREA CFxISTING 303 THW CU EXISTING 303/0 THW CU IN 1-1/4"C TO REMAIN. f f N 2 "C TO REMAIN. EXIST f f 200A METER If I f EXIST f I MAIN r r,�- I I I I� �I IIM �l� ZoF3 I�ExIS�I I�EXIS4I EXIST tI II li I II R L II II PNL II t-rAIN ::�:: I I 12P/2O f -I I I I "A1i II II a II 3 of 3 I'� T JJ LJ L I�-�JI I - -__'" Q`�''� I EXISTING 212 THW GU c _I 11Z(G) IN I/2 "C I EXISTING 303 THW GU � I TO REMAIN IN I -1 /4 "G t0 REMAIN. NEW 104(6) TO PUMP (EXIST) TO COLD WATER THW CU METAL PIPE FOR BONDING l I EXISTING 303/0 THW CU IN 2 "C UG. 120/24OV, IPH, 3W ELECTRICAL TO REMAIN PROVIDE NEW 2 -5/8 DIAM x 10' -0" LONG DRIVEN GROUND RODS, COPPER RC5EfR DIAGRAM CLAD, SEPARATED 6' -0" To REMAIN. N.T.S. E-' x,65 q 0 WV 0 u t Eae \r �o e. W� U 1T0NN W W � O ul Lu r ti r ye t. t1fr x,65 q 0 0 t Eae \r e. W 96 �jbtaz HE � sY! oy � F�ZQE b y S15 A i3UssimbiwX DATEt 09/14/09 PROJ No: 9029 DWCs BYt JFB CHECKED: JEB REV$ SHEET TITLEt ISSUED FORT E -2 OF 2 0 0 t ul Lu r r cl 1 z to zwa • t 0 m r• • CL 1 W 96 �jbtaz HE � sY! oy � F�ZQE b y S15 A i3UssimbiwX DATEt 09/14/09 PROJ No: 9029 DWCs BYt JFB CHECKED: JEB REV$ SHEET TITLEt ISSUED FORT E -2 OF 2