10-558R-014
AHU -1 COOLING COIL PEAK Peaked at Time: Mohr: 9 / 16 Outside Air: OADBM/B/HR: 89/76/113 Space Plenum Net Percent Sens. + Lat. Sens. + Lat Total Of Total Btu/h Btu/h Btu/h ( %) Envelope Loads 13 Lights 4,330 People Skylite Solar 0 0 0 0 Skylite Cond 0 0 0 0 Roof Con d 2,130 0 2,130 6 Glass Solar 6,135 0 6,135 19 Glass/Door Cond 4,105 0 4,105 12 Wall Cond 2,062 0 2,062 6 Partition /Door 112 0 112 0 Floor 0 -1,296 0 0 Adjacent Floor 0 0 0 0 Infiltration 2,106 2,106 6 Sub Total =_> 16,650 0 16,650 50 Internal Loads 13 Lights 4,330 People 0 Misc 11,775 Sub Total =_> 16,105 Ceiling Load 0 Ventilation Load 0 Adj Air Trans Heat 0 Dehumid. Ov Sizing 0 Ov /Undr Sizing 0 Exhaust Heat , 1 Sup. Fan Heat 0 Rot. Fan Heat 0 Duct Heat Pkup 0 Underflr Sup Ht Pkup 0 Supply Air Leakage 100.00 Grand Total => 32,754 Main Clg Aux Clg Opt Vent Total 0 4,330 13 0 0 0 0 11,775 36 0 16,105 49 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 251 1 0 0 0 0 0 0 0 0 0 0 0 0 33,005 100.00 System Checksums By SDM Consulting Engineers CLG SPACE PEAK Mo/Hr: Sum of OADB: Peaks Space Percent Sensible Of Total Btu/h (%) 0 0 0 0 2,130 7 6,135 20 4,105 13 2,062 7 112 0 0 0 0 0 585 2 15,129 48 4,330 14 0 0 11 ,775 38 16,105 52 0 0 0 0 0 0 0 0 31,233 100.00 2.8 33.0 Project Name: ADD & ALTER TO MUNILLAS RESIDENCE Dataset Name: FERNANDO MUNILLAJR RES.TRC Envelope Loads Skylite Solar Skylite Cond Roof Cond Glass Solar Glass/Door Cond Wall Cond Partition/Door Floor Adjacent Floor Infiltration Sub Total =_> Internal Loads Lights People Misc Sub Total =_> Ceiling Load Ventilation Load Adj Air Trans Heat OvlUndr Sizing Exhaust Heat OA Preheat Diff. RA Preheat Diff. Additional Reheat Underflr Sup Ht Pkup Supply Air Leakage Grand Total => HEATING COIL PEAK OF OF COOLING COIL SELECTION Heating Design Total Capacity OADB: Sens Cap. Coil Airflow Enter DB/WB /HR ton MBh MBh cfm °F °F gr/lb 2.8 33.0 31.5 1,412 75.0 60.3 54.7 0.0 0.0 0.0 0 0.0 0.0 0.0 0.0 0.0 0.0 0 0.0 0.0 0.0 2.8 33.0 Project Name: ADD & ALTER TO MUNILLAS RESIDENCE Dataset Name: FERNANDO MUNILLAJR RES.TRC Envelope Loads Skylite Solar Skylite Cond Roof Cond Glass Solar Glass/Door Cond Wall Cond Partition/Door Floor Adjacent Floor Infiltration Sub Total =_> Internal Loads Lights People Misc Sub Total =_> Ceiling Load Ventilation Load Adj Air Trans Heat OvlUndr Sizing Exhaust Heat OA Preheat Diff. RA Preheat Diff. Additional Reheat Underflr Sup Ht Pkup Supply Air Leakage Grand Total => HEATING COIL PEAK OF OF Mo /Hr: Heating Design 53.0 OADB: 47 0.0 0.0 Space Peak Coil Peak Percent Space Sens Tot Sans Of Total Btu/h Btu/h (%) 0 0 0.00 0 0 0.00 -749 -749 2.50 0 0 0.00 -8,478 -8,478 28.34 -1,736 -1,736 5.80 -358 -358 1.20 0 0 0.00 0 0 0 -1,296 -1,296 4.33 - 12,616 - 12,616 42.18 Leave DBIWBIHR OF OF gr/lb 55.0 52.0 53.0 0.0 0.0 0.0 0.0 0.0 0.0 4,330 4,330 -14.48 0 0 0.00 11,775 11,775 -39.37 16,105 16,105 -53.84 0 0 0.00 0 0 0.00 0 0 0 - 33,398 - 33,398 111.66 ExFlr 0 0.00 0 0 0.00 0 0 0.00 809 0 0.00 0 0.00 0 0.00 - 29,910 - 29,910 100.00 Single Zone TEMPERATURES AREAS Cooling Heating Gross Total Glass Ra Plenum 75.0 70.0 ft2 75.0 Floor 1.153 75.0 70.0 Part 231 0.0 Fn BldTD Int Door 0 Fn Frlct 0.1 ExFlr 0 MinStop /Rh 0 Roof 772 0 0 Wall 809 33 4 Ext Door 247 0 0 Single Zone TEMPERATURES 13 Cooling Heating SADB 55.2 89.0 Ra Plenum 75.0 70.0 Return 75.0 70.0 Ret /OA 75.0 70.0 Fn MtrTD 0.0 0.0 Fn BldTD 0.0 0.0 Fn Frlct 0.1 0.0 AIRFLOWS 13 Cooling Heating Cooling Heating Diffuser 1;412 1,412 Terminal 11412 1,412 Main Fan 1,412 1,412 Sec Fan 0 0 Nom Vent 0 0 AHU Vent 0 0 Infil 51 51 MinStop /Rh 0 0 Return 1,462 1,462 Exhaust 51 51 Rm Exh 0 0 Auxiliary 0 0 Leakage Dwn 0 0 Leakage Ups 0 0 ENGINEERING CKS 13 Cooling Heating % OA 0.0 0.0 cfmlft' 1.22 1.22 cfm /ton 513.26 ft2lton 419.31 Btulhr -ft' 28.62 -25.93 No. People 0 HEATING COIL SELECTION 13 Peaked at Time: CapacityCoil Airflow Ent Lvg 87/75/112 MBh cfm OF OF Main Htg -29.9 1,412 70.0 89.0 Aux Htg 0.0 0 0.0 0.0 Preheat 0.0 0 0.0 0.0 Humidif 0.0 0 0.0 0.0 Opt Vent 0.0 0 0.0 0.0 Total -29.9 0 Floor 0 RACED 700 v6.2.6.5 calculated at 02:36 PM on 09/15/2010 Alternative - 1 System Checksums Report Page 1 of 2 AHU -2 COOLING COIL PEAK 13 Peaked at Time: Mo /Hr: 8 / 11 Outside Air: OADB/WB/HR: 87/75/112 Space Plenum Net Percent Sens. + Lat. Sens. + Lat Total Of Total Btu/h Btu/h Btu/h ( %) Envelope Loads 13 Lights 4,726 People Skylite Solar 0 0 0 0 Skylite Cond 0 0 0 0 Roof Cond 2,273 0 2,273 6 Glass Solar 15,811 0 15,811 42 Glass/Door Cond 1,447 0 1,447 4 Wall Cond 2,523 0 2,523 7 Partition /Door 0 0 0 0 Floor 0 -1,220 0 0 Adjacent Floor 0 0 0 0 Infiltration 2,459 2,459 7 Sub Total =_> 24,513 0 24,513 66 Internal Loads 13 Lights 4,726 People 1,400 Misc 6,348 Sub Total =_> 12,474 Ceiling Load 0 Ventilation Load 0 Adj Air Trans Heat 0 Dehumid. Ov Sizing 0 Ov /Undr Sizing 0 Exhaust Heat 1 Sup. Fan Heat 0 Rot. Fan Heat 0 Duct Heat Pkup 0 Underflr Sup Ht Pkup 0 Supply Air Leakage 100.00 Grand Total => 36,987 0 4,726 13 0 1,400 4 0 6,348 17 0 12,474 33 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 326 1 0 0 0 0 0 0 0 0 0 0 0 0 37,313 100.00 System Checksums By SDM Consulting Engineers CLG SPACE PEAK Mo/Hr: Sum of OADB: Peaks Space Percent Sensible Of Total Btu/h ( %) 0 0 0 0 2,273 7 15,811 46 1,447 4 2,523 7 0 0 0 0 0 0 634 2 22,688 65 4,726 14 980 3 6,348 18 12,054 35 0 0 0 0 0 0 0 0 34,743 100.00 Total 3.1 37.3 Project Name: ADD & ALTER TO MUNILLAS RESIDENCE Dataset Name: FERNANDO MUNILLA JR RES.TRC Envelope Loads Skylite Solar Skylite Cond Roof Cond Glass Solar Glass/Door Cond Wall Cond Partition/Door Floor Adjacent Floor Infiltration Sub Total =_> Internal Loads Lights People Misc Sub Total =_> Ceiling Load Ventilation Load Adj Air Trans Heat Ov /Undr Sizing Exhaust Heat OA Preheat Diff, RA Preheat Diff. Additional Reheat Underflr Sup Ht Pkup Supply Air Leakage Grand Total => HEATING COIL PEAK OF OF COOLING COIL SELECTION Heating Design Total Capacity OADB: Sens Cap. Coil Airflow Enter DBIWB /HR ton MBh MBh cfm OF OF gr4b Main Clg 3.1 37.3 35.1 1,572 75.0 60.3 54.8 Aux Clg 0.0 0.0 0.0 0 0.0 0.0 0.0 Opt Vent 0.0 0.0 0.0 0 0.0 0.0 0.0 Total 3.1 37.3 Project Name: ADD & ALTER TO MUNILLAS RESIDENCE Dataset Name: FERNANDO MUNILLA JR RES.TRC Envelope Loads Skylite Solar Skylite Cond Roof Cond Glass Solar Glass/Door Cond Wall Cond Partition/Door Floor Adjacent Floor Infiltration Sub Total =_> Internal Loads Lights People Misc Sub Total =_> Ceiling Load Ventilation Load Adj Air Trans Heat Ov /Undr Sizing Exhaust Heat OA Preheat Diff, RA Preheat Diff. Additional Reheat Underflr Sup Ht Pkup Supply Air Leakage Grand Total => HEATING COIL PEAK OF OF Mo /Hr: Heating Design 52.7 OADB: 47 0.0 0.0 Space Peak Coil Peak Percent Space Sens Tot Sens Of Total Btu/h Btulh (%) 0 0 0.00 0 0 0.00 -1,197 -1,197 3.59 0 0 0.00 -3,226 -3,226 9.68 -2,756 -2,756 8.27 0 0 0.00 0 0 0.00 0 0 0 -1,220 -1,220 3.66 -8,398 -8,398 25.21 Leave DBlWBIHR OF OF grub 55.0 51.9 52.7 0.0 0.0 0.0 0.0 0.0 0.0 4,726 4,726 -14.19 0 0 0.00 6,348 6,348 -19.05 11,074 11,074 -33.24 0 0 0.00 0 0 0.00 0 0 0 - 35,992 - 35,992 108.03 ExFlr 0 0.00 0 0 0.00 0 0 0.00 977 0 0.00 0 0.00 0 0.00 - 33,316 - 33,316 100.00 Single Zone TEMPERATURES AREAS Cooling Heating Gross Total Glass Ra Plenum 75.0 70.0 ftZ 75.0 Floor 1,232 75.0 70.0 Part 0 0.0 Fn BIdTD Int Door 0 Fn Frict 0.1 ExFlr 0 MinStoplRh 0 Roof 1,235 0 0 Wall 977 119 12 Ext Door 18 0 0 Single Zone TEMPERATURES Cooling Heating SADB 55.2 89.0 Ra Plenum 75.0 70.0 Return 75.0 70.0 Ret /OA 75.0 70.0 Fn MtrTD 0.0 0.0 Fn BIdTD 0.0 0.0 Fn Frict 0.1 0.0 AIRFLOWS Cooling Heating Cooling Heating Diffuser 1,572 1,572 Terminal 1,572 1,572 Main Fan 1,572 1,572 Sec Fan 0 0 Nom Vent 0 0 AHU Vent 0 0 Infil 48 48 MinStoplRh 0 0 Return 1,620 1,620 Exhaust 48 48 Rm Exh 0 0 Auxiliary 0 0 Leakage Dwn 0 0 Leakage Ups 0 0 ENGINEERING CKS Cooling Heating % OA 0.0 0.0 cfm/ft' 1.28 1.28 cfm /ton 505.70 ft' /ton 396.12 Btuihrft' 30.29 -27.05 No. People 4 HEATING COIL SELECTION P.E. 53823 CapacityCoil Airflow Ent Lvg MBh cfm OF OF Main Htg -33.3 1,572 70.0 89.0 Aux Htg 0.0 0 0.0 0.0 Preheat 0.0 0 0.0 0.0 Humildif 0.0 0 0.0 0.0 Opt Vent 0.0 0 0.0 0.0 Total -33.3 'RACED 700 v6.2.6.5 calculated at 02:36 PM on 09115/2010 Alternative - 1 System Checksums Report Page 2 of 2 M5.00 I 1 ADDITION & ALTERATION TO THE O'IUNILLA RESIDENCE 5901 S.W. 81 STREET SOUTH MIAMI, FL 33143 APLAN UPDATE NOVEMBER 01,2010 ERNESTO ALOMA P.E. 53823 MANUEL P. MONTOYA P.E. 66220 HECTOR J. CASTILLO P.E. 65405 ALBERTO M.. MALATS c, P. E., `70692 - MECHANICAL ENGINEE O JOSE1Jj MAR EZ RODRIGO i.�ENE2ES d6gQ 8 ° Q` 0 f � 07 CONSULTING ENGINEERS 135 ALMERIA AVENUE CORAL GABLES, FLORIDA 33134 (305) 446 -2788 (PHONE) (305) 443 -5944 (FAX) EB- 00003791 www.sdmcorp.com ]Up 4ex ]EI ASSOCIATES, P.A. ARCHITECTS 500 SOUTH DIXIE HWY, SUITE 303 CORAL GABLES, FL, 33146 PH. (305) 665 -0641 JUNE 10, 2010 JOHN E. JUNKIN Aft 006454