14-516-006GENERAL ELECTRICAL NOTES: 1. All work shall be in accordance with the Local Building code, N.E.C. and other applicable codes and standards. 2. The contractor is responsible for evaluating field conditions by visiting the site prior to commencing/bidding work. 3, The contractor shall satisfactorily repair /replace equipment or part of structure damaged as a result of his work. Surfaces and finished areas shall be restored to match adjacent areas. 4. All material removed shall be disposed of as directed by owner. 5. All wiring indicating existing is based on original contract documents and is to be verified by contractor at job site. 6. All conductors shall be copper except as noted, all conductors shall be run in conduit. 7. All materials shall be U.L. approved. 8. New typewritten panel tally shall be furnished after job is completed reflecting all changes and additions. 9. All branch circuits shall be properly phase balanced. 10. Contractor shall sea] all openings with a fire seat similar to 'OZ' flamesecl. 11. Fuses shall be dual element, time delay type unless otherwise noted. 12. Risers are diagrammatic only. They do not show every bend required for installation. 13. This drawing is a guide for the installation of electrical service. The electrical contractor is responsible in providing a functional system. 14. All cables shall be run without splices except otherwise indicated. 15. All pull and junction boxes shall be accessible at all times. 16. Exact point and methods of connection shall be determined in field, 17. All work shall be done in a neat and workmanlike manner. 18. All raceway routed. Insulated conductors system shall be color coded as follows: 120/208V. SYSTEM 277/480V SYSTEM PHASE 'A' BLACK PURPLE PHASE 'B' RED BROWN PHASE 'C' BLUE YELLOW NEUTRAL WHITE GRAY GROUND GREEN GREEN 19. All underground conduit runs to have a minimum 24" cover. 20. All exterior electrical equipment shall be weather proof or shall be in a weather proof enclosure. 21. All trenching, backfilling, settings of post lights, and concrete bases for post lights shall be done by electrical contractor. 22. All outside lighting shall be installed in conduits and provide pull boxes as required. 23. Pole lighting shall be as shown and capable to withstand winds of up to 120 miles/hr. and designed to support three lighting fixtures maximum, see plans. Poles shall comply with N.E.C. section 410-15. 24. All underground "PVC" shall be provided with galvanized rigid elbows and adapters as required inside building. 25. Conduit running under paving shall be 24 inches bellow finished grade, minimum. 26. Coordinate all telephone work with local phone company engineer prior start of construction, notify contract engineer of any discrepancies encountered. 27. Coordinate all power utility work with local power company engineer and notify contract engineer of any discrepancies encountered. NOTE. THIS AREA SHALL CONPLY W1 2008 N.E.C. ALL RECEPTACLES OTHER THAN GFI RECEPTACLES SHALL HAVE ARC FAULT PROTECTION. ALL RECEPTACLES SHALL BE TAMPER RESISTANT SMOKE DETECTORS SHALL BE INTERCONNECTED • MIN 3 FT FROM REGISTER, BATH OR KITCHEN DOOR 2 in. MIN. CONNECT TO A CONCRETE-ENCASED ELECTRODE CONSISTING OF AT LEAST 20 FT OF ONE OR MORE BARE OR ZINC GALVANIZED STEEL REINFORCING BARS OF NOT LESS THAN 1/2 INCH OR CONSISTING OF AT LEAST 20 FT. OF BARE COPPER CONDUCTOR NOT SMALLER THAN No. 4 AND LOCATED WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT WITH EARTH. BOLTED -TYPE CONNECTION DEVICE OR EXOTHERMIC Y,=. ENCASED GROUNDING ELECTRODE DETAIL SPECIAL PURPOSE OUTLET TITAN INSTANT WTR HTR OR EQUAL PARTIAL ELECTRICAL PLAN n I CIO < < U < (-0 (-) U < 0 < n, 0 CE (7) n-- n-- -J LL- U U < Q < < -J 0 I CJ DO n � LLJ RUBEN J PUJOL' A.I.A. ARCHITECT N.,kC.A. AR# 0010458 PHONE No. (305) 968-2155 12237 SW 204 TERRACE MIAMI, FLORIDA 33177 CIO LJ < < (-0 (-) r-- 0 0 (7) n-- n-- ® Cf) < < Q < 0 0 0 -J 0 I CJ DO n n o Do LO Z < LO 0 CY cn U) 111 C/) 0 LLB < ry 0 V) LLJ ry Li -J 1-- < 0 C-) C) < LLJ C) C) LLJ 0 0 0 0— EL 0 0 RUBEN J PUJOL' A.I.A. ARCHITECT N.,kC.A. AR# 0010458 PHONE No. (305) 968-2155 12237 SW 204 TERRACE MIAMI, FLORIDA 33177