09-602-006� I •••i rrr • • i••i! rr• ••• r • • • r r • • ♦ u i • • • wri•• ••• iii • • • •ib! • • • 'i • U • • • !� • % CA n ( F D.1 O :_: : : FIRE PROTECTION GENERAL NOTES 1. FIRE PROTECTION SYSTEM TO COMPLY WITH NFPA 13, AND ALL APPLICABLE.STATE AND LOCAL CODES, 2. ADHERE TO AND OBTAIN ALL PERMITS, LICENSES AND GOVERNMENT REQUIREMENTS. 3. FINAL INSPECTION AND APPROVAL BY LOCAL FIRE DEPARTMENT, AND ARCHITECT /ENGINEER. 5. CUTTING OF STRUCTURAL AND /OR ARCHITECTURAL MEMBERS TO BE DONE ONLY WITH THE WRITTEN APPROVAL OF THE ARCHITECT. 6. PIPE ROUTING SHOWN SHALL BE USED AND ANY ADDITIONAL OFFSETS OR FITTINGS REQUIRED FOR PROPER INSTALLATION, COORDINATION WITH OTHER TRADES, AND /OR TO MAINTAIN PROPER CLEARANCES SHALL BE PROVIDED. VERIFY EXISTING STRUCTURAL, MECHANICAL, ELECTRICAL INSTALLATIONS AND AVOID ANY /ALL OBSTRUCTIONS OR INTERFERENCES WITH FIRE PROTECTION PIPE ROUTING. 7. FIRE STOP ALL PENETRATIONS OF SMOKE /FIRE WALLS, CEILINGS, FLOORS, ROOFS, ETC. FLASH AND COUNTERFLASH ROOF PENETRATIONS. (SEE FIRE RATED PIPE PENETRATION DETAIL). S. PROVIDE ACCESS PANELS TO ALL VALVES ABOVE NON - ACCESSIBLE CEILINGS AND CHASES. 9. SPRINKLER HEADS ARE TO BE COORDINATED WITH ALL EXISTING /NEW DIFFUSERS, SPEAKERS, LIGHTING FIXTURES AND CEILING SYSTEMS. 10. METHODS OF HANGING PIPES, HEADERS AND BRANCHES SHALL BE IN ACCORDANCE WITH N.F.P.A. 13. 11. AUTOMATIC SPRINKLER TEMPERATURE RATINGS OF FUSIBLE ELEMENTS TO BE IN ACCORDANCE WITH N.F.P.A. 13. 12. ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE UNDERWRITER'S LABORATORIES, INC. AND THE FACTORY MUTUAL LABORATORIES. VALVES SHALL BE FACTORY MARKED "UL" AND "FM ", 175 WORKING PRESSURE. 13. ALL VALVES ON THE FIRE PROTECTION SYSTEM TO BE ELECTRICALLY SUPERVISED. TYPE AND EXACT LOCATION OF FLOW, PRESSURE AND SUPERVISORY SWITCHES SHALL FACTORY MARKED "UL" AND "FM ", 175 WORKING PRESSURE. 14. ALL POWER WIRING SHALL BE ACCOMPLISHED UNDER THE ELECTRICAL DIVISION. ALL CONTROL AND INTERLOCK WIRING SHALL BE ACCOMPLISHED UNDER THIS SECTION OF THE SPECIFICATIONS IN ACCORDANCE WITH THE REQUIREMENTS IN THE ELECTRICAL DIVISION. COORDINATE ALL ELECTRICAL ITEMS WITH ELECTRICAL CONTRACTOR AND INSURE PROPER COORDINATION. 15. SPRINKLERS SHALL COVER THE ENTIRE AREA OF THE ROOM INCLUDING ALCOVES. SPRAY SHALL NOT BE BLOCKED BY WALLS OR PARTITIONS. 16. ALL SPRINKLER HEADS MOUNTED IN CEILING SHALL BE LOCATED A MINIMUM OF 4" AWAY FROM ANY WALLS, CEILING HEIGHT CHANGES OR ANY OTHER VERTICAL INTERSECTING SURFACE. 17. PIPE SHALL BE REAMED AND CLEANED BEFORE ASSEMBLY. 18. MAINTAIN A MINIMUM OF 18 INCHES FROM THE BOTTOM OF THE SPRINKLER DEFLECTOR TO THE TOP OF STORAGE/FILE STORAGE. 19. PROVIDE SPRINKLERS ABOVE AND BELOW EXPOSED DUCTWORK 4 FEET OR WIDER. 20. FIRE SPRINKLER SYSTEM TO BE MONITORED BY FIRE ALARM SYSTEM BY OTHERS. 21. Q INDICATES HYDRAULIC REFERENCE NODES No. 1 NAMUR DETAIL Revisions SUBMIT FOR APPROVAL By JRGN nar -1N ANCHOR 53 PSI Reading 42 I G.P.M. 1860 y 2/9/09 Of Test 3/2• RM iOUrIIWC 3/1' ALL THREAD ROD STEEL PIPE EXCEPT THREADED LIGHTWALL N/A No 12 -0 Time Test 1 PIK SEE VMIE�) 1' TO 15 -0 15 -0 (!Z 15 -0 15 -0 TYPICAL HANGER DETAIL Hydran THREADED LIGHTWALL STEEL PIPE N/A 12 -0 PPE SIZE ME SIZE TYPE OF MIN, 'C' W. 'C' N/A N/A FASTENER Dim, OM. 3/4' 9--0 1 -3/1' X 1 -17/32- ERM -NN ANCHOR 1/2' 1 -5/1• 1' 0. 1 -3/4. 15 -0 13110• 1 -7/1' 15 -0 ti /1N 2' 2• 1 -3/12 2 -3/1' 2 -1/2' 1/2• 1 -1/2• X 2 -1/32• PROP-IN ANCHOR 1-711C 2 -314" 3. 1 -3/4' 3 -1/4' 3-1/2` 2. 3 -2 /8• 4' 5/1' 1 -6/1' X 2 -16/32' OR{r -IN ANCHOR 2 -1/4' 3 -7 /1• O' 2 -0/4' 4 -314' p 3/4' 1 -3/4' X 3 -114•, OT. -IN ANC. 3 -5/12' 1• N/A I N/A I N/A N/A No. 1 Date 29/2009 Revisions SUBMIT FOR APPROVAL By JRGN Static Residual F itot Flow I 53 PSI Reading 42 I G.P.M. 1860 Of Test 2/9/09 Of Test Date STEEL PIPE EXCEPT THREADED LIGHTWALL N/A 12 -0 12 -0 Time Test 1 15 -0 15 -0 15 -0 15 -0 15 -0 15 -0 15 -0 Hydran THREADED LIGHTWALL STEEL PIPE N/A 12 -0 12 -0 12 -0 12 -0 12 -0 12 -0!, N/A N/A Fre S rinkler Piping Plan SCALE: 1/8 " =1' -0" DRAIN TEST 1" DRAIN ASSEMBLY 11/" DRAI 4" RISER PIPE RISER CLAMP (I-LINE MODEL 33373CTC OR EQUAL) MIN I' THICK MEDIUM DENSITY 304/4 NEOPRENE STEEL PLATES (CLUE TOGETHER WITH NEOPRENE PAD CONCR, FLOOR TO FARM ONE UNIT. USE CONTACT CEMENT), ELEVATION 2" DRAIN SEE FIRESTOP DETAIL 3' LAB PLAN VIEW 3' NOTE, PROVIDE RISER CLAMP AT EVERY OTHER FLOOR FIRE SPRINKLER ,END STRAPS CONTROL VALVE ASSEMBLY DETAIL N.T.S. oken By I LT M FERNANDEZ Location 5876 SW 68 ST GE TO SPRINKLER ---Ire , F -0R 11/Z" CONTROL VALVE FOR 21/Z" CONTROL VALVE �10 I L MAXIMUM DIS ANCE; EEN HANGERS Water Supply Information pressure 55 PSI Pressure 53 PSI Reading 42 I G.P.M. 1860 Of Test 2/9/09 Of Test 12:15 oken By I LT M FERNANDEZ Location 5876 SW 68 ST GE TO SPRINKLER ---Ire , F -0R 11/Z" CONTROL VALVE FOR 21/Z" CONTROL VALVE �10 I L MAXIMUM DIS ANCE; EEN HANGERS NOMINAL PIPE SIZE (in.) 3/4" 1 " 1-1/4- I 1 -1 /2" 2" 2-1/2" 3" 3-1/2" 4" 5" 6i" a" STEEL PIPE EXCEPT THREADED LIGHTWALL N/A 12 -0 12 -0 15 -0 15 -0 15 -0 15 -0 15 -0 15 -0 15 -0 15 -0 15 -0 THREADED LIGHTWALL STEEL PIPE N/A 12 -0 12 -0 12 -0 12 -0 12 -0 12 -0!, N/A N/A N/A N/A N/A COPPER TUBE 9--0 8-0 10 -0 10 -0 12 -0 12 -0 12 -0 15 -0 15 -0 15 -0 15 -0 15 -0 CPVC 5 -6 6-0 C -C 7 -0 5 -0 9 -0 12 -0 N/A N/A N/A N/A N/A POLYBUTYLENE (IPS) N/A 3 -9 4-7 5--0 5 -11 N/A N/A N/A N/A N/A N/A N/A POLYBUTYLENE (CTS) 2 -11 3 -4 3 -11 4--5 5 -5 N/A N/A N/A N/A N/A N/A N/A Project Design Criteria Sprinklers/ Spacing r* SOMERSET CHARTERSCHOOL System No. Symbol Qty Size K Temp Description SIN REC PENDENT TY -3231 � 5876 SW 68 ST Design Area Area #1 Area #2 © 119 1/2" 5,6 155 TYCO -QUICK RESPONSE WHITE TY --FRB SEMI �+ �� Fires Density 10 GPM /SQ Fr 10 GPM S .Ft / 4 1 1/2" 5.6 155 TYCO -QUICK RESPONSE WHITE TY -FRB SEMI REC SW TY -3331 :' Miami, Florida 33143 Design Area S.f. 225 225 (� I P R I N K , mtct Wllh: Psi Req'd © City Main 54.93 1 54.95 Gpm Req'd 9 City Main 306.7 250.3 ; , Sj for N.. 1 _ wt•: 2/9/2009 ' Gpm Req d v Bosr 50.06 39.72 '� } ;All Fire Sprinklers � 1/8.= 1 0 No. Spkr. In Ds'n, Area 9 9 ;? � _ • 7492 N.W. 8nd Street �`; . ;" S i,11. r }4 choc4d ryp ' F d All Fire S nn ers' A1J: Authority Having Jurisdiction Elev. 0 Highest 5pkr 10' 20' Medley,Florida 33126'., {; � t / s �, , ;.� 244 TEL:(305) 403 -4455 FAX:(305) 403 -4488 " " "� ` C.ntrrat N•.} FP-2 " 3 Domestic /outside Hose 100 100 Certification # 56528000012005 /1 �' I'�� 09 -r Of - _ 120 Total This Sheet State 4 . .. I I • T,`::.