09-321R-003Of. q* 1064 Battery Calculation. MAIN POWER SUPPLY VOLTAGE DROP CALCULATION QTY DC RESISTENCE FOR SOLID COPPER WIRES AT 15 DEGREES Current (Amps) SIZE OHMS PER FOOT 0 18 0.00111 0.2585(o X 1(o 0.00489 24 = 620 Alarm Load 14 0.00301 Required Alarm Time in Hours Current (Amps) 12 0.00121 1 • • e Wire resistance values comply with NFPA 10 NEC chapter 9 table 8. Conductor X Properties 2002 edition. ri ri • • �© Total 1098 B(mA) 4 ri FORMULA FOR CALCULATION OF VOLTAGE DROP IN DC 2 WIRE CKT. - VD= Rx2Lxl 148 C) Where VD: 8.0 0 VD = Voltage drop at the last device on the circuit �• R = Resistance or wire in Ohms per foot. 0.000 ° (Values of resistance for cooper wire per tables above) I- *+ L = Length one way of the circuit in feet. 0.000 0 1 = Total circuit current in Amperes. 1.531 Totals (Amps) Totals (Amps) 1.961 C) MAC Of WIre she 014 from FRCP MAC 02 WIro size 014 Arm FRCP cc R = 000301 Ohms per foot. R = 0.00301 Ohms per foot. L = 100 feet. L = CM feet. ro I = 0.085 Amp. I = 0000 Amp. 75Cd 75Cd i5Cd 75Cd i5Cd 75Cd 75Cd VD= Rx2Lxl VD- Rx2Lxl to VD = 0.00301 x 2 x 100 x 0.085 VD = 0.00301 x 2 x 000 x 0.00 o rr o o VD = 0.1 VD = 0.0 20A Volt - 0.1 Volt = 20A Volt - 0.0 Volt = ©© 203 Volt at the end of the line. 20.4 Volt at the end of the line. ri ii ii AUC 01 Wrrs she 014 hoe. BPSO! MAC 02 Wire size 014 from BPS#! R = 000301 Ohms per foot. R = 0.00301 Ohms per foot. L = 115 feet. L = 140 feet. I = 1B31 Amp. I = 1.961 Amp. VD =Rx2Lxl VD- Rx2Lxl ©© VD- 000301x 2 x 115 x 1.831 VD = 000301 x 2 x 140 x 1.961 o rr it o • VD= 20 VD= 11 20A Volt - 20 Volt = 20.4 Volt - 1.1 Volt = �© 18.4 Volt at the end of the line. 18.1 Volt at the end of the line. i ro MAC 83 WIre she 014 from BPSO1 MAC 04 WIre she O!4 fMm BPS#! R = 000301 Ohms per foot. R = 0.00301 Ohms per foot. ©© L = 165 feet. L = 185 feet. orrao- I = 1.961 Amp. 1 = 1321 Amp. VD =Rx2Lxl VD= Rx2Lxl VD= 0.00301 x 2 x 165 x 1.%1 VDa 0.00301x 2 x 185 x 1321 VD= 10 V0=15 © 20.4 Volt - 20 Volt = 20A Volt - 15 Volt = r 18.4 Volt at the end of the line. 18.9 Volt at the end of the line. o rr ri ri MAC 01 W/ro sire 014 from BP302 ro e O!4 from B © R = 000301 Ohms per foot. R = 0.00301 Ohms per foot. ri L = 126 feet. L = 234 feet. rr rr rr q I = 1.915 Amp. I = 2.188 Amp. ® VD =Rx2Lxl VD =Rx2Lxl �© VD. 000301 x 2 x 126 x 1.915 VD-- 0.00301 x 2 x 234 x 2.188 ri ri VD= 15 VD= 40 © 20A Volt - 15 Volt = 1 20.4 Volt - 4.0 Volt = ii 18.9 Volt at the end of the line. 16.4 Volt at the end of the line. rr rrari 1 -© R = 000301 Ohms per root. R = 0.00301 Ohms per foot. 'r L = 195 feet. L = 100 Feet. I = 2.611 Amp. I = 0.650 Amp. VD- Rx2Lxl VD =Rx2Lxl VD= 0.00301 x 2 x 195 x 2611 VD= 0.00301x 2 x 100 x 0650 VD= 3.1 VD= 0.4 20.4 Volt - 3.1 Volt : 20A volt - 0.4 Volt = 113 Volt at the end of the line. 20.0 Volt at the end of the line. Of. q* 1064 Battery Calculation. MAIN POWER SUPPLY Calculation in total sheet Standby Load UNIT (mA) QTY Required Standby Time ni Current (Amps) 369 0 Hours ( 24 or 60 Hours ) 0.2585(o X 18 24 = 620 Alarm Load 255 Required Alarm Time in Hours Current (Amps) 0.562 1 • • e �© X r ri • • ri ri • • �© Total 1098 B(mA) 4 ri 0.000 6234 Multiply by the Derating Factor of 12 Strobe Light 15Cd 148 Total Ampere -Hours (AH) Minimum Required 0.000 8.0 0 Spare 0.000 0.000 0.000 0.000 0 Spare 0.000 0.000 1 0.000 0.000 Totals (Amps) Totals (Amps 1.531 Totals (Amps) Totals (Amps) 1.961 1321 Amp Actual load. 14 -1 14 -2 14 -3 14 -4 14 -5 1.5 Volts dropped 281mA 281mA 255mA 255mA 255mA 75Cd 75Cd i5Cd 75Cd i5Cd 75Cd 75Cd won, 070710 ©© 'r o rr o o rr o o .. ri ©© o o ii ri ri ri ri ©© ri ri ii ri • ri ii ii � � � � - � - ©© rr a ri rr o o ri :: ©© o ri rr ri .: ri o rr it o • - • • - 0© r ri ri ri ii ri ri ri �© ri rr o ri i ro e e, �• a ©© oaoorr• M aarrrri• ©© rroorro• orrao- ., o a rr rr .. - rr © r ri ii ii o ri rr o r © ri �i ri ri o rr ri ri . .. ri © o ri ri rr ri ri ri ri ri ri © rr p rr rr rr rr rr q ` e - - • • • rr ® o ri it o ri ii ri o ri ii �© o o : ri ri ` - •• • rr © rr oiriro 0 o rorr ii © o iroo rr rrari • ' -© ri ri ri ri ri - 'r ■ -- Calculation in total sheet Standby Load UNIT (mA) QTY Required Standby Time ni Current (Amps) 369 0 Hours ( 24 or 60 Hours ) 0.2585(o X 18 24 = 620 Alarm Load 255 Required Alarm Time in Hours Current (Amps) 0.562 1 ( I. E. 5 MIN. = 0284) 0.411915 X 0.000 0.084 = 0.0346 Add standby and alarm load for required Total 1098 B(mA) 0.000 Ampere Hours Battery 0.000 6234 Multiply by the Derating Factor of 12 Strobe Light 15Cd 148 Total Ampere -Hours (AH) Minimum Required 0.000 8.0 WILL PROVIDE 8*1P MIN BATTERIES 2 X I:2 VOLT FIRE ALARM CAPABLE OF 64 DEVICES ADDRESSES IN ONE CLASS 'B' LOOP AND 3.15A FULL LOAD OUTPUT (25A MAX. PER CIRCUIT) TWO CLASS 'B' STYLE 'Y' NAG MAIN RECALL ALT. RECALL E. W. L. 1 FIRE ALARM RISER #LT.& FIRE ALARM BOOSTERS 10.0AMP5 FULL LOAD OUTPUT (3.0 AMPS MAXIMUM PER CIRCUITS) FOUR CLASS 'B' STYLE 'Y' INDEPENDENT NAC NITIATION CIRCUIT TO BE CLASS 'B' STYLE '4' NOTIFICATION CIRCUIT TO BE CLASS 'B' STYLE 'Y' M33 M32 R3 R2 Rl H31 831 Roof. WP F PS33 PS32 Second floor. SHUNT TRIP -, MONITOR WATERFLOW 4 TAMPER SWITCH I IMONITOR TAMPER SWITCH 3 M21 DD2 DDl H22 H21 T4 Fl T6 Second floor. First Floor TAMPER SWITCH PIT MONITOR WATERFLOW 4 TAMPER SWITCH M31 R4 326 325 524 523 622/,' 821 ID rT r1 45HAFT S22 P521 HI LSl S6 55 64 53 52 Sl M2 DI M1 P53 P52 PSl T4 FI Tl TI T T3 MONITOR TAMPER SWITCH CKT 'I' FROM FACP 2.5 Amp Max load. 0.034 Amp Actual load. WP SI 0.01 Volts dropped ANNi FAA 1D,1F TO DEDICATED PHONE LINE 3'12 THHN,120VOLT, 20 Amp CIRCUIT TO DEDICATED BREAKER' 21 PANEL H - ELECT. ROOM Ist FLOOR FA® 1112TN14N Green - 3'12 T", 120VOLT, 20 Amp CIRCUIT TO DEDICATED BREAKER' 21 PANEL H ELECT. ROOM Ist FLOOR iNAC Trip PI GreeN - Green BATTERY BACKUP CALCULATIONS DW POWER BOOSTER BPS#1 (4 ALARM MODE DEVICE UNIT (mA) QTY TOTAL (mA) Horn Strobes 110Cd WP 369 0 0000 Horn Strobes 15Cd 281 18 5058 Strobe light 15Cd 255 8 2040 0.562 1 Horn /Strobe 15Cd 0.000 0281 0.000 1.961 5 Total 1098 B(mA) Supervisory Current Calculation Supervisory Current 10 + A (if WI-12 = OFF) 10 (mA) Supervisory hours ( i.e. 24,60) x 24 (Hr) Supervisory battery required (mAHr) = 1680 C (mAHr) Alarm Current Calculation Alarm Minutes( i.e. 5min) = 5 D (min) Alarm Hours ( D160) = 0.084 E (Hr) Alarm Current 190 + A (if SWi - 12 = OFF) + B = 1288 (mA) Alarm Hours 1 0.084 1 E (Hr) Alarm Batterg Required (mAHr) - 6122 F (mAHr) Total Batteru Requirement Total Amps -Hours Battery Size (1.11 x C) + (2 x F) 3.09 1.0 AH Min. 1000 Device Current Draw Each Standby Alarm WILL PROVIDE 7 AMP MIN BATTERIES 2 X 12 VOLT Circuit Configuration Power Booster P 11 Ckt name: First floor 11 Ckt name: First floor 03 Qty Device Current Draw Each Standby Alarm Current Draw Total standby Alarm Qty Device Current Draw Each Standby I Alarm Current Draw Total Standby Alarm 2 Horn /Strobe 15Ccl 0.000 0281 0.000 0.562 1 Horn /Strobe 15Cd 0.000 0281 0.000 1.961 5 Strobe Light 15Cd 0.000 0255 0.000 1.215 0 Strobe Light 15Cd 0.000 0255 0.000 0.000 0 Spare 0.000 0.000 0.000 0.000 0 Spare 0.000 0.000 1 0.000 0.000 Totals (Amps) Totals (Amps 1.531 Totals (Amps) Totals (Amps) 1.961 kt name: First floor 12 Ckt name: First floor 04 Qty Device Current Draw Each tandby Alarm Current Draw Total standby Alarm Qty Device Current Draw Each standby Alarm Current Draw Total Standby Alarm 1 Horn /strobe 15Cd 0.000 0281 0.000 1.961 2 Horn /Strobe 15Cd 0.000 0281 0.000 0.562 0 Strobe Light 15Ccl 0.000 0255 0.000 0.000 3 Strobe Light 15Cd 0.000 0255 0.000 0.165 F_o[ Spare 0.000 0.000 0.000 0000 0 Spare 0.000 0.000 0.000 P1321 .000 Line voltage wiring. Totals (Amps) 1.961 S Totals (Amps) 1369�,nA 110cd CKT '4' FROM FAB 5PS•2 3.0 Amp Max load. 0 Ob50 AMV-Attgal*lpa�- WP 0.4:Volts, dropped , , � 23-9 v . �. 369mA 1 15Cd 155d 15Cd 15C01 15TC1 15Cd 15Cd 15Gd 23 -1 23 -2 23 -3 23 -4 23 -5 234 23 -1 23 -8 281mA 281mA 281mA 281mA 281mA 281mA 281mA 281mA N;n B BPS"2 . load. 2 15Cd 15Cd 15Cd 15Gd 15Cd 15Cd 75Cd 15Cd 110Cd TOTAL; l 331 Horn Strobes 110Cd CKT '2' FROM FAB BP602 3.0 Amp Max load. ^ 1 S -LuJ` VVr as 5339 2.188 Amp Actual load. 22 -1 22 -2 22 -3 22 -4 22 -5 22 -6 22 -1 22 -1a 22 -5 4.0 Volts dropped .25 281mA 281mA 281mA 281mA 255mA 255mA 281mA 255mA 331MA system smoke detector connected to activate i Q 15Cd i5Cd 15Cd -15Cd i5Cd 15Cd -15CCI (E) System Heat detector (135 deg. F) located within CKT 'I' FROM FAB BPS"2 � 7 3.0 Amp Max load. Q Fire alarm system wiring to head detectors. 1.915 Amp Actual load. Qi 21 -1 21 -2 21 -3 21 -4 21 -5 21 -6 21 -1 15 Volts dropped 281mA 255m;4 255mA 281mA 281mA 281mA 281mA of system head detector 4 shunt trip in OR POWER BOOSTER ��Cd i5Cd ISGd 15Cd 15Cd OQ Line voltage wiring. CKT '4' FROM FAB BPS "I S 3.0 Amp Max load. 26 1321 Amp Actual load. 14 -1 14 -2 14 -3 14 -4 14 -5 1.5 Volts dropped 281mA 281mA 255mA 255mA 255mA 75Cd 75Cd i5Cd 75Cd i5Cd 75Cd 75Cd 13 -1 13 -2 13 -3 13 -4 B -5 134 13 -1 ®M 281mA 281mA 281mA 281mA 281mA 28lmA 281mA 8 3Zff1 715Cd 15Cd 15Cd 715Cd 15Cd 15Cd i5Cd 1 Green Teen 12 -1 12 -2 12 -3 12 -4 12 -5 12 -6 12 -1 281mA 281mA 281mA 281mA 281mA 281mA 281mA 715Cd 15Cd 15Cd 15Cd 15Cd 715Cd 715Cd II -1 I1-2 11 -3 11 -4 II -5 11 -6 II -1 255mA 255mA 255mA 281mA 255mA 255mA 281mA CKT '3' FROM FAB BPS "I 3.0 Amp Max load. i.961 Amp Actua I load. 2.0 Volts dropped CKT '2' FROM FAB BP51 30 Amp Max load. 1361 Amp Actual load. 1.1 Volts dropped CKT '1' FROM FAB 13P501 3.0 Amp Max load. 1.831 Amp Actual load. 2.0 Volts dropped BATTERY BACKUP CALCULATiONS 0 POWER BOOSTER BPS#2 ALARM MODE DEVICE UNIT (mA) QTY TOTAL; l 331 Horn Strobes 110Cd 331 I Horn Strobes 15Cd 281 19 5339 Strobe light 15Cd 255 4 1020 G) Elevator machine room, lobby 4 top of hoistway KTA system smoke detector connected to activate fire fighter's services recall. Total 6696 B(mA) Supervisory Current Calculation Supervisory Current 10 + A (if 5WI -12 = OFF) = 10 (mA) Supervisory hours ( i.e. 24,60) x 24 (Hr) Supervisory battery required (mAHr) = 1680 C (mAHr) Alarm Current Calculation Alarm Minutes ( i.e. 5min) = 5 D (min) Alarm Hours ( D/(00) 0,084 E lHr) Alarm Current 190 + A (if SWl - 12 = OFF) + B = 6886 (mA) Alarm Hours = 0.084 E (Hr) Alarm Batterg Required (mAHr) - 518.42 F (mAHr) Total Battery Requirement Total Amps -Hours Battery Size (I.11 x C) + (2 x F) 3.0 1.0 AH Min. 1000 Elevator Disconnect switch with shunt- trip I�IRIN�� ®R�• INTELLIGENT WILL PROVIDE T AMP MIN BATTERIES 2 X 12 VOLT FIRE ALARM ELEVATOR POWER 1215CONNECT Shirt trip disconnecting means 120 volt AC Not circuit (Power to operate the shunt trip Neutral diconnecting means) RELAY • Relay contacts shown de- energized M31 IM TOIDC R4 SUPERVISORY SIGNAL TO FACP TO IDC t e NORMALLY OPEN 1 Ft Alf��rv`" 4 }i' .L 3E A Glrf�r; RAL ST�if . I i tL- . � i >_. A CEFCt IFiGF�TL- OR F4_AD„RD F:t•',1L 22 PO�6 -rED of FINAL INSPECT, I;):.1, AS PER NFPA72 FiLZE ALAJ' d: S'Y'S1 F lvl TO BE iN5TALU-P, lid Zi. COPDANCE VM-1A P4FPA 712; 70;101- aESreNroo: FE_.! 110 Juan A. Rodriguez. laL°ifA"R,l7, -1 System Contractor State Lic: EF- 0001235 12491 aW 134 CT Unit 24 * Miani, FL. 33186 Fh: 305-992 -4284 Fx - 305- 232 -6190 sssxodricJrezeaoltan 12491 5W 134 CT Unit 24 r 7M BrAll Urn 1111!111141111�1111f Miami, F1.33186 PINO CURT15 P.E. CORP. Ph: 305 - 232 - 6163 �iliClli11�ATL'�ARTfI�! Alejandro E. Piro Fx: 305 - 232 -6192 - - Proffessional Engineer REVISION 50MER5ET CHARTER 5CHOOL State Reg.- P.E. - 0051451 Na DATE BY @ SOUTH MIAMI State Lic. #21283 I 03 -20 -2009 B.J. 5876 5A 68th 5T South Miami, Florido 33143 14842 5W 34th Ln © 03 -20 -2009 (A5 BUILT) J.R. Boston Investors Grou INC, ,''' � . , , �t - • � Miami, FL. 33185 P X03 -09 -09 4 ' �, Ph: 305 -562 -8616 Fx33IL35 -3623 C/O Miller Hamilton Snider 4 Odom r. 1/6 -0 1 ``' �''� inocurtis a ®bellsouthnet 1200 Brickel Ave 68th 5t. Ilth FI. ED.V, sue; 8� srr+a� r'~ R £ • s fir ev- Ivi Notes. TYPICAL I ELEVATOR E VATOR Q Elevator Disconnect switch with shunt- trip I�IRIN�� ®R�• INTELLIGENT � Elevator Fire Fighter's services Recall Wiring ' tional' Fire sprinkler Shut -off valve. Tamper ����M switch wiring connected to main FACP. G) Elevator machine room, lobby 4 top of hoistway KTA system smoke detector connected to activate fire fighter's services recall. (E) System Heat detector (135 deg. F) located within � 24' of sprinkler head. Q Fire alarm system wiring to head detectors. Qi 5hint trip control power monitor. Shunt trip power connected to auxiliary contact of system head detector 4 shunt trip in disconnect switch for elevator shut down. OQ Line voltage wiring. FIRE ALARM ELEVATOR POWER 1215CONNECT Shirt trip disconnecting means 120 volt AC Not circuit (Power to operate the shunt trip Neutral diconnecting means) RELAY • Relay contacts shown de- energized M31 IM TOIDC R4 SUPERVISORY SIGNAL TO FACP TO IDC t e NORMALLY OPEN 1 Ft Alf��rv`" 4 }i' .L 3E A Glrf�r; RAL ST�if . I i tL- . � i >_. A CEFCt IFiGF�TL- OR F4_AD„RD F:t•',1L 22 PO�6 -rED of FINAL INSPECT, I;):.1, AS PER NFPA72 FiLZE ALAJ' d: S'Y'S1 F lvl TO BE iN5TALU-P, lid Zi. COPDANCE VM-1A P4FPA 712; 70;101- aESreNroo: FE_.! 110 Juan A. Rodriguez. laL°ifA"R,l7, -1 System Contractor State Lic: EF- 0001235 12491 aW 134 CT Unit 24 * Miani, FL. 33186 Fh: 305-992 -4284 Fx - 305- 232 -6190 sssxodricJrezeaoltan 12491 5W 134 CT Unit 24 r 7M BrAll Urn 1111!111141111�1111f Miami, F1.33186 PINO CURT15 P.E. CORP. Ph: 305 - 232 - 6163 �iliClli11�ATL'�ARTfI�! Alejandro E. Piro Fx: 305 - 232 -6192 - - Proffessional Engineer REVISION 50MER5ET CHARTER 5CHOOL State Reg.- P.E. - 0051451 Na DATE BY @ SOUTH MIAMI State Lic. #21283 I 03 -20 -2009 B.J. 5876 5A 68th 5T South Miami, Florido 33143 14842 5W 34th Ln © 03 -20 -2009 (A5 BUILT) J.R. Boston Investors Grou INC, ,''' � . , , �t - • � Miami, FL. 33185 P X03 -09 -09 4 ' �, Ph: 305 -562 -8616 Fx33IL35 -3623 C/O Miller Hamilton Snider 4 Odom r. 1/6 -0 1 ``' �''� inocurtis a ®bellsouthnet 1200 Brickel Ave 68th 5t. Ilth FI. ED.V, sue; 8� srr+a� r'~ R £ • s fir ev- Ivi .% s �