Loading...
10-699R-008„ __ - E co Q . A - - 9_ ® P I IN LEGEND VOLTAGE DROP CALCULATIONS VOLTAGE DROP CALCULATIONS - - -" - - COUNT SYMBOL DEVICE TYPE MODEL r . MAN ALT RE BOSCH FIRE ALARM CONTROL PANEL - - BOX MOUNTING IN CONDUIT _ _ _ - t�] z M - _ i, , ."� .. _. _ .. , .,, .,...,,., . - VD 2 X L X R X I OPERATING RANGE FOR DEVICES OHMS PER THOUSAND VD 2 X L X R X I OPERATING RANGE FOR DEVICES OHMS PER THOUSAND - W W J 1 FACP FIRE ALARM CONTROL• PANEL '"FPA- 0000 -UL SERIES , B08G.f•i<,....� -,. �.„ ... .. 1000 ARE BETWEEN 16VDC AND 33VDC 18 AWG 7.77 1000 ARE BETWEEN 16VDC AND 33VDC 18 AWG 7.77 4' SQUARE OX). (2-1/8- DEEP) BOX _ _ Q ' u, I%I t STANDBY ALARM 16 AWG 489 16 AWG 489 (OR 4' BOX). PROVIDE Q Q � a (n . n TOTAL STANDBY TOTAL ALARM ADEQUATE SUPPORT f ('� LL "� � a" 4 /s FIRE ALARM POWER SUPPLY AL802 -WAL SERIES BOSCR • 3 ' ; ' ` CURRENT CURRENT VD= VOLTAGE DRQP 14 AWG .3.07 VD= VOLTAGE, DROP 14 AWG 3 -07 Ul t DESCRIPTION QTY CURRENT PER QTY CURRENT FOR BOX IN CEILING FLEX Q� N ' PER UNIT PER UNIT L =ONE -WAY LENGTH OF 12 AWG 1 93 L =ONE -WAY LENGTH OF CIRCUIT 12 AWG '1.93 4" SQUARE � r N � AMPS ITEM (AMPS) AMPS (AMPS) R = CONDUCTOR RESISTANCE IN OHMS PER THOUSAND FEET 10 AWG 1 21 R = CONDUCTOR RESISTANCE IN OHMS PER THOUSAND FEET 10 AWG 1.27 (2 -1/8" DEEP) BOX 7 H Ii Q n C 50 M HORN / STROBE GEC SERIES GENTEX I (AMPS) (AMPS) I= LOAD CURRENT I= LOAD CURRENT Q Q ~, D =1J� . Q � HORN ! STROBE = _ CEILING ti j - 0 M a EPA- 1000 -UL MAIN BOARD 0.1250 x 1 0.1250 0.2400 x 1 fl.2400 �.. 5 WGEC SERIES GENTEX �, F • 0 WEATHERPROOF ; ,lc ,y W FAP -325 SERIES SMOKE DETECTOR 0.0004 x 40 = 0.0160 0.0080 x 40 = 0.3200 POWER SUPPLY #1 POWER SUPPLY #2 4' SQUARE BOX TO I % D N (n 1 O HORN! STROBE GCC SERIES GENTEX FAH325 SERIES HEAT DETECTOR 0.0004 x 11 = 0.0039 0.0080 X 11 = 0.0880 3-O ADAPTER RING I = Q ( � CEILING'MOUNT (QRNORINGiFNG 1, °j FAD -328 -R SERIES DUCT DETECTOR 0:0004- x 3 = ROD12 D.0080 x 3 - D.D24D STANDBY ALARM STANDBY ALARM t• - * D344 -RT REMOTE TEST STATION 0.0005 x 3 = 0.0015 0.0015 x 3 = 0.0045 TOTAL STANDBY TOTAL ALARM TOTAL STANDBY TOTAL ALARM BOX IS USED) t t PLUG - IN G ! . V 66 m STROBE ONLY GES SERIES GENTF�C CURRENT CURRENT CURRENT CURRENT _ F DESCRIPTION QTY CURRENT PER QTY CURRENT DESCRIPTION QTY CURRENT PER QTY CURRENT DETECTOR BASE ���� PER UNIT PER UNIT PER UNIT PER UNIT w - - - LL a III ., STROBE ONLY FMM325A SERIES PULL STATION 0.0003 x 9 = 0.0027 0,0040 x 9 = 0.0360 ITEM (AMPS) (AMPS) ITEM (AMPS) (AMPS) �✓ 3 � WGES SERIES GENTEX = _ (AMPS) (AMPS) (AMPS] (AMPS) NOTE: MIN PiPE FLEX 1/2° WEATHERPROOF D328A SERIES RELAY MODULE 0,0001 x 6 0.0006- 0.0050 x B 0.0300 FREE WIRE IN CEILING DETECTOR HEAD GEC -2475 0.0000 X 3 = 0.0000 0.1950 x 3 = 0.5850 AL802 -WAL 0 075 x 1 = 0 075 0 175 x 1 = 0.175 AL802 -WAL 0 075 x 1 = 0.075 0 175 x 1 = 0.175 40 O SMOKE DETECTOR FAP -325 SERIES BOSCH WGEC -2475 0.0000 x 4 = 0.0000 0.1950 x 4 = 0.7800 CIRCUIT #1 0809 x 1 = 0.809 CIRCUIT #1 0643 x 1 - 0.643 CIRCUIT 42 0 780 x 1 = 0 780 CIRCUIT 92 1 033 x 1 = 1 033 BOX MOUNTING IN LIFT OUT OR INTERLOCKING TYPE 11 � HEAT DETECTOR FAH -325 SERIES BOSCH WGES -2475 0.0000 X 3 = 0.0000 0.1120 X 3 = 0.3360 CIRCUIT #3 0 890 x t = 0 890 CIRCUIT #3 0 809 x 1 = 0.809 CEILINGS WITH SYSTEMS INSTALLED IN CONDUIT TOTAL SYSTEM 0.1508 TOTAL SYSTEM 2.4435 CIRCUIT #4 0892 x 1 = 0.892 CIRCUIT #4 0838 x 1 = 0.838 THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, STANDBY AMPS ALARM AMPS TOTAL SYSTEM TOTAL SYSTEM TOTAL SYSTEM TOTAL SYSTEM 3 DUCT DETECTOR FAD-R SERIES BOSCH (AMPS) (AMPS) STANDBY (AMPS) 0.075 ALARM (AMPS) 3.546 STANDBY (AMPS) 0 075 ALARM (AMPS) 3 498 AND IS NOT AN EXACT SPECIFICATION. REQUIRED OPERATION TIME FROM NFPA 72 4.4.1.5.2.2:(1) & 4.4.1.5.3.1 REQUIRED OPERATION TIME FROM NFPA 72 4 4 1 5.22 (1) & 4 4 1 5 3 1 REQUIRED OPE STANDBY TIME FROM NFPA 72 4 41 5 2 2 (1) & 4 41 5 3.1 3 RT REMOTE TEST STATION D344 -RT SERIES BOSCH STANDBY: 24 HOURS ALARM: 5 MINUTES X 1/60 = 0.084 HOURS STANDBY: 24 HOURS ALARM: 5 MINUTES X 1/60 = 0 084 HOURS STANDBY: 24 HOURS ALARM: 5 MINUTES X 1160 = 0 084 HOURS DETECTOR BASE S 9 Q MANUAL PULL STATION FMM -325.0 SERIES BOSCH TOTAL REQUIRED REQUIRED TOTAL REQUIRED REQUIRED NOTE; 3 CABLE ( REQUIRED REQUIRED REQUIRED REQUIRED TOTAL ALARM REQUIRED REQUIRED TOTALALARM REQUIRED REQUIRED TOTAL ALARM STANDBY STANDBY ALARM STANDBY STANDBY ALARM NOTE- S 6 R RELAY MODULE D328A SERIES BOSCH TOTAL STANDBY STANDBY ALARM STANDBY ALARM TIME CURRENT STANDBY ALARM TIME CURRENT (] Q STANDBY ALARM TIME CURRENT CURRENT CAPACITY CAPACITY CURRENT CAPACITY CAPACITY ( -) CURRENT AMPS CAPACITY CAPACITY TIME (HOURS) (HOURS) (AMPS) TIME (HOURS) (HOURS) (AMPS) FROM INTFC BOARD TO NEXT DEVICE (E) = EXISTING DEVICE (RE) = RELOCATE EXISTING i TIME (HOURS) ( ) (HOURS) (AMPS) (AMPS) (AMP HR) (AMP- HR) (AMPS) (AMP HR) (AMP HR) AT FACP + (WHERE APPLICABLE) 202 TOTAL DEVICES i - (AMP -HR) - (AMP -HR) _ _ _ _ (ER) = EXISTING TO BE REPLACED (N) =NEW DEVICE 24 X 0 075 1 800 0084 X 3 5.46 0 298_ 24 X 0 075 1 800 0084 X 3 498 0 294 -^ ^f ^ ^�^� t-`1 24 X 0.151 - 3.620 0.084 X 2.444 0.205 NOTE: i REQUIRED REQUIRED MINIMUM MINIMUM REQUIRED REQUIRED MINIMUM MINIMUM STANDBY ALARM REQUIRED DEBATING AMP /HOUR AMPIHOUR STANDBY ALARM REQUIRED AERATING AMP /HOUR AMP /HOUR 2( +) 1(- 2( +) 1{_ AMP/HOUR AMP/HOUR FIRE ALARM INSTALLATION $OPERATION NOTES REQUIRED REQUIRED MINIMUM MINIMUM PSI CAPACITY CAPACITY FACTOR BATTERY BATTERY PS2 CAPACITY CAPACITY FACTQR.t.2 BATTERY BATTERY 30 Q gp Q REQUIRED BATTERY BATTERY ' STANDBY ALARM DEBATING AMP /HOUR AMP /HOUR (AMP -HR) (AMP -HR) REQUIRED REQUIRED (AMP -HR) (AMP -HR) REQUIRED REQUIRED p mtTYP ❑ mtTYP Ift'10 1_5 AMP /HOUR LOOP ADDRESS LOOP ADDRESS FIRE ALARM SEQUENCE OF OPERATION: Pi CAPACITY CAPACITY FACTOR 1.2 BATTERY BATTERY 1 800 0298 = 2098 x 1.2 = 2.517 4.5 1.800 0294 = 2.094 X 1.2 = 2.513 4.5 �-- I-� ACTUATION OF ANY MANUAL PULL STATION, SMOKE DETECTOR, HEAT BATTERY � � Q'. (AMP -HR) (AMP -HR) REQUIRED REQUIRED DETECTOR OR WATER FLOW SWITCH SHALL CAUSE THE FOLLOWING TOTALS FOR CIRCUIT #t TOTALS FOR CIRCUIT #3 TOTALS FUt{ t:lt{f:Utf #1 tUTALS FUtt S:t1�t:UJt #3 t WIRING FOR ADB -FL BASE (STYLE 4) OPERATIONS TO OCCUR; 3.620 + 0.205 = 3.825 X 1.2 = 4.590 7 QTY NOTIFICATION TYPE AMPS TOTAL QTY NOTIFICATION TYPE AMPS TOTAL QTY NOTIFICATION TYPE AMPS TOTAL QTY NOTIFICATION TYPE AMPS TOTAL 3 GEG2475 (75cd) 0.195 0.585 1 GCC-2475 (75cd) 0 330 0 330 1 GEG2475 (75cd) 0 195 0.195 3 GEG2475 (75cd) 0 195 0 585 1. GENERAL ALARM ACTIVATION OF ALL.PROGRAMMED SIGNAL .61 ' T "- "`' ' w " 2 GES -2475 (75cd) 0 112 0 224 5 GES -2475 (75cd) 0 112 0 560 4 GES 2475 (75cd) 0 112 0 448 2 GES -2475 (75cd) 0 112 0 224 NOTE 1 DETECTOR (SLC LOOP) TO BE INSTALLED USING TWISTED FPL WIRE 'q' :� 0 0 000 0 000 0 0 DDO Dow 0 0 000 0 000 0 0 000 0.000 0 Q ON FLOOR OF INCIDENCE AND FLOOR ABOVE AND BELOW. NOTE 2: DO Nor LOOP WIRE TO PROVIDE TERMINALS 1 & 2. o - 0 000 0.000 0 - 0 000 0000 0 - 0.000 0.000 o - 0 000 0 000 IF MULTIPLE FLOORS ' ' m q> "" BREAK WIRE RUN TO PROVIDE SUPERVISION ( ) o 0 0DO 0.000 0 0 000 0 000 0 o.ow 0.000 0 0 000 0000 I * 0 - 0 000 0 000 D - 0 000 D 000 0 - 0,000 0.000 0 = 0.000 0 000 NOTE 3 R • " = ' ^ _• OBSERVEPOLARITY. DO NOTGROUND CONTROL WIRES O 2. LIGHT THE ASSOCIATED INDICATORS CORRESPONDING TO ` "" "' a - 0000 0550 a - 0IXi0 0000 a - alma aooa a - alma 0.000. �� SHIELDS. TIE SHIP LDS TOGETHER AT EACH DETECTOR. Q ACTIVE SIGNAL CIRCUITS. D 0000 0.000 0 0000 0.000 0 - - - - 0000 0000 0 - 0000 0000 SCOPE OF WORK 5 TOTAL AMPS' 0 809 6 TOTAL AMPS' 0 890 5 TOTAL AMPS. 0 643 5 TOTAL AMPS: 0.809 NOTE 4 SET THE ROTARY DIALS ON THE REAR OF THE DETECTOR HEAD TO 3. A GENERAL ALARM SHALL BE ANNUNICATED UPON ACTIVATION OF CORRESPOND TO THE LAST TWO DIGITS OF THE DEVICE LOOP ADDRESS. I- INSTALLATION OF A NEW BOSCH FIRE ALARM FACP, DIALER, TOTALS FOR CIRCUIT 92 TOTALS FOR CIRCUIT #4 TOTALS FOR CIRCUIT #2- TOTALS FOR CIRCUIT #4 REFER TO THE FLOOR PLANS FOR THE DETECTOR DEVICE ANY PULL STATION, FLOW SWITCH &DETECTION DEVICE. A TROUBLE �� POWER SUPPLIES, ELEVATOR RECALL, INITAITING &NOTIFICATION QTY NOTIFICATION TYPE AMPS TOTAL QTY NOTIFICATION TYPE AMPS TOTAL QTY NOTIFICATION TYPE AMPS TOTAL OTY NOTIFICATION TYPE AMPS TOTAL SIGNAL SHALL BE ANNUNCIATED UPON FAILURE OR REMOVAL OF A 4 GEG2475 (75cd) 0 195 0.780 4 GEG2475 (75cd) 0.195 0.780 3 GEG2475 (75cd) 0 195 0 585 2 GEG2475 (75cd) 0 195 0.390 NOTE 5. RECORD THE LOOP ADDRESS & DEVICE TYPE IN THE SPACES PROVIDED ON v DEVICES AS SHOWN ON PLANS. THE SCOPE OF WORK IS A 4 STORY Z I I DETECTION OR MANUAL DEVICE. A SUPERVISORY SIGNAL SHALL PS S I,,<" FiLL VOiD OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS 0 anon a000 1 GES -2475 (75cd) a112 0.112 4 GES -2475 (75cd) 0-112 0 -440. 4 GES -2475 (75cd) 0-112 0-448 , A., � ; BUtLDtNGfNCLUDtNG THE ROOF LEVEL AND HAS A TOTAL ANNUNCIATE ANY TAMPER, HVAC, OR DUCT DETECTOR ACTIVATION. LABORATORIES, INC.3 FOR USE IN THROUGH PENETRATION 0 - 0 000 0.000 0 - - 0 000 0.000 0 - 0 o0n 0 Ono 0 - 0 Om o 000 , f UL US FIRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FIRE AREA OF: 12,250 SQ. FT. THE NEW FACP IS AN ADDRESSABLE ADA HEIGHT REQUIRMENrs BOX MOUNTING REQUIRMENTS 0 0000 0.000 0 0000 0000- 0 0000 0000 0 0000 0000 4. IF MULTIPLE FLOORS, EACH ELEVATOR LOBBY, HOIST, AND MACHINE ® RESISTANCE DIRECTORY 5OL6,9OG9 INTELLIGENT SYSTEM. THE SYSTEM HAS A SLC DEVICE CAPACITY o - 0 000 0.000 0 - 0 000 0 000 0 - 0 000 0 000 0 0 000 0 000 1900 BOX M OF 127 DETECTORS AND MODULES. 0 - 0 000 0.000 0 0.000 0 000 0 - 0 000 0 000 0 - 0000 0 000 PROVIDE ADEQUATE SUPPORT ROOM SMOKE DETECTOR SHALL INITIATE AN ALARM CONDITION IN STROBE OR FOR BOX IN CEILING T. THE BUILDING AND RETURN ALL ELEVATORS TO THE PRIMARY OR 0 0.000 0 000 0 a000 0 000 0 0 -000 a000 D - 0 -000 0 -000 HORN/STROBE �i Z ' 11 - ALTERNATE FLOOR OF EGRESS IN COMPLIANCE WITH ANSI ASME .017.1. 2 4 1 2.THIS INSTALLATION WILL INCLUDE UTILIZATION OF NEW AND 0 - 0 000 0000 0 - 0000 0000 0 0 -000 0000 0 0000 0.000 0 EXISTING COMPATIBLE COMPONENTS 4 TOTAL AMPS 0.780 5 TOTAL AMPS: 0.892 7 TOTAL AMPS: 1.- - 6 TOTAL AMPS: 0 838 80" A.F.F. OR 0 r 6' BELOW CEILING E O co X 5. WATERFLOW SWITCH SHALL ACTIVATE GENERAL ALARM. '4 4 VOLTAGE DROP CALCULATIONS VOLTAGE DROP CALCULATIONS (WHICHEVER IS LOWER) A VALVE TAMPER SWITCH SHALL CAUSE A SYSTEM SUPERVISORY 3- THE MAXIMUM HEIGHT OF CEILING 9' -8 ". ' "'� '`t' WIRE RUN VOLTAGE WIRE RUN VOLTAGE 1 I ALARM INDICATION. .s.. • •+,.':':,_1 OHMS PER TOTAL POWER VOLTAGE OHMS PER TOTAL POWER VOLTAGE �; _= .. ' %.. t,.v:; 4. SEE BATTERY CALCULATIONS FOR MAXIMUM LENGTH PER CIRCUIT ONE WAY VOLTAGE READING ACCEPTABLE CIRCUIT ONE WAY VOLTAGE READING ACCEPTABLE r WIRE SIZE CIRCUIT SUPPLY DROP AT WIRE SIZE CIRCUIT SUPPLY DROP AT T�,i }. +: { L _ °'g .f.. NUMBER (FEES. DROP AT LAST VOLTAGE DROP NUMBER (FEET) DROP AT LAST VOLTAGE DROP I I CEILING NOTIFICATION CIRCUIT. DRAW VOLTAGE END DRAW VOLTAGE END 6. ANNUNCIATION OF THE ACTIVE DEVICE AT THE FIRE ALARM CONTROL .: ?, -- °'. �=-;: (W-C -s.) DEVICE (W C S) DEVICE Q, ,••. ) ^;j r „ -; �;•;r OHMS AWG OHMS AWG PANEL AND ANY ANNUCIATORS, IN MONITORED BUILDING, SEND A ' °i CIRCUIT 112 307 14 0809 0559 20.4 1984 3%. YES CIRCUIT 131 307 14 0.643 0517 20.4 19.88 3 °/. YES ' `='CX +.':•. 5. THIS BUILDING DOES NOT HAVE A SPRINKLER SYSTEM. O SIGNAL TO THE U.L. MONITORING CENTER FOR ALARM, TROUBLE, �''�'� i �•, �• � •� r`.::.� + CIRCUIT #2 144 3.07 14 0.780 0 690 20.4 19.71 3% YES CIRCUIT #2 119 3 07 14 1.033 0 755 20 4 19 65 4% YES 1 1 _ - ;._t' , ; -- + ,; :r•..vs•• PLUG -IN WATERFLOW AND SUPERVISORY CONDITIONS. ` k'�' �' - clRCUrr #3 98 307 14 0890 0536 204 1986 3 °Jo YES CIRCUIT #3 102 307 14 0809 0507 204 1989 2% YES i i DET €CTORBASE A 3 �� s ' F. FILL VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS CIRCUIT #4 162 3.07 14 0 892 0.887 20.4 1951 -4 %. YES CIRCUIT #4 76 3.07 14 0.838 D.391 20 4 20.01 2% YES FIRE ALARM SPECIFICATIONS: 2 - LABORATORIES, INC.® FOR USE IN THROUGH - PENETRATION (W -C S.) = WORST CASE SCENARIO (W C S.) = WORST CASE SCENARIO ALL EQUIPMENT TO BE U.L. LISTED FOR FIRE SERVICE AND SHALL BE SECTION L US FIRESTOP SYSTEMS (XHEZ). SEE CURRENT UL FIRE ® RESISTANCE- DIRECTORY 50L6,90G9 " #, E' ALARM SYSTEM STEM TO p� - DETECTOR HEAD COMPATIBLE WITH THE SYSTEM BEING USED. SYSTEM IS TO BE POWER A -A - J, 0. -. ' `� J7 N LIMITED. - F IC1 r a t-5 \:9 6�y L�r� ]NSTA =D IN AC'C01RDANC-11- baTV PULL STATION System No. C -AJ -1044 � ,� O E r NI IAi��i -DAD � ,, CO i. e N 9 °11' F I R L: DEPARTMENT NFPA 7t-; 70; 101 148"A.F.F. 0 BIG MOUNTING IN SHEET ROCK OR PLASTER TYPE CEILINGS SYSTEM TO BE CENTRAL STATION SERVICE AS PER NFPA -72. June 15, . 2005 (Se to GLDG PER "vIlT FIRE 0.L;,itfrl o (MUST BE INSTALLED WITH CONDUIT) F Ratings -2 3, and AHr_(Seei[ems2A and 4)P-' qgy ``B FIRE SUPPRESSION lJJATEl7i'9���I`dE,:T. THIS DIAGRAM IS FOR REPRESENTATIVE PURPOSES ONLY, T Rating - 0 Hr. iB � AND IS NOT AN EXACT SPECIFICATION. FIRE ALARM PANEL SHALL BE LISTED FOR CENTRAL STATION SERVICE PER L Rating at Ambient - 2 CFMlsq. ft. A t� F IRE ALARM SHALL BE A CENTRAL NFPA 72, 2002, SECTION 5-2, UNLESS OTHERWISE SPECIFIED. L Rating at 400 F - less than 1 CFMlsq. ft. DAi%; ,-2 • ?fllfl �1f: STATION SERVICE. A CERTIFICATE NOT TO SCALE NOT TO SCALE W Rating - Class l (iPa, item 4) 3 2 OR PLACARD SHALL BE POSTED AT THE FIRE ALARM PANEL MUST HAVE AN EARTH GROUND CONNECTION AS REQUIRED BY THE SYSTEM MANUFACTURER AND ARTICLE 760 OF THE 1. Floor or Wall Assembly NATIONAL ELECTRICAL CODE- MINIMUM WIRE SIZE IS 12 AWG FOR GROUND Lightweight or normal weight (100 -150 pcf or 1600 -2400 kg1m3) concrete. Except as VOLTAGE DROP CALCULATIONS VOLTAGE DROP CALCULATIONS noted in table under Item 4, min thickness of solid concrete floor or wall assembly is _ A 1c h CONNECTION, (NOTE: PANEL NEUTRAL OR CONDUIT 4 -112 in. (I 14 mm). Floor may also be constructed of any min 6 in. (152 mm) thick UL VD = 2 X L X R X I OPERATING RANGE FOR DEVICES OHMS PER THOUSAND VD = 2 X L X R X I OPERATING RANGE FOR DEVICES OHMS PER THOUSAND GROUND IS NOT ACCEPTABLE). Classified hollow core Precast Concrete Units *. When floor is constructed of hollow VOLTAGE DROP CALCULATIONS V core precast concrete units, packing material (Item 3) and caulk fill material (Item 4) to 1000 ARE BETWEEN 16VDC AND 33VDC 18 AWG 7.77 1000 ARE BETWEEN 16VDC AND 33VDC 18 AWG 7 77 LLI ALL STROBE LIGHTS SHALL ACTIVATE UPON INITIATION OF THE GENERAL be installed symmetrically on both sides of floor, flush with floor surface. Wall assembly 16 AWG 4 89 16 AWG 4.89 VD = 2 X L X RX I OPERATING RANGE FOR DEVICES OHMS PER THOUSAND 0 VD = VOLTAGE DROP 14 AWG 307 VD = VOLTAGE DROP 14 AWG 3.07 1000 ARE BETWEEN 16VDCAND 33VDC 18 AWG 7.77 Q ALARM AND SHALL BE SYNCHRONIZED IN OPEN AREAS. ALL AUDIBLE may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is SECTION L - ONE -WAY LENGTH OF CIRCUIT 12 AWG 193 L = ONE-WAY LENGTH OF CIRCUIT 12 AWG 1.93 16 AWG 489 W In solid lightweight or normal weight concrete. Floor Is 32 In. (813 mm). Max diam of R = CONDUCTOR RESISTANCE IN OHMS PER THOUSAND FEET 10 AWG 1 21 R = CONDUCTOR RESISTANCE IN OHMS PER THOUSAND FEET 10 AWG 1.21 IZ SIGNALS SHALL HAVE THREE PULSE TEMPORAL PATTERN AND SOUND A -A VD= VOLTAGE DROP 14AWG 3 07 LEVEL SHALL BE AT LEAST 15 DBA ABOVE AMBIENT SOUND LEVEL AND opening in floor constructed of hollow -core precast concrete units is 7 in. (178 mm). See I= LOAD CURRENT I = LOAD CURRENT L = ONE -WAY LENGTH OF CIRCUIT 12 AWG 1.93 Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire R = CONDUCTOR RESISTANCE IN OHMS PER THOUSAND FEET 10 AWG 1.21 HAVING A DURATION OF AT LEAST 60 SECONDS MEASURED 5 FT ABOVE Resistance Directory for dames of manufacturers. system No. W- L-3001 - - ca THE FLOOR IN OCCUPIED AREAS. September 07, 2004 1= LOAD CURRENT REVISIONS: � 1A. Steel Sleeve (Optional, not shown) - Max 15 in. (381 mm) ID (or smaller) Schedule FRatings - 1 and 2 Hr. (See items 1) POWER SUPPLY #3 POWER SUPPLY #4 � j FIRE ALARM CIRCUITS AND DEVICES SHALL BE CLASS "B ". 10 (or heavier) steel sleeve east or grouted Into floor or wall assembly. Sleeve may T Rating - 3/4, 1, 1 -112 and 2 Hr. (See item 2) PER CITY COMMENTS Z extend a max of 2 In. (51 mm) above top of floor or beyond either surface of wall-Max L Rating at ambient --15 CFMlsq. ft. (See item 3) STANDBY ALARM STANDBY ALARM POWER SUPPLY #5• 1 Q 16 in. (406 mm) ID (or smaller) min 0.028 (0.71 mm) wall thickness (or heavier) TOTAL STANDBY TOTAL ALARM TOTAL STANDBY TOTAL ALARM D.L. (07112110) E ALL WIRING AND CONDUIT TO CONFORM TO N.F.P.A. AND N.E.C. 760. L Rating at 400 F -less than 1 CFMlsq. ft. (See item 3) CURRENT CURRENT CURRENT CURRENT DESCRIPTION QTY CURRENT PER QTY CURRENT DESCRIPTION QTY CURRENT PER QTY CURRENT galvanized steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a PER UNIT PER UNIT PER UNIT PER UNIT STANDBY ALARM PER AS- BUILTS co (AMPS) ITEM (AMPS) (AMPS) (AMPS) {AMPS) ITEM (AMPS) (AMPS) (AMPS) CURRENT TOTAL STANDBY CURRENT TOTAL ALARM m max of 1/2 in. (13 mm) beyond either surface of floor or watt. 1. Wail Assembty " The t or 2 hr fire -rated gypsumwaMoardlstud wall assembly shag ( DESCRIPTION QTY CURREVTPER QTY CURRENT- 2 D.L. 08/18/10 .- CONNECTIONS TO LIGHTS AND POWER SERVICE SHALL BE ON A be constructed of the materials and in the manner described in the individual U300 or PER UNIT ITEM (AMPS) PER UNIT (AMPS) ( ) 2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall AL802 -WAL 0 075 x 1 = 0 075 0.175 x 1 = 0.175 AL802 -WAL 0 075 x 1 = 0 075 0.175 x 1 = 0 175 CD CD DEDICATED BRANCH CIRCUIT. THE CIRCUIT AND CONNECTIONS SHALL BE (AMPS) (AMPS) ) rn CIRCUIT #1 1.033 x 1 = 1 033 CIRCUIT #1 0.726 x 1 = 0 726 MECHANICALLY PROTECTED. THE CIRCUIT DISCONNECTING MEANS SHALL concentrically or eccentrically within the firestop system. Max annular space between include the following construction features: AL802 -WAL 0 075 x 1 = 0.075 0175 x 1 = D 175 ' HAVE A RED MARKING AND BE ACCESSIBLE ONLY TO AUTHORIZED pipe, conduit or tubing and edge of through opening or sleeve is dependent on the CIRCUIT #2 1 033 x 1 = 1.033 CIRCUIT #2 0.867 x 1 = 0 867 CIRCUIT#3 1728 x 1 = 1.228 CIRCUIT #3 1311 x 1 = 1311 CIRCUIT #1 0672 x 1 - 0672 �p PERSONNEL AND BE PER N.F.P.A. 72 2002 EDITION parameters shown in Item 4. Min annular space between pipe or conduit arui edge of A. Studs -Wall framing may consist of either wood studs m sleet channel studs. Wood _ _ CIRCUIT #2 0 809 x 1 = 0.809 r through opening is 0 in. (0 mm) (point contact). Pipe conduit or tubing to be rigidly studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC with nom 2 by 4 in. lumber CIRCUIT #4 0.726 x 1 = 0.726 CIRCUIT #4 1 033 x 1 - 1 033 M TOTAL SYSTEM TOTAL SYSTEM TOTAL SYSTEM TOTAL SYSTEM CIRCUIT #3 0 950 x 1 = 0.950 0 supported on both sides of floor or wall assembly. The following types and sizes of end plates and cross braces. Steel studs to be min 33/8 in. wide by 13/8 in. deep 0.075 4 -195 0.075 4.112 SPARE 0000 x D = 0 000 LL THE FIRE ALARM PANEL IS PROVIDED WITH STANDBY BATTERY PER N.F.P.A. metallic pipes, conduits or tubing may be used: channels spaced max 24 InOC STANDBY AMPS ALARM AMPS STANDBY (AMPS) ALARM AMPS TOTAL SYSTEM TOTAL SYSTEM ^ 72 WITH 24 HOURS OF STANDBY AND 5 MINUTES OF ALARM (AS REQUIRED). REQUIRED OPERATION TIME FROM NFPA 72 4 -4.1.5 2.2.(1) & 4 -4 1 -5 31 REQUIRED OPERATION TIME FROM NFPA 724 4.1.5 2,2.(1) & 4.4 1.53 1 STANDBY AMPS 0.075 ALARM AMPS 2.606 CD SHOULD LOSS OF NORMAL 120VAC POWER OCCUR, FIRE ALARM PANEL A. Steel Pipe - Nom 30 in. (762 mm) diam (or smaller) Schedule 10 B. Gypsum Board* - Nom 1/2 or 5/8 in. thick, 4 ft wide with square or tapered edges. REQUIRED OPERATION TIME FROM NFPA 72 4.4.1.5.2 2.(1) & 4.4.1.5 -3.1 06 WILL AUTOMATICALLY TRANSFER TO BATTERY. (or heavier) steel pipe. The gypsum wallboard type, thickness, number of layers and sheet orientation shall be STANDBY: 24 HOURS ALARM: 5 MINUTES X 1/60 = 0.084 HOURS STANDBY: 24 HOURS ALARM. 5 MINUTES X 1/60 = 0.084 HOURS B. Iron Pipe - Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe. as specified in the individual Wall or Partition Design_ Diam of circular through opening TOTAL REQUIRED REQUIRED TOTAL REQUIRED REQUIRED STANDBY: 24 HOURS ALARM: 5 MINUTES X 1/60 - 0.084 HOURS REQUIRED REQUIRED TOTAL ALARM REQUIRED REQUIRED TOTAL ALARM O A CERTIFICATE OF COMPLETION WILL BE PREPARED AND A COPY C. Conduit - Nom 6 in- (I 52 mm) diam (or smaller) rigid steel conduit- to be 31B in_ to 518 in- largo[ than outsidadiarnof cable or cable bundle. STANDBY STANDBY ALARM STANDBY STANDBY ALARM STANDBY ALARM TiME CURRENT STANDBY ALARM TIME CURRENT TOTAL REQUIRED REQUIRED �y D. Conduit - Nom 4 in. (102 mm) diam (or smaller) steel electrical metallietubing. CURRENT CAPACITY CAPACITY CURRENT CAPACITY CAPACITY REQUIRED REQUIRED TOTAL ALARM PROVIDED TO THE OWNER AND THE CITY FIRE RESCUE DEPARTMENT. E. Copper - Tubing Nom 6 in. (11 52 mm) diam (or smatter) Type L C. Fasteners - When wood stud framing is employed gypsum wallboard layers attached TIME (HOURS) (AMPS) (AMP -HR) (HOURS) (AMPS) (AMP -HR) TIME (HOURS) (AMPS) (AMP -HR) (HOURS) (AMPS) (AMP -HR) STANDBY STANDBY STANDBY ALARM TIME CURRENT ALARM C CURRENT CAPACITY CAPACITY 2 (or heavier) copper tube, to studs with cement coated nails as specified in the individual Wall or Partition Design TIME (HOURS) (HOURS) (AMPS) -LA OWNER MANUALS ,iNSTALLATIONiNSTRUCTiONS ,OPERATION 24 X 0075 = t800 0084 X 4195 = 0352 24 x 0.075 = T8tx7 0084 X 4117 = 0345 (AMPS) (AMP-HR) (AMP FIR) F. Copper Pipe -Nom 6 in. (152 mm) diam (or smaller) Regular When steel channel stud framing is smplgyed, gypsum wallboard attached tq studs, with INSTRUCTIONS AND RECORD DRAWINGS SHALL BEAT THE SITE ON (or heavier) copper pipe. Type S self - drilling, self - tapping bugle -head steel screws as specified in the Individual 20. _ X o 075 = 1 soo D 084 . X 2 606 = o.2t9 M COMPLETION OF JOB AND FINAL ACCEPTANCE. Wall or Partition Design. REQUIRED REQUIRED MINIMUM MINIMUM REQUIRED REQUIRED MINIMUM MINIMUM REQUIRED REQUIRED E 3. Packing Material - Polyethylene backer rod or nom 1 in. (25 mm) thickness of STANDBY ALARM DEBATING AMP /HOUR AMP/HOUR STANDBY ALARM DEBATING AMPMOUR AMPiHOUR REQUIRED REQUIRF� MINIMUM MINIMUM tightly-packed mineral wool batt or lass fiber insulation firm packed Into opening as a The hourly F Rating of the, flresto AMP /HOUR AMP /HOUR W INSTALLATION NOTES: 9 firmly P p 9 h , p system is equal to the hourly fire rat' of the, wall CAPACITY CAPACITY FACTOR 1.2 BATTERY BATTERY CAPACITY CAPACITY FACTOR 1.2 BATTERY BATTERY REQUIRED n ' PS3 BATTERY PS4 BATTERY STANDBY ALARM DEBATING AMP /HOUR AMPIHOUR Q permanent form. Packing material to be recessed from to surface of floor or from both assembt in which it Is Installed. (AMP -HR) (AMP -HR) REQUIRED REQUIRED (AMP -HR) (AMP-HR) REQUIRED REQUIRED AMPIHOUR ALL FIRE STOP PENETRATIONS SHALL BE MADE WITH APPROVED N.E.C. P g p Y � PS5 CAPACITY CAPACITY FACTOR 1.2 BATTERY BATTERY �, surfaces of wall as required to accommodate the required thickness of caulk fill material BATTERY ELECTRICAL TUBING AND SHALL BE SEALED WITH U.L. APPROVE FIRE STOP 1 800 + 0.352 = 2 152 x 1 2 = 2.593 4 5 1 aoo + 0.345 = 2.145 X 1 2 = 2.574 4.5 (AMP -HR) (AMP HR) REQUIRED REQUIRED LL (Item 4). 2. Cables - Individual cable or max 1 in. diam cable bundle installed in through opening MATERIAL. with an annular space of min 0 In. (point contact) to max 3141n. Cable to be rigidly 1 800 + 0 219 = 2019 x 12 = 2 423 45 CD 4. Fili,Void or Cavity Material* - Caulk or Sealant - Applied to fill the annular space flush supported on both sides of wall assembly. The following types and sizes of cables may TOTALS FOR CIRCUIT #1 TOTALS FOR CIRCUIT #3 TOTALS FOR CIRCUIT #1 TOTALS FOR CIRCUIT #3 .- QTY NOTIFICATION TYPE AMPS TOTAL QTY NOTIFICATION TYPE AMPS TOTAL QTY NOTIFICATION TYPE AMPS TOTAL QTY NOTIFICATION TYPE AMPS TOTAL TOTALS FOR CIRCUIT #1 TOTALS FOR CIRCUIT #3 COLOR CODING MAY NOT APPLY TO EXISTING WIRE. with top surface of floor. In wall assemblies, required caulk thickness to be Installed be used: 3 GEG2475 (75cd) 0 195 0.585 4 GEG2475 (75cd) 0.195 0.780 2 GEG2475 (75cd) 0.195 0 390 5 GEG2475 (75cd) 0.195 0.975 QTY NOTIFICATION TYPE AMPS TOTAL QTY NOTIFICATION TYPE AMPS TOTAL IRE TO BE LABELED ACCORDINGLY. symmetrically on both sides of wall, flush with wall surface. At point contact location m 4 GES 2475 Toad) 0. 112 0.448 4 GEfi 2475 (75cd) x112 x448 3 GES 2475 (75cd) 0.112 x336 3 GE S-2475 (75cd) x112 x336 6 GES 2475 5cd 0.112 0.672 2 GEG2475 5cd D_i95 0.390 between penetrant and sleeve or between penetrant floor t mink s f mm) A. Max ula pair d c AWG copper conductor telephone cable neca le is used, 0 - 0000 0000 0 - 0.000 0000 a - 0000 0000 0 - 0000 0000 0 0DOG UODD 5 GES -2475 (75cd) 0.112 0.560 LICENSED ENGINEER: Q CONDUIT SHALL BE A MINIMUM OF 1/2" AND 40% FILL MAXIMUM. diam bead ofcaulk shall be applied at top surfaces offlnor and at troth surfaces of wall. PVC insulation and jacket materials. When max 25 pair telephone cable is used, D 0000 D DOD o 0 o0D O.oOD D 0.000 0 000 [) 0 DOD O.ODO 0 0.000 0.000 0 0.000 0 000 0) The hourly F Ratings and the min required caulk thicknesses are dependent upon a 0 0.000 0 000 0 - 0 000 0 000 0 - 0.000 0.000 0 - 0 000 0 000 0 - 0 000 0.000 0 - 0 000 0 000 SHANTI LAL C. PATEL to number of parameters, as shown in the following table: T Rating is 2 hr.When 50 to 150 pair telephone cable is used in 1 hr fire rated wall, rt TWO TELEPHONE LINES SHALL BE PROVIDED TO THE FIRE-CONTROL o 0.000 0.000 0 - (1000 0.000 0 0.000 0.000 0 0.000 0.000 0 - 0.000 0000 0 - D.DDD 0.000 004 327 -0475 M T Rating is 3!4 hcWhen 50 to 150 pair telephone cable is used in 2 hr fire rated watt - - _ _ - 0 - 0 ODO O.DOO 0 - 0 000 0_000 C� Mm. Floor or Wall Nom. Po Tufaaor Max Annular Mm. CauUc F Rat D 0.000 Q.oQO 0 0.000 0000 - 0 4000 0 -000 Q O.QQD q.lm0 COMMUNICATOR. "g T Rating is 1 hr. Thkns In. (mm) Conduit Dlam in. (mm) Space in. (mm) Thkns in. (mm) Hour 0 0000 0.000 0 0.000 0.000 0 0 000 0 000 0 0.000 0.000 0 0.000 0000 0 0000 0.000 P.E. 002�i5€ ' =18'r C3 2 -1/2 (64) 1/2 -12 (13305) 1 -318 (35) 112 (13) 2 7 TOTAL AMPS 1.033 8 TOTAL AMPS 1.228 5 TOTAL AMPS: 0.726 8 TOTAL AMPS: 1.311 0 0.000 0000 0 0000 0.000 FIRPs!�, �ft�N . ♦o In ALL FLOW, TAMPER, PIV AND BACKFLOW WILL HAVE MONITOR MODULES; B. Max No. 10 AWG multiple copper conductor Type NM ("Romex ") nonmetallic 6 TOTAL AMPS o 672 7 TOTAL AMPS: 0 950 ♦ 'l . ­_ 0 ♦ U •.... 0 ♦ 112 -12 13- 305 3-1/4 83 . 0) FIRE PROTECTION SPRINKLER PUMP MONITORING. 3 POINTS 2-1/2(64) ( ) _ (, -) t (zSl 2 sheathed cable with PVC insulation and jacketmaterials. When Type NM cable is used, � rr5 . ( ) TOTALS FOR CIRCUIT #2 TOTALS FOR CIRCUIT #4 TOTALS FOR CIRCUIT #2 TOTALS FOR CIRCUIT #4 % �J . • y ♦ Q 4 -112 (tt4) 1/2-6(13-152) 1318 (35) 1la (6) (a) z max T Rating is 1 -1/Z hr. TOTALS FOR CIRCUIT #2 TOTALS FOR CIRCUIT #4 e . . e (A).FIRE PUMP RUN (B).FIRE PUMP FAIL (C).FIRE PUMP PHASE REVERSAL. QTY NOTIFICATION TYPE AMPS TOTAL QTY NOTIFICATION TYPE AMPS TOTAL QTY NOTIFICATION TYPE AMPS TOTAL QTY NOTIFICATION TYPE AMPS TOTAL Q -7 d 4-1/2(114) 1/2-12(13-305) 1-1/4(32) 1/2(13) 2 3 GEG2475 (75cd) 0 195 0.585 2 GEG2475 (75cd) 0 195 0 390 1 GEG2475 (75cd) 0 195 0 195 3 GEG2475 (75cd) 0.195 0585 QTY NOTIFICATION TYPE AMPS TOTAL QTY NOTIFICATION TYPE AMPS TOTAL + O y Z Z C. Multiple fiber optical communication cable jacketed with PVC and having a max 3 GEG2475 (75cd) 0 195 0 585 0 - 0 000 0 000 .. O •. r of ROUTING OF THE FIRE ALARM SYSTEM CONDUIT IS DIAGRAMMATIC. VERIFY 4-1/2(114) 112 -20 (13 -508) 2 (51) 1 (251 2 4 GES -2475 75cd 0 112 0 448 3 GES -2475 75cd 0 112 0 336 6 GES -2475 (75cd) 0.112 0 672 4 GES -2475 (75cd) 0.112 0 448 • �_ outside diam of 518 in. When fiber optic cable Is used, max T Rating Is 2 hr. 2 GES -2475 5c 0112 0 224 D 0 000 0 000 Zr . _ m r a? D 0 000 0 000 0 0 000 0 000 0 0 000 0 000 0 0 000 0 000 EXACT LOCATIONS OF DEVICES AND WIRE ROUTING PRIOR TO STARTING a -v2 (114) u2-20_ (13.5Oa) 2 (51) 1(25) 2 - 0 0.00.0 0000 o Dow 0000 0 -- 0.000 0000 0 - 0.000 0.000 0 - 0000 0000 0 -- 0000 0.000 . ; o `�= WORK. 4-1/2(114) 1/2-12(13-305) 3-114(83) 1 (25) 2 D. Max 12 AWG multi conductor (max seven conductors) power /control cable with 0 0 -000 0 000 0 - 0 -000 0 000 .0 0 - 0.000 0 000 0 - 0.000 0.000 0 - 0 000 0 000 0 - 0 000 0.000 0 . f�• r N 4 -1/2 (110.) 22 -30 (558 762) 2 (51) 1/2 (51) 2 cross linked polyethylene (XLPE) insulation and XLPE or PVC jacket materials. When 0 0000 0000 0 0000 0.000 0 0 000 0 000 0 0000 0.000 0 0 -000 0000 0 0 -000 0 -000 y • � e multi conductor power /control cable Is used, max T Rati is 2 hr, 0 0 -000 0000 0 0 -000 0000 ,. . • v . t� ; c MOUNTING REQUIREMENTS: 5-1/2 140 1/2 -s 13-152 1 -3/a 35 1 z5 b 2 ng - 0 0000 0000 0 000.0 0000 0 - 0000 000.0 0 0000 O.000 O ( 1 ( 1 t) t t 0 0 000 0.000 a - o o0n o 000 ♦ . W % MANUAL PULL STATIONS TO REINSTALLED AT48" A.F.F. o - 0000 ODDO o - ODOD 0.000 0 - D .000 0 -000 0 - D.ODo 0.000 (a)Min 2 in. (51 mm) thickness of mineral wool batt insulation required in annular space. E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SER cables with 0 0 000 0 000 0 0.000 0 000 �ti t.,t b Min 1 in. 25 mm thickness of mineral wool ball insulation required in annular space 7 TOTAL AMPS: 1.033 5 TOTAL AMPS: 0.726 7 TOTAL AMPS. 0 867 7 TOTAL AMPS: 1 033 () ( ) p polyvinyl chloride Insulation and jacket materials. 5 TOTAL AMPS 0 809 0 TOTAL AMPS: 0000 ♦�4 S�� CD MOUNT FIRE ALARM SYSTEM STROBES & HORN/ STROBES AT 80" A.F.F. on both sides of floor or wall assembly_ Min 1 in. (25 mm) thickness of caulk to be 4011! # # I t t t t1 CD FROM BOTTOM OF DEVICE OR 6" BELOW CEILING. installed flush with each surface of floor or wall assembly. 3. Filk,Void or Cavity Materials* - Caulk, Sealant or Putty - Caulk or putty fill material VOLTAGE DROP CALCULATIONS VOLTAGE DROP CALCULATIONS VOLTAGE DROP CALCULATIONS r�1 (WHICH EVER IS LOWER) Installed to completely fill annular space between cable and gypsum wallboard on both WIRE RUN OHMS PER TOTAL POWER VOLTAGE VOLTAGE WIRE RUN OHMS PER TOTAL POWER VOLTAGE VOLTAGE WIRE RUN VOLTAGE PROJECT NUMBER: 3M COMPANY - CP 25WB+ caulk or FB3000 WT sealant. Note: W Ratio applies sides of wall and with a min 1/4 in. diam bead of caulk or u applied to perimeter of CIRCUIT ONE WAY VOLTAGE READING ACCEPTABLE CIRCUIT ONE WAY VOLTAGE READING ACCEPTABLE OHMS PER TOTAL POWER VOLTAGE ( g PP putty PP �' WIRE S� CIRCUIT SUPPLY DROP AT WIRE S� CIRCUIT SUPPLY DROP AT CIRCUIT ONE WAY VOLTAGE READING ACCEPTABLE F -09101 on when FB -3000 WT sealant is used. cables at its egress from each side of the wall. NUMBER (FEET) DROP AT LAST VOLTAGE DROP NUMBER (FEET) DROP AT LAST VOLTAGE DROP WIRE S� CIRCUIT SUPPLY DROP AT SMOKE DETECTOR SHALL NOT BE LOCATED WITHIN 3' OF N ) () 9 DRAW VOLTAGE END DRAW VOLTAGE END NUMBER (FEET) DRAW DROP VOLTAGE AT LAST END VOLTAGE DROP (W C.S) DEVICE (W.0 S.) DEVICE C 8 DEVICE SUPPLY AIR OUTLETS. * OHMS AWG OHMS AWG ) OHMS AWG DATE: SCALE: Bearing the UL Classification Marking 3M COMPANY - MP+ Sttx putty, CP 28W6+ caulk, caulk or WT sealant or Cable Wrap CIRCUIT #1 144 3.07 14 1.033 0.913 20.4 1949 4% YES CIRCUIT #1 67 307 14 0.726 0.299 204 2010 1% YES CIRCUIT #1 104 307 14 0 672 0 429 20.4 19.97 2% YES o putty (Note: L Ratings apply only when CP 25WB+ caulk or F83000 WT sealant is CIRCUIT #2 156 3.07 14 1.033 0 989 20.4 19 41 5% YES CIRCUIT #2 143 3 07 14 0.867 0.761 20 4 19.64 4 °A YES CIRCUIT #2 111 307 14 0 809 0551 20.4 19.85 3% YES .I SMOKE DETECTORS TO BE INSTALLED AS PER N.F.P.A. 72. WALL MOUNTED *NOTE used.) 11 /18/09 N.T.S. SMOKE DETECTORS SHALL BE MOUNTED 4" MINIMUM FROM CEILING WITH CIRCUIT #3 its 3 07 t4 t ZZa 00.97 20 a 7950 4 °% YES CiRCUiT#3 757 3 07' 14 t 311 1 264 204 i9 14 6°k YES CIRCUIT #3 137 3.07 14 0.950 11799 20.4 19.60 4% YES cw This material was extracted by 3M fire protection products from 2004 edition of the CIRCUIT #4 114 3.07 14 0.726 0 506 20.4 1989 2% YES CIRCUIT #4 179 307 14 1.033 1.135 204 19.26 8% YES SPARE D 307 14 0.000 0 000 20.4 20.40 a% NOT USED DRAWN BY: CHECKED BY: Cn 12" MAXIMUM FROM CEILING. UL fire resistance directory. *Bearing the UL Classification Mark (W C S.) = WORST CASE SCENARIO (W.C.S) = WORST CASE SCENARIO (W C S) = WORST CASE SCENARIO O D.L. B.P. a NOTES, RISER & DETAILS - FIRE ALARM PLAN 7 OF 7 0 SCALE: N.T.S