09-653-010GENERAL N©TE5 - ELECTRICAL 1. -DO NOT SCALE ELECTRICAL DRAWINGS, REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT AND CONFIRM WITH OWNERS' REPRESENTATIVE. 2.- ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION OF THE NEC THE NFPA 10 4 SHALL COMPLY WITH THE CURRENT FLORIDA BUILDING CODE, AND ALL STATE AND LOCAL RULES AND ORDINANCES. 3.- MINIMUM WIRE SIZE SHALL BE NO, 14 AWG, EXCLUDING CONTROL WIRING, UNLESS OTHERWISE INDICATED. ALSO, UNLESS OTHERWISE INDICATED, ALL CONDUCTORS SHALL BE COPPER WITH THW OR THHN /THWN INSULATION FOR SIZES NO. 6 AND SMALLER. CONDUCTORS LARGER THAN NO, 6 SHALL HAVE TYPE THW NO. 8 AND LARGER SHALL BE STRANDED. ALL RACEWAYS AND PIPES PLACED IN OR THROUGH ANY CONCRETE SLAB SHALL BE SPACED A MINIMUM OF 3 DIAMETERS OF THE LARGEST CONDUIT OR PIPE OF ANY OTHER SERVICE .(WHEN APPLICABLE) 4.- ALL RACEWAYS UNDERGROUND AND /OR LARGER THAN 2 INCHES IN DIAMETER, SHALL BE GALVANIZED RIGID STEEL. PVC PIPE SGH. 40 WILL BE ACCEPTABLE IF APPROVED BY LOCAL REGULATIONS. CONTRACTOR TO VERIFY, ALL OTHER RACEWAYS 2 INCHES AND SMALLER IN DIAMETER MAY BE EM.T. WHEN AMOVE GROUND 5,- OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, AND CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCATIONS (4" x 4" MINIMUM SIZE). ro.- DISCONNECT SWITCHES SHALL BE HORSEPOWER RATED, HEAVY DUTY, QUICK -MAKE, QUICK - BREAK, IN NEMA I OR 3R ENCLOSURE AS REQUIRED BY EXPOSURE. Z.- IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION, THE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM, AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. 8. MOTOR STARTERS SHALL BE MANUAL OR MAGNETIC WITH THREE OVERLOAD RELAYS. S.- THE ELECTRICAL SYSTEM SHALL BE FULLY OPERATIONAL AND TESTED, AS WELL AS COMPLETELY GROUNDED AS REQUIRED BY THE NE.C. 10.- LOAD DATA IS BASED ON INFORMATION GIVEN TO THE ENGINEER At THE TIME OF DESIGN. VERIFY ALL EQUIPMENT CONDUCTOR SIZE, PROTECTION, ETC. REQUIREMENTS PRIOR TO ORDERING PANEL BOARDS, OR PRIOR TO INSTALLATION. 11.- ALL MATERIALS, DEVICES OR APPLIANCES LALL BE LISTED AND BEAR WITH THE STANDARDS OF UNDERWRITERS LABORATORIES (U.L.) OR ANY APPROVED NATIONALLY RECOGNIZED LABORATORY 12.- ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTANCE BY ENGINEER/ARCHITECT MUST BE A CONDITION OF THE CONTRACT. 13.- ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH PROGRESS OF CONSTRUCTION. 14.- CONTRACTOR SHALL GUARANTEE ALL MATERIALS, EQUIPMENT AND WORKMANSHIP ARE FREE OF DEFECT FOR A PERIOD OF NO LESS THAN ONE YEAR FROM THE DATE OF ACCEPTANCE. 15.- CONTRACTOR SHALL REMOVE ALL DEBRIS 4.ND UNUSED FIXTURES AND RETURN TO OWNER OR DISPOSE OF PROPERLY IF SO DIRECTED BY OWNER. 16.- CONTRACTOR SHALL INCLUDE IN HIS PRICE, PERMIT, TAXES AND /OR IMPACT FEES, INSURANCE, ETC, AND ENGINEERING FEES FOR PREPARATION OF AS -BUILT DRAWINGS. Ii.- IT 16 SUGGESTED THAT THE CONTRACTOR .CONFER WITH LOCAL UTILITY TO LOCATE THE ELECTRIC METER TO COMPLY WITH FEMA REQUIREMENTS 18.- ALL CONTROL WIRE$ AND CONNECTIONS REQUIRED FOR ALL ELECTRICAL APPLIANCES, AIR CONDITIONING AND VENTILATING EQUIPMENT OPERATION SHALL BE PROVIDED AND TESTED FOR A FULLY OPERATIONAL SYSTEM. M.- MAINTAIN 12" MINIMUM SEPARATION BETWEEN OUTLET BOXES ON OPPOSITE SIDES OF SOUND INSULATED WALLS 20.- CLAIMS FOR EXTRA WORK DUE TO MEETING CODE REQUIREMENTS WILL NOT BE CONSIDERED. 21. -ALL LIGHTING FIXTURES COLOR FINISH SHALL BE SELECTED BY ARCHITECT OWNER REPRESENTATIVE BEFORE ORDERING. 22.- CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND VERIFY EXACT LOCATIONS PRIOR TO BIDDING THE PROJECT. 23,- VERIFY AT FIELD WITH ARCHITECT OWNER REPRESENTATIVE EXACT LOCATION OF SIGNAL OUTLETS, LIGHT FIXTURES CONTROL SWITCHES AND WALL FIXTURES MOUNTING HEIGHT BEFORE ROUGHING -IN. 24.- COORDINATE W/ OWNER TYPE OF DATA PROVIDER BEFORE INSTALLATION OF OUTLETS. 25. -ALL DUPLEX RECEPTACLES SHALL BE 125V- 15A -2P -3W GROUNDED, STANDARD GRADE, COLOR SELECTED AND APPROVED BY ARCHITECT. 26- ALL LIGHT SWITCHES SHALL BE I POLE TOGGLE 125Y RATED 20A. COLOR SELECTED AND APPROVED BY ARCHITECT. 21 -ALL RECEPTACLES SHALL BE WIRED IN ACCORDANCE WITH N.E.C. TO ENDURE CORRECT POLARITY. 28.- CIRCUIT NUMBERS SHOWN ARE FOR IDENTIFICATION ONLY. IT SHALL BE THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO COMPLETE PHASE PANEL BOARD (BALANCE LOAD). 29. -ALL JUNCTION AND PULL -BOXES SHALL BE ACCESSIBLE ALL THE TIME, 30. -ALL RACEWAY ROUTED, INSULATED CONDUCTORS SYSTEM SHALL BE COLOR CODED AS FOLLOWS. 120/240V SYSTEM PHASE "A ": BLACK PHASE "B "- RED NEUTRAL WHITE GROUND GREEN 31. -ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL BE WEATHER - PROOF. FLOOR FLAN - ELECTRICAL aSCALE: 1/4" = V-011 WALL MOUNTED INCANDESCENT FIXTURE OUTLET. MOUNTING HEIGHT TO BE VERIFIED WITH ARCHITECT AND /OR OWNER. DUPLEX RECEPTACLE 3 POLE, 3 WIRE, 125V, 20A, MOUNTED AT 18" A.F.F. DUPLEX RECEPTACLE 3 POLE, 3 WIRE, 125V, 20A, WITH ARC -FAULT INTERRUPTER PROTECTION MOUNTED At 18" APP. SINGLE POLE TOGGLE SWITCH 204,120V MOUNTED 46" A.F.F. 3 3 -WAY TOGGLE SWITCH 2OA, 120V MOUNTED 48" AFF, © DIMMER SWITCH LUTRON NOVA SERIES 120V, 150OW OR EQUIVALENT, MOUNTED AT 48" A.F.R T TELEPHONE OUTLET, WALL MOUNTED AT IS" A.F.F, CEILING OR WALL MOUNTED JUNCTION BOX WITH COVER, TO SUIT LOCATION. TV /CABLE OUTLET, WALL MOUNTED AT 18" A.F.F. EF EXHAUST FAN MOTOR CONNECTION (FRACTIONAL HORSEPOWER) LEI DISCONNECT SWITCH TYPE AND SIZE AS SHOWN SD SMOKE DETECTOR 120V TYPE WITH BATTERY BACKUP (SEE PLAN NOTES) --- - — CONDUIT RUN CONCEALED IN CEILING OR WALLS, -- CONDUIT RUN UNDERGROUND, IN OR BELOW FLOOR SLAB. ICI ELECTRICAL PANEL SIZE AND RATING A$ SHOWN (SEE PANEL SCHEDULE$) GF.I. INDICATES GROUND FAULT INTERRUPTER W.P. INDICATES WEATHERPROOF, NEMA 3R ENCLOSURE. E INDICATES EX15TING EQUIPMENT t0 REMAIN. ER INDICATES EXISTING EQUIPMENT RELOCATED AS SHOWN, F INDICATES FUTURE ELECTRICAL EQUIPMENT NOT INSTALLED UNDER THIS CONTRACT, O�or^�V �tq NU NZAHSX60 z L!J Lu W oc.) Z a WD Q Wa ry cA 0M �< of > 2 ui cn u- _ z Q UJ 0 CL O w CL DATE: 07/15/09 FROJ NO: 9029 DWG 5Y, JFl u. JER d u M W O O�or^�V �tq NU NZAHSX60 z L!J Lu W oc.) Z a WD Q Wa ry cA 0M �< of > 2 ui cn u- _ z Q UJ 0 CL O w CL DATE: 07/15/09 FROJ NO: 9029 DWG 5Y, JFl CHECKED, JER �1. I I