09-321R-002In ry Cs 0 r�l 0 E ch 0 C7 TZC:S co e� C ,t) GENERAL NOTES I.- The Fire Alarm System is designed for 'Somerset Charter School at South Miami' located at 5816 SW 66th St South Miami, FI- 33143. 2.- All equipment shall be New, Identified, Compatible and UL. listed for use as per CDC ch 8, NFPA 12 Ch. 1 -4 and FBC 901. 3: The Design and installation of the Fire Alarm system shall comply with the NFPA -10 National Electric Code (NEC) 2005 edition, the Florida Building Code (FBC) 11-41133,2004 edition, Life Safety Code NFPA 101, 2006 Edition and NFPA 11 National Fire Alarm Code 2002 Edltion- 4.- The Fire Alarm System consist of an intelligent fire detection and notification system. The Fire Alarm System is GE Security 'i0 -64' Intelligent Life Safety System. 5: All Fire Alarm equipment for this project shall be rated 'Power Limited' - 6: All fire penetrations shall be sealed with U.L. approved Fire Stop Materials. (see Fire Penetration Detail). 1: Manual Stations to be installed at 48' AFF as per chapter Il figure 5(a) of the Florida Building Code (FBC). 8.- Fire Alarm circuit to be class 'B' Style '4' for initiation and class 'B' Style 'Y' for Notification circuits. 9.- Cable size shall compiy with the Article 160 -11 and the cable installation shall comply with the separation and use of conductors and cable as specified in Article 160 -54 and 160 -61 of the National Electric Code - 10.- The Fire Alarm must have a ground as per manufacturer recommendation this ground to be *11 THHN min. 11.- Location of Smoke Detector: The location of the Smoke Detector are specified in the set of plans. 12: All 120 V. feed to FACP to be on dedicated circuit and marked red Fire Alarm circuit. 13.- All Control Relay to be within 3 feet of device being controlled. 14.- Building wiring shall specifically conform with the National Electric Code, Article 160 Part 'C' for 'Power Limited' Fire Protection signal circuit with emphasis on article 160 -52(b) on power limited wiring method and materials article 160 -28, 40% fill in y' conduit minimum. 15: All Alarm Notification Devices shall audible and visual and shall be done via Horn Strobe combination Devices. Strobe light shall be clear Xenon type, with intensity of 15 candelas as per article 428 (U through (5) of the ADA. guidelines of july 25, 1992 and as per article 11 -4283 (4) of the Florida Building Code 2004 Edition. 16: System to be a Certificated /placarded Central station services in comppliance with NFPA 1282 2002 edition. 11.- This design was based on calculation over a set of plans provided to the design engineer. if the post installation on site tests conduted by the Authority having juridiction determines that, because of unforeseeable condions or change in field parameters, the audible alarm level falls below the required level in specific areas, the number of audible Horn Strobe shall be increased to comply with the requirements and to comply with the requirements and to the satisfation of the authority having juridiction. 18.- All new wiring installed in duct, plenums and other spaces used for enviromental air shall be type FPLP, as per N.E.C. (National Electric Code) article 160 -61. 19.- System is design to comply with NFPA 101 Chapter 14 Section 143A New Educational Occupancy. WIRE LEGEND D = 2 " 18 THHN or FPLP MIN. INITIATION CKT. S = 2 014 THHN or FPLP MIN. NOTIFICATION CKT. F = 2 ' IS THHN MIN. AUX. POWER CKT. A = 3 f12 THHN POWER CKT 120V 20A. All conduit 1/2' minimum EMT, PVC or Smurf (ENT) NOTE: For a l l underground runs: D 2 s18 THW MIN. INITIATION CKT. S = 2 h4 THW MIN. NOTIFICATION CKT. F = 2 '14 THW AUX. POWER CKT. A = 3 012 THW POWER CKT 120V 20A FIRE ALARM SYSTEM SEQUENCES OF OPERATION I. -The Activation of the fire alarm initiating devices shall automatically initiate the Function detailed below A.- MANUAL FIRE ALARM PULL STATION Activation of the manual Fire Alarm Pull Station shall Initiate the following functions: I.- Generate an audible alarm signal at the Fire Alarm Control Panel and at the Remote Annunciator Panel. 2.- Generate an audible alarm signal simultaneosuly on all areas of the building by means of Horn and Horn /Strobe devices. Generate a visual alarm signal simultaneosuly on all areas of the building by the use of Strobe devices or combination Horn /Strobe notification devices. 3.- Indicate the location of the Pull Station by displaying, In English, the alarmed devices and its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. 4.-Transmits a Fire Alarm signal to the Listed Central Station by way of digital telephone dialer. B.- FIRE ALARM SMOKE DETECTORS Activation of the Fire Alarm Smoke Detector shall initiate the following functions: I.-Generate an audible alarm signal at the Fire Alarm Control Panel and at the Remote Annunciator Panel. 2.-Generate an audible alarm signal simultaneosuly on all areas of the building by means of Horn and Horn/Strobe devices. Generate a visual alarm signal simultaneosuly on all areas of the building by the use of strobe devices or combination Horn/Strobe notification devices. 3.-Indicate the location of the smoke detector by displaying, in English, the alarmed devices and its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. 4.- Transmits a Fire Alarm signal to the Listed Central Station by way of digital telephone dialer. C.- FIRE ALARM ELEVATOR SMOKE DETECTORS (elevator lobby d machine room) Activation of the Fire Alarm Smoke Detector (elevator lobby 4 machine room only) shall initiate the following functions. I.- Generate an audible alarm signal at the Fire Alarm Control Panel and at the Remote Annunciator Panel. 2.- Generate an audible alarm signal simultaneosuly on all areas of the building by means of Horn and Horn/Strobe devices. Generate a visual alarm signal simultaneosuly on all areas of the building by the use of strobe devices or combination Horn /Strobe notification devices. 3.- Indicate the location of the smoke detector by displaying, in English. the alarmed devices and its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. 4.- Initiate the automatic recall operations of all the elevator as follows: a. Recall all elevators to the ground floor upon activations of any alarm initiating circuit on any floor other than the ground floor. b. Recall all elevators to the alternate level upon activations of any alarm initiating circuit on the ground floor. 5.-Activate the warning lights at the elevator lobby. 6.- Transmits a Fire Alarm signal to the Listed Central Station by was of digital telephone dialer. D.- FIRE ALARi'1 SMOKE DUCT DETECTORS. Activation of the Fire Alarm Smoke Duct Detector shall initiate the following functions: I.- Generate an audible supervisory signal at the Fire Alarm Control Panel and at the Remote Annunciator Panel. 2.-Indicate the location of the Smoke Duct Detector by displaying, in English the alarmed devices and its location on the FACP alphanumeric display and on the Remote Arnunciator alphanumeric display. 3. -Shut off the air handling unit and A/C equipment associated with the Duct Detector. 4.- Transmits a Fire Supervisory signal to the Listed Central Station by way of digital telephone dialer. C.- FIRE ALARM WATER FLOW DETECTORS. Activation of the Fire Alarm Water Flow Detector shall Initiate the following functions: 1.- Generate an audible alarm signal at the Fire Alarm Control Panel and at the Remote Annunciator Panel. 1.- Generate an audible alarm signal simultaneosuly on all areas of the building by means of Horn, Horn /Strobe and flowbell devices. Generate a visual alarm signal simultaneosuly on all areas of the building by the use of strobe devices or combination Horn/Strobe notification devices. 3. -Flow Bell shall sound upon activation of flow switch only. 4.-Flow Bell shall sound as long as water is flowing. 5. -Flow Bell shall not be capable of being silenced from FACP_ 6.- Indicate the location of the Waterflow switch bg displaying, in English, the alarmed devices and its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display. 1.- Transmit5 a Fire Alarm signal to the Listed Central Station by way of digital telephone dialer. D.- FIRE ALARM TAMPER SWITCH DETECTORS Activation of the Fire Alarm Tamper Switch Detector shall Initiate the following functions: I.- Generate an audible supervisory signal at the Fire Alarm Control Panel and at the Remote Annunciator Panel. 2.- Indicate the location of the Tamper Switch Detector by displaying, in English, the alarmed devices and its location on the FACP alphanumeric display and on the Remote Annunciator alphanumeric display . 3.-Transmits a Fire Supervisory signal to the Listed Central Station by way of digital telephone dialer. E.- FIRE ,4LLRr1_ELE-VAIoRpOZLRDl -5C-014NEC.T -($HUT TRIE)_ / (Activation of the Fire Alarm Heat Detector at Top of the shalt or Elevator Machine Room shall llnitiate the following functions: 1.- Generate an audible alarm signal at the Fire Alarm Control Panel and at the Remote Annunciator Panel. 2.-Generate an audible alarm signal simultaneosuly on all areas of the building by means of Horn and Horn /Strobe devices. Generate a visual alarm signal simultaneosuly on all areas of the building by the use of strobe devices or combination Horn/Strobe notification devices. 3.- Indicate the location of the Heat detector by displaying, in English, the alarmed devices and Its location on the FACP alphanumeric display. 4.-Initiate Control Relay to disconnect power to Elevator (shunt trip) 5. -Power for control circuit of shunt trip shall be monitored for integrity and upon loss of power shall initiate a supervisory signal at main panel to comply with NFPA 12 2002 edition 6 -15AA 6: Transmits a Fire Alarm signal to the Central Station by way of digital telephone dialer. II: A trouble shall be annunciated upon any abnormal condition failure or removal of any devices. III: A break in any field wiring or grounding of any coductor will result in the activation of the trouble buzzer, which can be silenced at the panel trouble silenced button. IV.- Any subesquent Alarm after system has been silenced shall resound Notification appliances. V: Upon Alarm, Supervisory or Trouble signals initiation panel will transmit Listed Central Station by way of digital telephone dialer_ ADA HEIGHT REQUIREMENT IL74L STROBE OR O SO' AFF. TO BORON OF LENS FIORN / STROBE O OR W BELOUI CELING O (UMICHEAR B Lam PLLL STATION O 48' AFF. p FIRE PENETRATION DETAIL Through penetration firestop System System No. W -L -12% July 0% 1003 F. Ratklg - Ill 4 2Hr T. Rating - 0 4 1/4 Fk A Section A -A 1.- Wall Assembly - The I or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the material and in the manner described in the individual U300 or U400 Series wall or partition design in the UL. Fire Resistance Directory and shall include the following construction features: A. Stud - Wall framing may consist of either wood stud or steel channel stud. Wood stud to consist of nom 2 in. bg 4 in. lumber spaced 16 in. cc. Steel stud to be min. 3 -1/2 in. wide spaced max. 24 in. CC. B. Gypsum board - The gypsum board type, thickness, number of layer, fastener type and sheet orientation shall be as specified In the Individual U300 or U400 Series Design In the U.L. Fire Reslstence Directory. Max. diam. of opening is 10 -5/8 in. The hourly F rating of the firestop system is equal to the hourly fire rating of the wall assembly in which It is installed. The hourly T rating is 0 and 1/4 Hr for I and 2 Hr rated assemblies, respectively. 2.- Through Penetrants - One metallic pipe, conduit, tubing or flexible metal pipe Installed concentrically or eccentrically within opening. Annular space between penetrant and periphery of opening or sleeve shall be min. of 0 in (point contact) to max. 2 in. Penetrant to be rigidly supported on both sides of wall. The following types and sizes of penetrants may be used: A.- Steel Pipe- Nom 8 in. diam (or smaller) schedule 5 for heavier) steel pipe. B.- Iron Pipe- Nom 8 In. diam (or smaller) cast or ductile iron pipe. C.- Conduit- Nom 4 In. diam (or smaller) steel electrical metallic tubing (EM.T.) or nom. ro in. rigid steel conduit. D.- Copper Tubing - Nom 4 in. diam (or smaller) Type L (or heavier) Copper tubing. E.- Copper Tubing - Nom 4 in. diam (or smaller) Regular (or heavier) Copper pipe. F.- Through Penetrating Product - Flexible metal piping - The following types of steel flexible metal gas piping may be used: 1. Nom. 2 in. diam. (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both skies of floor or wall assembly. OMEGA FLEX INC. 2. Nom. 1 in. diam. (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. TITEFLEX CORP. A BUNDY CO. 3. Nom. 1 in. diam. for smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. WARD MFG INC. 3.- Fill, Void or Cavity materials- - Caulk - Min. 5/8 in. thickness of caulk applied within the annulus, flush with both surface of wall min 114 in. diam. bead of caulk applied to gypsum board /penetrant interface at point contact location on both sides or wall. 3M COMPANY - 1C15WB or CP 25WB- - Bearing the U.L. Classification Mark SMOKE DETECTOR MOUNTING DETAIL I= CEILING 5110KE DETECTOR 3' MN. M1 A/C DIFUSER LEVEL 25' -0" FLOOR PLAN Scale %s" =V -0" LEGEND FIRE PENETRATION qEWL - - - Through penetration firestop System - System No. C -AJ -1421 July 05, 2003 F. R "t'ng ;1­;r T QM­ OW1 1: Floor or Wall Assembly - min 2 - 1/2 in.Thick reinforced lightweigth or normal weight (100 -150 pcf) concrete floor or min. 3 in.thick reinforced lightweight or normal weight concrete wall. Floor assembly may also be constructed of any min 6 in. thick U.L. Classified hollow-core Precast Concrete Units. Wall may also be constructed of any U.L. Classified Concrete Block. Max. diam. of opening 12 -3/4 in. Max. diem openlnig in floor constructed of hollow -core concrete is 1 in. See Concrete Block (CAZT) and Precast Concrete Unit (CFTV) categories in Fire Resistences Directory for names of manufacturers. IA.- Steel Sleeve (optional)- Nom. 12 in. diam. (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted Into floor or wall assembly. Steel sleeve may be installed flush or may project max. 2 in beyond the floor or wall surface. 2.- Through Penetrants - One metallic pipe, conduit, tubing or flexible metal piping installed concentrically or eccentrically within opening. Annular space between penetrant and periphery of opening or sleeve shall be min. of 0 in (point contact) to max. 2 in. Penetrant to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of penetrants may be used: A.- Steel Pipe- Nom 10 in. diam (or smaller) schedule 10 (or heavier) steel pipe. B.- Iron Pipe- Nom 10 in. clam for smaller) cast or ductile Iron pipe. C.- Conduit- Nom ro in. diam for smaller) steel condult or nom. 4 in. diam. (or smaller) steel electrical metallic tubing. D.- Copper Tubing - Nom 4 In. diam (or smaller) Type L (or heavier) Copper tubing. E.- Copper Tubing - Nom 4 in. diam for smaller) Regular (or heavier) Copper pipe. F.- Through Penetrating Product - Flexible metal piping - The following types or steel flexible metal gas piping may be used: 1. Nom. 2 In. diam. (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. OMEGA FLEX INC. 2. Nom. I in. diam. for smaller) steel flexible metal gas piping. Plastic covering on Piping may or may not be removed on both sides of floor or wall assembly. TITEFLEX CORP. A BUNDY CO. 3. Nom. 1 in. diam. for smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. WARD MFG INC. 3.- Firestop system - The details of the firestop system shall be as follows: A.- Packing material - Min. 2 in. thickness of min 4 pcf mineral wool batt insulation firmly packed Into opening as a permanent form. Packing material to be recessed from top surface of floor or to edge of sleeve or from both surface of wall or both ends of sleeve as required to acommodate the required thickness of fill material. In floor constructed of hollow -core concrete, packing material to be recessed from top and bottom surface of floor or sleeve as required to accomodate the required thickness or fill material. B.- Fill, Void or Cavity materials- - Caulk - Min. 1/2 in. thickness of caulk applied within the annulus, flush with top surface of floor or top edge of sleeve or with both surfaces of wall or both ends of sleeves.ln floor construted of hollow -core concrete min. 1/2 In. thickness of caulk applied within the annulus, flush with top and bottom surfaces, of floor or sleeve. Min. 1/4 diam. bead of caulk applied to the penetrant/ /sleeve Interface at the point contact location on the top surface of floor or both surfaces of wall or hollo -core concrete. 3M COMPANY - 1C15WB or CP 25WB- - Bearing the U.L. Classification Mark. SYMBOL DESCRIPTION CATALOG. (GE - SEC.) FAC q Fire Alarm Control Panel. 1064 pqA Fire Alarm Remote Annunciator. RICD -C FA Remote Booster Power Supply 10Amps_ BPS -10A OIntelligent Photo Smoke Detector. Signature Series SIGA -PS 0 Manual Pull Station Signature Series 5I6A -210 Fx: 305 - 232 -15M2 Manual Pull Station Weatherproof MPSRi- SHTW -GE © Intelligent Fixed Temperature/Rate -of -rise Heat Detector. Signature Series SIGA -HRS ,SIN Control Relay Module. Signature Series SIGA -CR M❑ Single input Module. Signature Series SIGA CTI Reg.- P.E.- 005g451 Dual Input Module. Signature Series SIGA CT2 gWaterflow Switch Provided by others Tamper Switch Provided by others 2 Duct Detector Signature Series 616A SO I Genesis Strobe (Selectable 15, 30, 15, I10Cd output) GI -vM Genesis Horn- STrobe (Selectable 15, 30 15,110Cd out t) 1_ ifji,� Horn - Strobe Weatherproof 110001. 151 -BA -T WPQ Weatherproof Bell. 439D-6AUXR) -W End of the line. ILAN FIRE ALA S17fit nom Sr <CE. A C" `R 11Fk.ATE OR F�L/?C "' �'. ? ;st 6 >,1� E-2 POSTED AT FINIAL IN'aPE C1'NO'N, P?R NFPA 72 FIRE ALARM i SYSTEM TO BF. INSTALLED 1N f CCv'llANCE WITH NFPA 72; 7(4 101- �,A W i1111ii'11.01 �t -;_. �`�✓t�' ?')yh� tea:_. �o -..f`. .3::1 i DESWiNEIN Juan A. Rodriguez. Alarm System Contractor State Lic: EF- 0001235 124`1194 134 CT Unit 24 Miami, FL. 33186 Ph. 305- 9924284 Fx.- 305- 732 -6190 S"YOCI-iguezeaotzom CONSULTING: � s 4�rrT ililM ' - : 12491 5W 134 CT Unit 24 r- zip STATE U &M=r=L Miami, Fl. 33186 �t !, !; ` PINO CURT15 P.E. CORP. Ph: 305 - 232 - 6163 � -'. Alejandro E. Piro MiK1A�1Yj7�AT1L�M:rARTlrt Fx: 305 - 232 -15M2 :�� ' ' SON SOMERSET CHARTER 5CHOOL - Q Proffessional Engineer ` Reg.- P.E.- 005g451 Ns, DAN By @ 5OUTH MIAMI .State State Lic. #2'7283 B.J. 5616 5W 68th 5T I 03- 20 -200q South Miami, Florida 33143 ��,,t{ r v ' 14842 5W 34th Ln © 03 -20 -2001 (AS BUILT) J.R. A t , ,, Miami, FL. 33185 Boston Investors Grou ING p X03 -01 -01 j , ' ^'d ` 1J �' Ph: 305 -562 -8616 Fx305 -221 -3623 C/0 Miller Hamilton Snider 4 Odom E.D.V. I/8 " =1' -0" i l� ! ML pinocurtispe@beflsouth.net p p 1200 Brickel Ave 68th St. Ilth FI. Miami. Fl- - 33131 CL AP J. R. ��� �3