Loading...
11-1245-001ANSUL, R -102 RESTAURANT FIRE SUPPRESSION SYSTEM (Standard UL 300 Listed TANK AND CARTRIDGE REQUIREMENTS ACTUATION AND EXPELLANT GAS LINE REQUIREMENTS Maximum Once the hazard analysis is completed and the total nozzle flow This section contains the guidelines for installing the actuation and Duct numbers are established, the quantity and size of agent tanks and expellant gas lines between the regulated release mechanism reg- Appliance cartridges needed to supply the nozzles with the proper volumes ulator, each regulated actuator regulator, and each agent tank. Supply Line of agent at the proper flow rates can be determined. For cartridges These limitations should be considered when selecting the com- Branch Line used in the regulated release mechanism, flow capacities, tank ponent mounting locations. Pipe Size quantities and sizes, and regulated release cartridge options are 3/8 in. given in the table below. Actuation Gas Line - 6 to 8' Tanks Maximum 3/8 in. Total Quantity and Regulated Release " 8 Tank maximum reflects the utilization of 3 tank regulated actuators. 40 ft. Flow Size of Cartridge Options 1. Use only 1/4 in. Schedule 40 black iron, hot - dipped galva- 4 ft. Num ers' Tanks Nitrogen Carbon Dioxide nized, chrome - plated, or stainless steel pipe and fittings. 1100 11- 5 (1) 1.5 Gallon LT -20 -R 101 -10 2. The actuation gas line piping is installed from the regulated (2.4 m) 6-11 (1) 3.0 Gallon LT -30 -R 101 -20 release mechanism to each regulated actuator connected (3.7 m) within the system. The total length of the actuation gas line 6 ft. 11-16 (1) 1.5 Gallon Double 101 -30 from the regulated release assembly to the regulated actuator 2 ft. (1) 3.0 Gallon assembly(ies) must not exceed 20 ft. (6 m) when using an 0 E 16-22 (2) 3.0 Gallon Double 101 -30" LT -20 -R, an LT 30 -R nitrogen cartridge, or a 101 -10 or a (1.2 m) When one or more regulated actuators are used, the following 101 -20 carbon dioxide cartridge. See Figure 81. (.6 m) tank and cartridge combinations apply for each regulated actuator. '9 Regulated Actuator Regulated Actuator 4 Tank(s) Cartridge Elbows (1) 1.5 Gallon LT20 -R or 101 -10 - (1) 3.0 Gallon LT 30 -R or 101 -20 2W (1) 1.5 Gallon and LT -A- 101 -30 or 101 -30" or 1 (1) 3.0 Gallon double tank 2 (2) 3.0 Gallon LT-A-101-30 or 101 -30" or Maximum Flow double tank 4 ' For exceptions to maximum now numbers, soe Dishibutlon Piping Requirements for 1.5 4 gallon and 3.0 gallon systems In this Section. Diameter - 31 -7/8 in. • The 101.30 cartridge can not be used when (2) two 3.0 gallon tanks are mangolded together.) For higher total flow numbers (23 to 110), multiple cartridges and Total Pipe Used regulated actuators are required as shown in the System Selection 4.5 ft. Guide in Section IX - Appendix. 7.5 ft. REGULATED ACTUATOR ASSEMBLY - EXPELLANT GAS LINES 1N NOT INCLUDED IN ACTUATION 1 GAS LING LENGTH TOTALS Distribution Piping Requirements - 3.0 Gallon System Maximum Minimum Duct Plenum Appliance Requirements Supply Line Branch Line Branch Line Branch Line Pipe Size 3/8 in. 3/8 in. 3/8 in. 3/8 in. Maximum Length 40 ft. 8 ft. 4 ft. 12 ft. 1100 (12.2 m) (2.4 m) (1.2 m) (3.7 m) Maximum Rise 6 ft. 4 ft. 2 ft. 2 ft. 0 E (1.8 m) (1.2 m) (.6 m) (.6 m) Maximum 900 '9 4 4 6 Elbows 1 - 419337 2W Maximum Tees 1 2 2 4 Maximum Flow 11'" 4 2 4 Numbers Diameter - 31 -7/8 in. Total Pipe Used 10.5 FT. 4.5 ft. 0.5 ft. 7.5 ft. ACTUATION GAS LINE WITH AN LT-20-R, MEN'S ROOM LT-00•R. 101.10 OR 101.20 CARTRIDGE MAXIMUM LENGTH OF 20 FT. (6 m), \ / MAXIMUM NO. OF FITTINGS 9 1� REGULATED ACTUATOR ASSEMBLY REGULATED E REAR EXIT hl. REGULATED RELEASE \ ASSEMBLY WOMEN'S ROOM ~ �� 7 ELECTRIC\ ELECTRIC REMOTE PULL STATION PANE B JPANEL A AT PATH OF EGRESS All (VERIFY LOCATION) HORN C;P, STROBE K CLASS FIRE EXTINGUISHER WITH INSTRUCTIONS, LESS SYSTEM THAN 30' FROM HOOD CYLINDER -I r)r ATION) - (VERIFY LOCATION) WARE WASHING-, I - I ,14x14 W -0" I - COUNTER ANSUL R -102 NOZZLE APPLICATION CHART ■ 0 PARTIAL PLAN KITCHEN HOOD 1/4" = V -0" COUNTER Q JA I v GENERAL NOTES: 1. Systems comply with UL 300. 2. Systems comply with NFPA 17 and 17A 3. All pipe run in J" black iron. 4. All changes in direction of conduit shall be be made with corner pulleys 5. Upon activation of the fire system: A. Make -up air fan(s) must shut down. B. All electric appliances and outlets under the hood must shut down. C. Exhaust fan must continue to run, or turn on if control switch is in the off position. D. Alarm device (horn & strobe) must activate. F. Gas supply must shut off. SYSTEM COMPLIANCE NOTES NFPA 17A 2002 EDITION 4.5.2 All piping and fittings are black iron. 5.1.5 If applicable, two or more hazards protected by same system or simultaneously operated systems. 5.2.1.6-Manual actuator provided. 5.2.1.7-All operating devices protected. 5.2.1.8-Audible and /or visual indicator provided. 5.2.1.10 - Manual pull located at path of egress. 5.4.5 Tanks accessible for service'. 5.6.1.7-All penetrations sealed by UL listed device. 6.1.1.(2)- Installation conforms to NFPA 17A -2002. 6.1.1.(3) -AIL equipment listed by manufacturer. 6.1.1.(4)- Auxiliary devices acceptable to AHJ and manufacturer. 6.1.1.(5)- Balloon test per manufacturer. 6.1.1.(6)- Hazard protected (see plan). 6.3.1 Plans suitably dimensioned. 6.3.2 Plans detailed (see plan). 6.3.3 See piping allowances. 6.3.4 See floor plan. PLAN VIEW 1/2" = 1' -0" 6..0" DUCT ZW 14x14 0.5 2.5' 12' "QUICK SEALS" 2' STEEL BAFFLE PLATE -NFPA 96, 8" /_2008, 12.1.2.5 GRIDDLE RANGE FRYER 18x20 24x24 14x21 (DIMENSIONS REPRESENT THE COOKING SURFACE) FRONT VIEW 1/2" = 1' -0" 1/2" EMT G SYSTEM CYLINDER 1/2- EMT HORN & STROBE GAS VALVE K CLASS K CLASS FIRE EXTINGUISHER 30 FEET MAXIMUM FROM HOOD Maximum Minimum ai Nozzle Tip o Hazard Hazard Dimension Nozzle Quantity Nozzle Heights Nozzle Part No. Stamping- Flow No. Number of Nozzles Number of Flow Points Duct or Transition Length - Unlimited 1 - 430912 1100 (Single Nozzle) Perimeter - 50 in. A I--7 .00i �•.. = s 0 E 3 Diameter - 16 in. Duct or Transition Length - Unlimited 1 - 419337 2W 1 2 (Single Nozzle) Perimeter - 100 in. U Q Diameter - 31 -7/8 in. 83 rn Plenum Length - 10 ft. 1 - 419335 1N 1 1 (Horizontal Protection) Fryer (Non -Split Vat Only) Maximum Size 1 27 - 47 in. 419339 230 1 2 (with drip board) 21 in. x 14 in. High Proximity Fry pot must not exceed 15 in. x 14 in. Range Longest Side 28 In. Area - 336 sq. in. 1 40 - 48 in. W/ Backshelf 419333 1 F Range Longest Side (High Proximity) 28 in. 1 40 - 50 in. 419340 245 1 2 Area - 672 sq. in. Griddle Longest Side (High Proximity) 36" 1 35 - 40 in. 419335 1N 1 1 Area - 1080 sq. in. Gas- Radiant Char - Broiler Longest Side - 36 in. Area - 864 sq. in. 1 15 - 40 in. 419335 417332 / 1 N 1 NSS / Salamander Length - 32.5 in. Broiler Width - 30 in. 2 - 419334 1/2N TOTAL FLOW POINTS USED 8 MAXIMUM FLOW POINTS ALLOWED 11 ■ 0 PARTIAL PLAN KITCHEN HOOD 1/4" = V -0" COUNTER Q JA I v GENERAL NOTES: 1. Systems comply with UL 300. 2. Systems comply with NFPA 17 and 17A 3. All pipe run in J" black iron. 4. All changes in direction of conduit shall be be made with corner pulleys 5. Upon activation of the fire system: A. Make -up air fan(s) must shut down. B. All electric appliances and outlets under the hood must shut down. C. Exhaust fan must continue to run, or turn on if control switch is in the off position. D. Alarm device (horn & strobe) must activate. F. Gas supply must shut off. SYSTEM COMPLIANCE NOTES NFPA 17A 2002 EDITION 4.5.2 All piping and fittings are black iron. 5.1.5 If applicable, two or more hazards protected by same system or simultaneously operated systems. 5.2.1.6-Manual actuator provided. 5.2.1.7-All operating devices protected. 5.2.1.8-Audible and /or visual indicator provided. 5.2.1.10 - Manual pull located at path of egress. 5.4.5 Tanks accessible for service'. 5.6.1.7-All penetrations sealed by UL listed device. 6.1.1.(2)- Installation conforms to NFPA 17A -2002. 6.1.1.(3) -AIL equipment listed by manufacturer. 6.1.1.(4)- Auxiliary devices acceptable to AHJ and manufacturer. 6.1.1.(5)- Balloon test per manufacturer. 6.1.1.(6)- Hazard protected (see plan). 6.3.1 Plans suitably dimensioned. 6.3.2 Plans detailed (see plan). 6.3.3 See piping allowances. 6.3.4 See floor plan. PLAN VIEW 1/2" = 1' -0" 6..0" DUCT ZW 14x14 0.5 2.5' 12' "QUICK SEALS" 2' STEEL BAFFLE PLATE -NFPA 96, 8" /_2008, 12.1.2.5 GRIDDLE RANGE FRYER 18x20 24x24 14x21 (DIMENSIONS REPRESENT THE COOKING SURFACE) FRONT VIEW 1/2" = 1' -0" 1/2" EMT G SYSTEM CYLINDER 1/2- EMT HORN & STROBE GAS VALVE K CLASS K CLASS FIRE EXTINGUISHER 30 FEET MAXIMUM FROM HOOD REMOTE PULL STATION -AT PATH OF EGRESS (SEE PLAN) 48" Seal -, 2 RAJA BUCHANAN FL P.E # 48916 W C W� t� I■-1 N E-4 � °o W� 0 T LO Date: 9/16/2011 Drawn: FP Reviewed: RAB Job #: Revisions: Drawing No. MECHANICAL HOOD -3 fa i n• 1 �y� I I r" C i r.. 1 l i 1 � ai - - o to -00 to C, a QJ � rr� ,-% Vl u A I--7 .00i �•.. = s 0 E 3 n � m o eo U Q 83 rn to REMOTE PULL STATION -AT PATH OF EGRESS (SEE PLAN) 48" Seal -, 2 RAJA BUCHANAN FL P.E # 48916 W C W� t� I■-1 N E-4 � °o W� 0 T LO Date: 9/16/2011 Drawn: FP Reviewed: RAB Job #: Revisions: Drawing No. MECHANICAL HOOD -3 fa i n• 1 �y� I I r" C i r.. 1 l i 1 � ai