11-146-011ROUND FLEX DUCT HANGING DETAIL
NTS
MAX. SPAN 48"
mmudem
ATTACH TO TOP CORD
OF JOIST WITH 5/16 NUTS,BOLT, FENDER WASHERS
DUCT HANGING DETAIL
NTS
NOTE:
HANG DUCTS ACCORDING
TO SMACNA STANDARDS
TYPICAL HAN
STRAP & SADDLE
DUCT HANGING
DETAIL
=14mo
1wf09VJI9RM19m1=--
pr
TYPICAL CHANNEL
& STRAP DUCT
HANGING DETAIL
"low,
GENERAL MECHANICAL NOTES
GENERAL MECHANICAL NOTES
AC UNIT EXISTING AC UNIT 1- ALL WORK EXECUTED UNDER THESE OFFICIAL DOCUMENTS SHOULD BE PERFORMED BY A
LICENSED AND INSURED MECHANICAL CONTRACTOR AND BE IN COMPLIANCE WITH THE
LATEST FLORIDA BUILDING CODE (FBC), SHEET METAL & AIR CONDITIONING
DUCTWORK: RIGID FOILFACED 1.5" R=6.0 SUPPORT CONTRACTOR'S ASSOCIATION (SMACNA) STANDARDS, AND ALL OTHER APPLICABLE STATE
48" O.C. ALL TURNS AND TRANSITIONS AND LOCAL CODE. ;-"7,
PRESSURE TAPE AND MASTIC ,SEAL ALL SEAMS ...............
. . . . . . . . . . . . . . .
AND JOINTS. 2- ALL WORK SHALL BE PERFORMED IN A FIRST CLASS WORKMANSHIP MANNER TO
PRODUCE A COMPLETE SYSTEM THAT IS FULLY BALANCED, AND ADHERES TO ALL
FLEX UL CLASS ONE AIR DUCT, R=6 APPLICABLE CODES AND REGULATIONS.
SUPPORT 48"O.C.. SPIN IN COLLARS- 3- MECHANICAL CONTRACTOR SHALL PROVIDE A WRITTEN GUARANTEE THAT THE COMPLETE
WITH M.V.D. TIE WRAP INNER LINER AND SYSTEM INSTALLED IS FREE OF DEFECTS OF MATERIALS AND WORKMANSHIP FOR A ��jjLO
PRESSURE TAPE AND MASTIC SEAL OUTER PERIOD OF A YEAR AFTER THE WORK IS COMPLETE AND TURNED OVER TO THE OWNER.
LINER WITHOUT COMPRESSING INSULATION ARCHITECTURE &
4- THE MECHANICAL CONTRACTOR IS RESP NSIBLE TO OBTAIN HIS OWN PERMIT AND PAY
EXHAUST: GALVANIZED SNAP LOCK-SUPPORT, R=6 ALL PERMIT AND INSPECTION FEES. PLANNING LLC_
48" O.C• AND AT ALL'JURNS. NO SUPPORT
OR WEIGHT TO LAY ON EXHAUST FAN HOUSING 5-AT THE COMPLETION OF THE PROJE OR RESPONSIBLE TO PROVIDE A
INSULATION R=6 ,SET OF PRINTS CLEARLY MARKED, D CONDITIONS TO THE AA26001717
DIFFUSERS: METALAIRE SERIE 5800 ENGINEER FOR RECORD.
RETURNS: METAL*AIRE SERIES RH 6-0
.,ONTRACTOR SHALL PAY SPECIAL IPMENT, FURNITURE, AND
- CARPETING TO PREVENT CONTAMI WRAPPING FURNITURE AND
EXHAUST FAN :NA EQUIPMENT. ALL WASTE AND DEB 'THE END OF EACH DAY TO 5200 SUNSET DRIVE
THERMOSTAT: REUSE EXISTING NEW USE BUILDING STANDARD MAINTAIN ACCEPTABLE INDOOR AIR Q ALIT L VEL U G THE CONSTRUCTION. MIAMI, FL 33143
7- ANY PORTION OF EXISTING BUILDING (FLOOR, WALL, CEILING, OR ROOF) THAT IS T- 786.2535530
AFFECTED BY EITHER REMOVAL, RELOCATIOW40R INSTALLATION OF A NEW EQUIPMENT F. 305.6612944
SHALL BE REPAIRED AND MATCHED FINISHED EXISTING CONDITIONS ACCORDING TO E-JUAN@CDG-CAP.COM
ARCHITECTURAL DRAWINGS OR SPECIFICATIONS.
8- WHEREVER DUCT RUNS THROUGH STRUCTURAL ELEMENT SUCH AS BEAM PRECAUTION
SHALL BE TAKEN TO COORDINATE WITH OTHER TRADES TO RELOCATE OR TO PROVIDE
NECESSARY SLEEVE BEFORE CONCRETE IS BEING POURED.
FRESH REQUIREMENTS PER ASHRAE 62.1 2001 9- SUPPLY 6 COPIES OF SHOP DRAWINGS FOR REVIEW TO ARCHITECT. NO EQUIPMENT IS TO
BE ORDERED PRIOR TO THEIR APPROVAL.
10-MECHANICAL CONTRACTOR TO PROVIDE TWO (2) COMFORT BALANCE VISITS TO SUIT THE
OFFICE AREA NEEDS OF THE CLIENTS.
5CFM/PERSON 2PEOPLE + 0.06CFM/SF X 198 = 23CFM 11-OPENINGS AND DUCT TRAVELING THROUGH FIRE RATED WALL, TENANT DEMISING WALL,
MASSAGE AREA
MECHANICAL AND ELECTRICAL ROOM, WALL AND FLOOR PARTITION, FLOOR AND ROOF 20CFM/PERSON X 5PEOPLE + .06CFM/SF X 446SF SLAB SHALL BE INSTALLED WITH "B"-FIRE DAMPER. 127CFM 12-NOT USED
FRESH AIR REQUIRED 150 CFM
FRESH AIR PROVIDED 150 CFM 13-MOTORIZED DAMPERS REQUIRED ON EXHAUST AND OUTDOOR SUPPLY WHERE AIR FLOW
IS GREATER THAN 300 CFM, PER F.B.C• 2004, SECTION 13-409, VENTILATION,
PARAGRAPH 13-409.1.ABC.3 VENTILATION CONTROLS. 0 M
14-H.V.A.C. CONTRACTOR IS RESPONSIBLE FOR PROVIDING A FULLY OPERATIONAL AND
BALANCED SYSTEM THAT ADHERES TO ALL APPLICABLE CODES AND REGULATIONS.
15-CONTRACTOR TO PROVIDE CERTIFIED TEST AND BALANCE FOR ALL SYSTEMS
16-IN CEILINGS BEING USED AS A PLENUM, COMBUSTIBLES OR COMBUSTIBLE CONTRUC11ON
SHALL NOT BE ALLOWED.
SITE VISIT <
C�
1- MECHANICAL CONTRACTOR IS DULY REQUIRED TO VISIT PROJECT SITE AND VERIFY >
EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS. HE OR SHE SHALL NOTIFY THE 0
ENGINEER OF ANY DISCREPANCY AT ONCE. FAILURE TO DO SO, THE MECHANICAL
CONTRACTOR IS PROCEEDING AT HIS OWN RISK.
2- DESIGN THAT IS CALLED FOR NEW DUCT OR PIPING TO BE CONNECTED TO EXISTING
SYSTEM REQUIRES THE CONTRACTOR TO VERIFY EXISTING DUCT & PIPING SIZE BEFORE � > Lo
FABRICATION AND INSTALLATION. I ^ () () 00
3- WHENEVER INTERFERENCE OR CONFLICT OCCURS WITH THE PROPOSED DESIGN, BEFORE = Lr)
PROCEEDING TO ANY CHANGE OR DEVIATION FROM THE EXISTING BID, THE CONTRACTOR
SHALL SUBMIT A WRITTEN REQUEST FOR THE CHANGE INCLUDED A DETAILED DRAWING
FOR APPROVAL FROM ARCHITECT/ ENGINEER.
4- CONTRACTOR SHALL CONSULT WITH STRUCTURAL ENGINEER' MERICUTTING OR MAKING
OPENING IN ANY BUILDING COMPONENT. CONTRACTOR $U4jL_Wk1FY THAT SfRUCTIURAL°l IN* "i;/
INTEGRITY OF THE BUILDING IS NOT BEING COMPROMISr:- z
5- POST TENSION STRUCTURAL SLAB: NO CUTTING OR DRJLLING SHALL BE TAKEN PLACE
WITHOUT THE X-RAY OF THE SLAB AND THE WRITTEN !APPR6,VAL OF THE STRUCTURAL In
ENGINEER OF THE BUILDING.
0
Cn u
EXISTING HVAC SYSTEM
L0
1- MECHANICAL CONTRACTOR MUST CHANGE THE AIR FIL6' IN-ALL ..WORKING AJ-R., \10
-CONDITIONING UNIT DURING CONSTRUCTION EVERY 21 tESS--,DEPENDING-OW4k= \10
AMBIENT ENVIRONMENT TO PREVENT AIR CONTAMINA1�1 N,-EQUIPMENTif.,
Vill-tift
BEARING FAILURE, DAMPER MALFUNCTION, ETC... rip (A
- __
2- AFTER CONSTRUCTION MECHANICAL CONTRACTOR IS T D VACUUM THOROUGHLY THE
MECHANICAL ROOM TO REMOVE ALL DUSTY PARTICLES, INSPECT AND' REPLACE AIR
FILTERS, BEARINGS OR BELTS FOR OPTIMAL UNIT OP RATION. A7'01�
N QUIP
1
3- WHEN REUSING EXISTING AIR CONDITIONING THE CON ACTOR MUST CLEAN THE COOLING
AND THE CONDENSER COILS, CHECK AND ADJUST IGERANT CHARGE TO ENSURE
PROPER UNIT FUNCTION, VERIFY THE EXISTING COND ISATE PIPING IS IN GOOD WORKING
CONDITION, AND MAKE NECESSARY REPAIR. CONTRAC R"-SHALL CHECK ALL ELECTRICAL
COMPONENTS, TIGHTEN ALL ELECTRICAL CONNECTION FOR PROPER OPERATION.
4- DETERIORATED DUCTWORK AND CEILING INSULATION ALL BE REPLACED. ALL EXISTING
r
DUCTWORK SHALL BE THOROUGHLY INSPECTED AND tEPAIRED REMOVED EQUIPMENT
THAT IS NOT BEING USED SHALL BE RETURNED TO THE OWNER.
5- ANY EQUIPMENT THAT WAS TEMPORARILY DISCONNECTED WITH RESPECT TO A REMOVAL
OF ANY OTHER DEVICE IT SHALL BE RECONNECTED TO THE EXISTING SYSTEM AND.
VERIFIED THAT IT IS FULLY OPERATIONAL.
6- CONTRACTOR SHALL VERIFY EXISTING AIR CONDITIONING AND HEATING- SYSTEMS FARE
FUNCTIONING PROPERLY, ITS PERFORMANCE RANGE 'WITH RESPECT ,TO ITS VOLUME
CAPACITY. SEAL:
7- EQUIPMENT THAT IS LOCATED EXTERIOR OF THE BUIIDING SHALL BE PROPERLY TIED
DOWN AND BE ABLE TO WITHSTAND A 140 MILESfH
r
SMOKE TEST READINESS IF AP jLICABTT--
1- BEFORE SCHEDULING SMOKE TEST CONTRACTOR IS I ,EIF ' AMIUAR--- NTH EXISTING
Q
BUILDING SMOKE EVACUATION SYSTEM BY COORDINATING %M_8U1MtNGMANAGER,-
VERIFY ALL MOTORIZED DAMPERS, SUPPLY AND EXHAUST FAN ARE FULLY OPERATED,
MAKE ALL NECESSARY REPAIR FOR THE TEST READINESS.