DESIGN
CODES: 2006 INTERNATIONAL
n
BUILDING iOr: ASCE 7-05
BASIC i SPEED:
IMPORTANCE FACTOR:
WIND EXPOSURE:
ASSUMED SOIL CLASSIFICATION
(IBC TABLE 0.
SANDY
CLAYEY SILT, SILT AND
SANDY
IF DIFFERENT
ENCOUNTERED,CONTRACTOR
SHALL CONTACT DESIGN
UL 1449, r
• r EDITION
2"X6" RECTANGULAR
HAND HOLE i
2—X6'CONDUIT ENTRY HOLE
r s •
ACTUAL BURIAL DEPTH POLE
MANUFACTURER
r�4+
:r
rod
•+r -r
•
r
age s 1 ll.
•err WITH FCI NO.
1 Jl {1--11 1 .
COMPRESSION C• ,r .
1=11 11. =1Ii�� 11— EXOTHERMIC WELD
MAN E
NO
SCALE: NTS
Drawing: t1JAXFILE01 \Commerclal\P \Wens Fargo\ We11s Fargo US\5016D40657 wells Fargo FL ATM & AHD Lighting\FL \140800- 140899\14081l_West Gables \Dwgs\14081 t West Gables.dwg
ELECTRICAL SYMBOL LEGEND
TYPE
PANELBOARD
®E -XX
NEW SURFACE - MOUNTED HID CANOPY DOWNLIGHT. LETTER
LAMP
LAMP TYPE
BALLAST TYPE
INDICATES TYPE.
®
NEW RECESSED - MOUNTED FLUORESCENT CANOPY DOWNLIGHT.
D-XX
LETTER INDICATES TYPE.
TF-XX
NEW POLE - MOUNTED HID AREA LIGHT. LETTER INDICATES TYPE.
NO.
NEW WALL - MOUNTED HID OR FLUORESCENT AREA LIGHT.
4B-XX
LETTER INDICATES TYPE.
�, --- -- `
NEW UNDERGROUND CONDUIT
A
NEW CONCEALED CONDUIT
_
EXISTING PANELBOARD
X
EXISTING RECESSED/SURFACE- MOUNTED HID /FLUORESCENT
CANOPY DOWNLIGHT
EXISTING POLE - MOUNTED HID AREA LIGHT.
r`
EXISTING WALL - MOUNTED HID OR FLUORESCENT AREA LIGHT.
SCWA
EXISTING RECESSED FLUORESCENT LIGHTING FIXTURE
NOTE: OBJECTS THAT APPEAR SHADED ARE EXISTING TO REMAIN.
PLAN NOTES
P1 NEW LIGHT POLE, POLE BASE AND AREA LUMINAIRE(S) IN LANDSCAPE. REFER
TO DETAIL 21E1 FOR POLE INSTALLATION DETAILS.
P2 REMOVE EXISTING FIXTURE AND MOUNT NEW FIXTURE IN SAME LOCATION AS
EXISTING FIXTURE. CONNECT TO EXISTING WIRING. FIELD MEASUREMENTS
INDICATED THAT EXISTING CIRCUITRY HAS CAPACITY FOR ADDITIONAL LOAD.
CONTRACTOR SHALL FIELD - VERIFY CAPACITY BY OPERATING EXISTING
LIGHTS AND MEASURING LOAD. NOTIFY PROJECT MANAGER IMMEDIATELY
SHOULD THE CAPACITY BE FOUND TO BE INSUFFICIENT. CONTRACTOR SHALL
COORDINATE MOUNTING REQUIREMENTS OF EXISTING POLE ON SITE PRIOR
TO ORDERING LIGHTING FIXTURE AND SHALL CONFIRM WITH MANUFACTURER
THAT THE EXISTING POLE AND BASE CAN ACCOMMODATE THE EPA
ASSOCIATED WITH THE NEW EQUIPMENT. CONTRACTOR SHALL FIELD - VERIFY
EXISTING POLE BASE RECEIVING NEW FIXTURE HEAD TO ENSURE THE BASE
HAS A DIAMETER OF AT LEAST 7 -0" AND EMBEDMENT DEPTH OF AT LEAST
6 -0 ". REQUIRED EXISTING DIAMETER AND DEPTH BASED UPON MAXIMUM
POLE DIMENSIONS OF 6 "x6" AND SOIL MATERIAL OF SAND WITH ALLOWABLE
BEARING PRESSURE OF AT LEAST 1500psf. CONTACT PROJECT MANAGER
IMMEDIATELY SHOULD THE EXISTING BASE NOT MEET THIS CRITERIA.
P3 REMOVE EXISTING FIXTURE AND MOUNT NEW FIXTURE IN SAME LOCATION AS
EXISTING FIXTURE. CONNECT TO EXISTING WIRING. ANY NEWLY- EXPOSED
BUILDING SURFACE SHALL BE CLEANED OF SURFACE DIRT AND RESTORED, IF
NECESSARY, TO MATCH EXISTING ADJACENT SURFACE. FIELD
MEASUREMENTS INDICATED THAT EXISTING CIRCUITRY HAS CAPACITY FOR
ADDITIONAL LOAD. CONTRACTOR SHALL FIELD - VERIFY CAPACITY BY
OPERATING EXISTING LIGHTS AND MEASURING LOAD. NOTIFY PROJECT
MANAGER IMMEDIATELY SHOULD THE CAPACITY BE FOUND TO BE
INSUFFICIENT. CONTRACTOR SHALL COORDINATE MOUNTING
REQUIREMENTS ON SITE PRIOR TO ORDERING LIGHTING FIXTURE.
P4 APPROXIMATE ELECTRICAL ROOM LOCATION. CONTRACTOR SHALL PROVIDE
AN OVERRIDE SWITCH FOR EXTERIOR SITE LIGHTING THAT WILL PROVIDE
"ON", "OFF" AND "AUTOMATIC" OPERATION. THE SWITCH SHALL BE LOCATED
ADJACENT TO EITHER THE LIGHTING CONTROL CONTACTOR, TIME -CLOCK OR
SOURCE PANELBOARD. PROVIDE CLEAR LABELING FOR THE SWITCH ON A
PERMANENT, ENGRAVED PHENOLIC LABEL.. TAPE OR HANDWRITTEN LABELS
ARE NOT ACCEPTABLE. CONTRACTOR SHALL VERIFY THAT CLOCK IS SET TO A
MINIMUM OF DUSK -TO -DAWN OPERATION AND THAT OVERRIDE SWITCH DOES
NOT INTERFERE WITH DUSK -TO -DAWN OPERATION WHEN IN "AUTOMATIC"
MODE.
P5 CLEAN REFLECTOR AND LENS (AS APPLICABLE) OF INDICATED FIXTURE OF
SURFACE DIRT AND DEBRIS AND RE -LAMP. FIXTURE WAS IDENTIFIED AS
INOPERABLE BY THIRD -PARTY SURVEY. NOTIFY OWNER IF FIXTURE HAS BEEN
REPAIRED PREVIOUSLY OR IF ADDITIONAL WORK IS REQUIRED TO RETURN
FIXTURE TO FULLY - OPERATIONAL CONDITION.
P6 CLEAN REFLECTOR AND LENS (AS APPLICABLE) OF INDICATED FIXTURE OF
SURFACE DIRT AND DEBRIS. FIXTURE WAS IDENTIFIED AS DIRTY BY
THIRD -PARTY SURVEY.
CIRCUITRY NOTES
FIXTURE(S) SHALL BE CIRCUITED TO A NEW 120 -VOLT, 20 -AMP, 1 -POLE
CIRCUIT BREAKER IN PANEL A. ROUTE CIRCUIT THROUGH ANEW 20 -AMP,
120 -VOLT LIGHTING CONTACTOR. EXTEND CONTROL TO NEW CONTACTOR
FROM EXISTING TIMECLOCK AND /OR PHOTOCELL - CONTROLLED LIGHTING
CONTACTOR. CONFIRM DUSK -TO -DAWN OPERATION. INSTALL NEW 298 WIRE,
1#8 GROUND IN 1" SCHEDULE 40 PVC CONDUIT AS SHOWN ON SITE PLAN 1/E1
FOR NEW LIGHTING FIXTURE(S).
s
s
- f
N h • •
PI.
M + flf
t
LIGHTING FIXTURE SCHEDULE
TYPE
FIXTURE DESCRIPTION
CATALOG SERIES
FIXTURE
LAMP
LAMP TYPE
BALLAST TYPE
MOUNTING
FIXTURE
REMARKS
VOLTAGE
NO.
WATTAGE
A
WALL - MOUNTED AREA LUMINAIRE, DARK BRONZE FINISH,
LITHONIA: ASW1- 150M- SR3 -TB- SCWA -LPI
METAL HALIDE LAMPING WITH SR3 DISTRIBUTION
120
1
METAL HALIDE
SCWA
SURFACE
150
E
SURFACE - MOUNTED AREA LUMINAIRE, DARK BRONZE
LITHONIA: KPS- 150M -R5-TB -LPI
COORDINATE MOUNTING WITH EXISTING CONDITION
FINISH, METAL HALIDE LAMPING WITH R5 DISTRIBUTION
120
1
METAL HALIDE
MAGNETIC
SURFACE
150
POLE- MOUNTED AREA LUMINAIRE, WHITE FINISH, METAL
LITHONIA- AS2- 400M- SR4SCFL -TB- SCWA- RP- I2 -DWH -LPI
NOMINAL FIXTURE HEIGHT SHALL BE 32' -0" AFG. REFER TO POLE
F
HALIDE LAMPING, SR4SC DISTRIBUTION, FLAT GLASS LENS,
120
1
METAL HALIDE
SCWA
POLE
400
INSTALLATION DETAIL FOR FURTHER INFORMATION
SQUARE TAPERED CONCRETE POLE
F1
POLE - MOUNTED AREA LUMINAIRE, WHITE FINISH, METAL
LITHONIA: AS2- 400M- SR3FL -TB- SCWA- RP- I2 -DWH -LPI
-R3
HALIDE LAMPING, SR3 DISTRIBUTION, FLAT GLASS LENS
120
1
METAL HALIDE
SCWA
POLE
400
F1
POLE - MOUNTED AREA LUMINAIRE, WHITE FINISH, METAL
LITHONIA: AS2- 400M- SR4SCFL- TB•SCWA- RP- 12-DWH -LPI
-R4
HALIDE LAMPING, SR4SC DISTRIBUTION, FLAT GLASS LENS
120
1
METAL HALIDE
SCWA
POLE
400
NOTE: FIXTURE FINISH OF BUILDING - MOUNTED LIGHTING FIXTURES BASED UPON FIELD OBSERVATIONS OF SURROUNDING FIXTURES AND SHALL BE CONFIRMED PRIOR TO ORDERING EQUIPMENT. MATCH EXISTING NEARBY BUILDING - MOUNTED FIXTURES FOR FINISH. LIGHT POLE TYPE
AND FINISH AND POLE - MOUNTED FIXTURE FINISH BASED UPON FIELD OBSERVATIONS OF EXISTING POLES AND POLE - MOUNTED FIXTURES, AND SHOULD BE CONFIRMED PRIOR TO ORDERING EQUIPMENT. MATCH EXISTING POLES FOR FINISH AND TYPE, AND MATCH EXISTING
POLE- MOUNTED FIXTURES FOR FINISH.
f
i1 ROViAf3_:ra�iF` VkJUD
Reynolds, Smith and Hills, Inc.
10748 Deerwood Park Boulevard South
Jacksonville, Ft 32256. 0.597
-Ph: (904) 25G -250G, Fax-(904):2564502
- - www.r--andh.cam
f FL Cert. Nos. AAC001886 ` IB26000956 "
ff EB0005620 • LCCO00210' GB238
WEST
GABLES
5880 Bird Rd
Miami, FL
33155
BE NUMBER :140811
ENVIRONMENT :2
SCENARIO : D
DISRUPTION : NO
DESCRIPTION:
ADDI COST : NO
DESCRIPTION:
IIIIIIIINITTERSTM
0
DATE r 08-26-2011
REVIEWED •
DRAWN
n