14-946-029HVAC NOTES 1.0 GENERA 1.1 PROVIDE ( FURNISH AND INSTALL ) ALL NECESSARY MATERIALS AND LABOR FOR A COMPLETELY OPERATIONAL AIR CONDITIONING, HEATING AND VENTILATING SYSTEM AS SHOWN ON THE DRAWINGS AND HEREIN SPECIFIED 1.2 INSTALL IN ACCORDANCE WITH THE FLORIDA BUILDING CODE 2010, ASHRAE, SMACNA, NFPA AND LOCAL ORDINANCES. 1.3 SCOPE OF WORK PROVIDE THE FOLLOWING COMPLETE SYSTEMS ; A. SUPPLY AND RETURN DUCT SYSTEM. B. EXHAUST SYSTEM FOR TOILET ROOMS, JANITOR CLOSETS & GARAGE. C. AIR CONDITIONING UNITS WITH REFRIGERANT PIPING AND CONTROLS FOR OFFICES. D. EMERGENCY GENERATOR EXHAUST PIPING & INSULATION. E. INDEPENDENT TEST AND BALANCE. 1.4 CONTRACTOR MUST BE FAMILIAR WITH THIS TYPE OF INSTALLATION AND THOROUGHLY UNDERSTAND ALL THE REQUIREMENTS FOR THE INSTALLATION OF EACH PIECE OF EQUIPMENT HEREIN SHOWN. ITS PROPER OPERATION REQUIREMENTS AND TESTING PROCEDURES FOR CITY APPROVALS. 1.5 PAY FOR ALL FEES, INSPECTIONS AND CONNECTION CHARGES REQUIRED 1.6 VERIFY AT JOB SITE ALL SPACE CONDITIONS, DIMENSIONS AND EQUIPMENT SIZES PRIOR TO DUCT FABRICATION OR INSTALLATION. COORDINATE REQUIREMENTS TO AVOID INTERFERENCE WITH OTHER TRADES. 1.7 NATURE OF DESIGN DRAWINGS: DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT INTEND TO SHOW EVERY FITTING, ELBOW, TRANSITION, ETC. THAT WILL BE NECESSARY FOR A COMPLETE OPERATIONAL SYSTEM AS REQUIRED BY THESE SPECIFICATIONS. 1.8 COORDINATION DRAWINGS: PREPARE 1/4" SCALE COORDINATION DRAWINGS SHOWING MAJOR SYSTEM COMPONENTS FOR A/E APPROVAL. 1.9 SUBMIT SHOP DRAWINGS FOR ARCHITECT / ENGINEER APPROVAL BEFORE PROCEEDING WITH THE PURCHASE OR INSTALLATION OF EQUIPMENT AND MATERIALS. SUBMIT AL AT ONCE IN A BINDER WITH AN INDEX AND DIVIDERS AS REQUIRED TO SEPARATE ALL DIFFERENT MATERIALS AND EQUIPMENT. 1.10 GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF ACCEPTANCE. 2.0 MATERIALS 2.1 DUCTWORK: ALL JOINTS SEALED WITH HIGH PRESSURE MASTIC. 2.1.1 GENERAL. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS. 2.1.2 DUCTWORK MATERIALS: A: GROUND FLOOR RETAIL SPACES: FIVE POUNDS DENSITY 1.5" THICK GLASS FIBER (R -6) DESIGNED, CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH SMACNA'S LOW PRESSURE DUCT MANUAL. ALL DUCT JOINTS SHALL BE SEALED AND TAPED. B: TOILETS ROOM EXHAUST AND FRESH AIR INTAKES: GALVANIZED SHEET METAL, CONSTRUCTED, AND INSTALLED ACCORDING TO LATEST EDITION OF SMACNA'S. LOW PRESSURE CONSTRUCTION STD. (0.5" W.G. SEAL ALL JOINTS WITH APPROVED FIRE RA D MASTIC. C: SECOND FLOOR OFFICE AREA: GALVANIZED SHEET METAL, CONSTRUCTED, AND INSTALLED ACCORDING TO LATEST EDITION OF SMACNA'S. LOW VELOCITY CONSTRUCTION STD. FOR 2" STATIC PRESSURE. INSULATE WITH 1-1/2" THICK FIBERGLASS BLANKET INSULATION WITH APPROVED FIRE & SMOKE REINFORCED ALUMINUM JACKET. D: ROUND INSULATED FLEXIBLE DUCT PROVIDE AS SHOWN ON PLANS, WIREMOLD WCK W 1-1/2" INSULATION & REINFORCED ALUM. VAPOR OR APPROVED EQUAL. MAXIMUM LENGTH PERMITTED PER RUNOUT = 5' -0" 2.1.3 DUCT INSULATION: (ALL A/C SUPPLY & RETURN) 1 -1 2" THICK, 1 -1/2 LB. DENSITY GLASS FIBER BLANKET WIT REINFORCED ALUMINUM FOIL VAPOR BARRIER. SEAL ALL JOINTS WITH APPROVED FIRE RATED MASTIC. 2.1.4 ACOUSTICAL LINING: (ALL A/C SUPPLY & RETURN) LINE FIRST 10 FT FROM UNIT WITH 1 THICK GLASS FIBER MATT FACED. PAINT WITH ANTIBACTERIAL COATING. ATTACH TO DUCT WITH APPROVED SMACNA PROCEDURE. 2.1.5 DUCTWORK ACCESSORIES: A. PROVIDE DOUBLE THICKNESS TURNING VANES AT ALL SQUARE ELBOWS. WHERE THE ELBOWS ARE RECTANGULAR INSTALL SINGLE THICKNESS INSTEAD. .1 ALTERNATE A: PROVIDE 3 -PIECE ELBOWS IN LIEU OF TURNING VANES FOR GLASS FIBER DUCTS ONLY. .2 ALTERNATE A: PROVIDE FULL RADIUS ELBOWS IN LIEU OF TURNING VANES. B. PROVIDE VOLUME EXTRACTORS BEHIND EACH SUPPLY OUTLET AND AT EACH DUCT BRANCH. 2.2 AIR DISTRIBUTION PRODUCTS : 2.2.1 PROVIDE SUPPLY AND RETURN GRILLES AND DIFFUSERS AS INDICATED ON THE DRAWINGS. 2.2.2 PROVIDE EXTRUDED ALL ALUMINUM AIR DISTRIBUTION PRODUCTS. 2.2.3 PROVIDE FINISHES AND TYPES OF MOUNT IN COORDINATION WITH THE CEILING TYPES AS SHOWN ON ARCHITECTURAL DRAWINGS. 2.2.4 PROVIDE OPPOSED BLADE, KEY OPERATED DAMPERS BEHIND ALL AIR SUPPLY OUTLETS. AIR DISTRIBUTION SCHEDULE YE5 No SYMBOL NECK SIZE MFGR. MODEL NUMBER REMARKS VOLUME DAMPER A SEE FL PLAN TITUS TDC -AA (2424 MODULE) S/A DIFFUSER YES ® SEE FL PLAN TITUS TDC -AA (12x12 MODULE) S/A DIFFUSER YES ® SEE FL PLAN TITUS 4F (24x24 MODULE) R/A GRILLE NO ¢ EXTERNAL STATIC PRESSURE. IN. OF WATER 0.50 0.50 0.50 L- NOTES: 2.78 / 913 2.78 / 913 1. REFER TO PLAN FOR QUANTITY, LOCATION, AIR THROW PATTERN AND SIZES. HP FLA 2. ALL AIR DISTRIBUTION DEVICES SHALL BE OF EXTRUDED ALUMINUM CONSTRUCTION, FURNISH WITH OPPOSED BLADE DAMPERS AND CONCEALED MOUNTING FRAME FOR ACOUSTICAL OR PLASTER CEILING INSTALLATION. 3,750 J 3. DIFFUSER COLOR SHALL BE WHITE BAKED ENAMEL STANDARD. 80/67 80/67 4. PROVIDE DIFFUSERS WITH MOLDED INSULATION BLANKET. o LEAVING AIR TEMP., aF DB WB 2.3 PIPING: 2.3.1 REFRIGERANT PIPING. SEAMLESS COPPER TYPE "L" AND HARD OR SOFT DRAWN ON ACR COPPER TUBING WITH WROUGHT COPPER BRAZED JOINT FITTINGS, WITH SILVER BRAZING CONTAINING NOT LESS THAN 49% SILVER. 2.4 NOT USED 2.5 INSULATION: 2.5.1 INSULATE ALL REFRIGERANT SUCTION PIPING WITH 3/4" CLOSED CELL POLYETHYLENE PRE MOLDED INSULATION, WITH AN APPROVED PIPE AND SMOKE JACKET. PAINT ALL EXPOSED INSULATION WITH TWO COATS OF WHITE LATEX PAINT. 2.5.2 NOT USED 2.5.3 INSULATE GENERATOR EXHAUST PIPE AND MUFFLERS WITH 1-1/2" CALCIUM SILICATE INSULATION. PROVIDE .016" THICK ALUMINUM JACKET. 2.6 ALL AIR CONDITIONING COMPRESSORS SHALL BE WARRANTED FOR A MINIMUM OF FIVE YEARS AFTER DATE OF ACCEPTANCE OF THE PROJECT. 2.7 CONTROLS: 2.7.1 GENERAL: PROVIDE THE NECESSARY AUTOMATIC CONTROLS FOR PROPER OPERATION OF ALL EQUIPMENT SPECIFIED HEREIN. FURNISH MAGNETIC STARTERS AND INTERLOCK WIRING INDICATED FOR EACH PIECE OF EQUIPMENT. 2.7.2 PUBLIC AREA DX EQUIPMENT: PROVIDE AIR CONDITIONING UNITS WITH PROGRAMMABLE MATCHING LOW VOLTAGE HEAT -COOL THERMOSTATS WITH ON -OFF AUTO SUB -BASE SWITCH, FURNISHED BY THE EQUIPMENT MANUFACTURER WITH HEAT -COOL STEPS AS REQUIRED. 2.7.3 CONTROL WIRING: PROVIDE (FURNISH & INSTALL) POWER SUPPLY WIRING SOURCE TO POWER CONNECTION, INCLUDE STARTERS, DISCONNECTS AND REQUIRED ELECTRICAL DEVICES, INTERLOCK WIRING, RACEWAY, CONDUITS, PULL WIRES AND EXPOSED CONDUITS FOR TEMPERATURE CONTROL SYSTEM. ALL WIRING SHALL RUN IN CONDUITS, NO EXCEPTION 2.7.4 CONTROL WIRING: PROVIDE (FURNISH & INSTALL) POWER SUPPLY WIRING SOURCE TO POWER CONNECTION, INCLUDE STARTERS, DISCONNECTS AND REQUIRED ELECTRICAL DEVICES, INTERLOCK WIRING, RACEWAY, CONDUITS, PULL WIRES AND EXPOSED CONDUITS FOR TEMPERATURE CONTROL SYSTEM. ALL WIRING SHALL RUN IN CONDUITS, NO EXCEPTION 2.8 STARTERS: PROVIDE MAGNETIC STARTER FOR ALL MECHANICAL EQUIPMENT IN THIS SECTION, OF TYPE DESCRIBED ON THE SCHEDULES WITH HAND - OFF -AUTO BUTTON POSITIONS ON THE COVER AND RED -GREEN PILOT LIGHTS. PROVIDE THE NECESSARY AUXILIARY OPEN AND CLOSED CONTACTS FOR THE INTENDED OPERATION AND INTERLOCKS. 2.9 IDENTIFICATION: 2.9.1 LABEL ALL EQUIPMENT WITH ENGRAVED BLACK PLASTIC PLAQUES 12 " x 4" HIGH WITH 1.5" LETTERS. 3.0 EXECUTION 3.1 INSTALL ALL EQUIPMENT AND MATERIALS IN STRICT ACCORDANCE WITH THE MANUFACTURER'S MANUALS AND RECOMMENDATIONS, PAYING SPECIAL ATTENTION TO REQUIRED CLEARANCES FOR INSTALLATION, OPERATION AND SERVICE. 3.2 SEAL ALL DUCT JOINTS WITH APPROVED FIRE AND SMOKE RATED HIGH PRESSURE MASTIC. • 01 THERMOSTAT LOCATION IS CRITICAL TO PROPER EQUIPMENT OPERATION. INSTALL THERMOSTAT AT LOCATIONS SHOWN ON PLANS. RELOCATE ONLY WHEN APPROVED BY THE A/E IN WRITING. 3.4 WHERE R/A IS PROPOSED BY WAY OF DOOR UNDERCUTS, PROVIDE A MINIMUM 1" CLEAR SPACE BETWEEN THE BOTTOM OF THE DOOR AND THE FLOOR FINISH CARPET OR TILE. 3.5 EQUIPMENT MUST OPERATE FREE OF OBJECTIONABLE NOISE AND VIBRATION REPAIR AND/OR REPLACE ALL SOURCES OF NOISE AND VIBRATION FOUND TO BE OBJECTIONABLE, TO THE SATISFACTION OF THE A /E. 3.6 BALANCE ALL SYSTEMS TO PROVIDE AIR QUANTITIES AND CAPACITIES TO MATCH SPECIFIED FLOWS & CAPACITIES. NOTIFY A/E OF ANY DEFICIENCIES NOTED DURING TESTING & BALANCING CALIBRATE FLOWS TO NEW EQUIPMENT PER MANUFACTURER'S REQUIREMENTS. BEFORE COMPLETING TEST & BALANCE PROCEDURES. ALLOW NECESSARY TIME FOR IMPLEMENTING PROPOSED SOLUTIONS BEFORE CONTINUING WITH TEST & BALANCE. AT END OF TEST AND BALANCE ISSUE A COMPLETE REPORT FOR A/E APPROVAL AND ALLOW TIME AND PROVIDE NECESSARY INSTRUMENTS FOR SPOT CHECKING WITH A /E. SUBMIT FINAL TEST AND BALANCE REPORT TO A/E FOR ACCEPTANCE. AIR QUANTITIES SHOWN ARE TO BE ADJUSTED AS REQUIRED TO MEET SPECIFIC JOB CONDITIONS. 3.9 STRICTLY FOLLOW ALL MANUFACTURER'S INSTALLATION MANUALS AND INSTRUCTIONS IN THE INSTALLATION OF ALL EQUIPMENT. OBTAIN, FROM EACH MANUFACTURER, PROPER CERTIFICATION FOR THE ADEQUACY OF THE INSTALLATION OF ALL PIECES OF EQUIPMENT BEFORE PLACING SYSTEM IN OPERATION. 3.10 PROVIDE MAINTENANCE AND OPERATION MANUAL 3.11 PROVIDE AS -BUILT REPRODUCIBLE DRAWINGS. 3,12 PROVIDE INSTRUCTION TO OWNER'S DESIGNATED PERSONNEL. HVAC DE51GN REQUIRE5: YE5 No DUCT SMOKE DETECTOR (EXISTING) x AREA SERVED: FIRE DAMPER(S) SEE FL PLAN x SMOKE DAMPER(S) PACKAGE x FIRE RATED ENCLOSURE REFRIGERANT TYPE x FIRE RATED ROOF /FLOOR CEILING ASSEMBLY 410A x FIRE STOPPING (EXISTING) x 4,500 SMOKE CONTROL DIRECT x PACKAGED A/C UNIT SCHEDULE UNIT DESIGNATION RTU -1, RTU -2 (EXISTING) RTU -3 (EXISTING) RTU -4 (EXISTING) AREA SERVED: SEE FL PLAN SEE FL PLAN SEE FL PLAN UNIT TYPE PACKAGE PACKAGE PACKAGE REFRIGERANT TYPE 410A 410A 410A FAN TYPE TOTAL AIR CFM 4,800 4,500 3,750 DIRECT OUTSIDE AIR CFM SEE 0/A CALCULATIONS SEE 0/A CALCULATIONS SEE O/A CALCULATIONS ¢ EXTERNAL STATIC PRESSURE. IN. OF WATER 0.50 0.50 0.50 L- FAN BHP /RPM BHP /RPM 2.78 / 913 2.78 / 913 2.78 / 913 OPENING REQUIRED IN. HP FLA -/ 10.0 A -/ 10.0 A -/ 10.0 A 60.5 Watts DESIGN AIR FLOW CFM 4,800 4,500 3,750 J ENTERING AIR TEMP., OF DB /WB 80/67 80/67 80/67 o LEAVING AIR TEMP., aF DB WB GC -124 GC -124 GC -142 a: FACE VELOCITY FPM (MAX) 500 500 500 1.2 TOTAL CAPACITY BTU /HR. SENSIBLE CAPACITY BTU /HR. 148,000 103,800 148,000 103,800 148,000 103,800 -- REHEAT COIL CAPACITY BTU /HR. NOTES: 1. EF -1 SHALL BE INTERLOCKED TO TOILET ROOF LIGHT FIXTURE. FOR NUMBER OF FANS REFER TO FLOOR PLAN. 2• EF -2 SHALL BE PROVIDED WITH ON /OFF SWITCH. 3. EF -3 INTERLOCKET WITH THERMOSTAT CONTROL JTYPE & THICKNESS TAWAY 2' TAWAY 2' TAWAY 2' L`• FACE AREA. SQ. FT. (MIN) -- -- -- OPERATING WEIGHT L.BS. 1380 1380 1380 w NO. OF COMPRESSORS 2 2 2 N CAPACITY REDUCTION PERCENT EACH 0 -50 -100% 0 -50 -100% 0 -50 -100% vi COMPRESSOR RPM (MAX) - -- - -- - -- � MOTOR POWER INPUT. KW (MAX) o 61COMPRESSOR FLA /LRA 19- 22.4/123 -149 19- 22.4/123 -149 19- 22.4/123 -149 (A NO. OF FANS 1 1 1 Q H P EA. / FLA EA. 6.2 A 6.2 A 6.2 A o TYPE PROPELLER PROPELLER PROPELLER 0 AMBIENT AIR TEMPERATURE "F 95 95 95 ELECTRICAL SERVICE AVAILABLE 208/3/60 208/3/60 208/3/60 ELECTRICAL HEATER - TOTAL KW STEPS 7.8 KW 7.8 KW 7.8 KW E2 ROOF CURB YES YES YES U Q VIBRATION ISOLATION TYPE INTERNAL INTERNAL INTERNAL M.C.A. / MOCP 54.6/70.0 54.6/70.0 54.6/70.0 MINIMUM EER 11.2 11.2 11.2 MODEL NO. TCD14A2B5 TCD14A2B5 TCD14A2B5 DESIGN MANUFACTURER CARRIER CARRIER CARRIER NOTES: 1. PROVIDE ALL RTU'S WITH OUTSIDE AIR HOODS 2. ALL UNITS SHALL BE PROVIDED WITH SINGLE POWER CONNECTION 3. ALL UNITS SHALL HAVE VERTICAL DISCHARGE. 4. ALL PACKAGE ROOFTOP A/C UNITS TO BE PROVIDED WITH 14 INCH HIGH ROOF CURBS. 5. PROVIDE AUXILIARY DRAIN PAN WITH FLOW SWITCH TO STOP THE UNIT AND AVOID OVERFLOW. FAN SCHEDULE UNIT NUMBER EF -1 EXISTING EF -2 EXISTING EF -3 NEW AREAS SERVED TOILET RM. JANITOR CLOSET IT ROOM LOCATION CEILING CEILING CEILING DUTY SUPPLY /EXH EXH. EXH. EXH. FAN TYPE CENT. CENT. CENT. DRIVE BELT /DIRECT DIRECT DIRECT DIRECT FAN SPEED RPM 900 900 1000 AIR QUANTITY CFM 77 77 84 TOTAL STATIC PRESS. H2O 0.25 0.25 0.25 OPENING REQUIRED IN. -- -- -- FAN MOTOR HP 60.5 Watts 60.5 Watts 56.2 Watts ELECTRICAL CHAR. V /0 /60 120/1/60 120/1/60 120/1/60 MANUFACTURER COOK COOK COOK MODEL NUMBER GC -124 GC -124 GC -142 WEIGHT LBS. 13 13 15 REMARKS SONES 1.2 1.2 1.9 ROOF CURB -- -- -- NOTES: 1. EF -1 SHALL BE INTERLOCKED TO TOILET ROOF LIGHT FIXTURE. FOR NUMBER OF FANS REFER TO FLOOR PLAN. 2• EF -2 SHALL BE PROVIDED WITH ON /OFF SWITCH. 3. EF -3 INTERLOCKET WITH THERMOSTAT CONTROL PROVIDE 4-18 go - 1 1/8" WIDE HURRICANE STIMPS PER CONDENSING UNIT. a.) 2 -3/8" X 3/4" LONG A307 STEEL GAL DOLTS AND NUTS FASTENED TO WEB OF ALUMINUM STAND RAIL --� Xx3/4• RUBBER NEOPRENE PA BY A/C CONTRACTOR - EXAMPLES: RUBBER VIBRATION PAD 4 7x47xt/4" GALV. STEEL. PLATE ANCHORED TO ROOF STRUCTURAL WITH 2 -3/18- GALVANIZED STEEL BOLTS THRU DECK WITH WASHERS AND NUTS. (TYP) 1/4" x 314" GALVANIZED STEEL " 1 -1/4 x 1- 1/4• x 3/32" THUMBSCREW TIGHTEN WITH TORQUE WRENCH N 1 -5/18" GALVANIZED STEEL BOLT & NUT. V x 1' x 3/32" 1 -1/2 x 1- 1/2• x 1 /e- Im: 1 ALL CONSTRUCTION TO MEET ALUMINIUM ASSOCIIICUUION SPECIFICATIONS. 2.- BASE AS MANUFACTURED BY MIAMI TECH INC. 3.- BASE TO HAVE DADE COUNTY PRODUCT CONTROL APPROVAL ROOFTOP EQUFMIE1Ji HEM InUHB]1ENIS T"DU T Ea>PMENr r � LEA PRODUCT CONTROL NUMBER 2255' TTO23r Ir NOA No. 13- 1017.09 37'10 48' 24' 4V TO W 30' 81' AM WM 48' CONDENSING UNIT ROOF DETAIL "M O/A CALCULATIONS (BASED ON A.S.H.R.A.E. 62) �` SQ. FT. (NET)* 0/A REQUIRED CFM REQUIRED A/C UNIT CFM DESIGNED OFFICE AREA SECOND FLOOR 12,966 5 PERSONS }!� CFM /0.06 CFM 1000 S.F. /� PERSON) +( 1.103 RTU -1, RTU -2 RTU -3 do RTU -4 RTU -1 500 CFM RTU -2 500 CFM SQ. FT. (EXISTING) RTU -3 (500 CFM) RTU -4 (500 CFM) SOUND INSULATED HOUSING - ADJUSTABLE MOUNTING FLANGE REMOVABLE ALUM. CEILING GRILLE NX�'w- I :" I ' i err AIR FLOW TYP. CEILING TYPE EXH. FAN DETAIL N.T.S. :� AIR `- EXHAUST CENTRIFUGAL FAN INSIDE HOUSING .r - i . • i ta► n► RATW 3 it W r � ! rr� AS HANGER STRAP i. r �! snW HANGERS I, wx MAX. UPPER and LOWER HANGER ATTACHMENTS and DEVICES 1-1/2- PVC SCH. 40 SLEEVE (TYP.) REFRIGERANT PIPES - -� 8• MIN. PIPE SUPPORT w w ^^ +�...�� o a v a C. `n to >gz ai z � <0 0 W " Zip W era¢ -zr M 41nD z o cci .°� �Z °ate Cc ru YO_ vz-- u'°-�i iQ Go mow! x- WXWd'ZW �iWUZ�z Fri r � cy � w A � �Nzwz, V1 � -F Ti p� ®zz' wa z W J 0 W Q w�gOOg =�UVag .ri rya gQi -a .r2 owa.wo BOLT, SCREW OR WELD RUNNER TO DUCT VANES AND VANE RUNNERS DETAIL N.T.S. CONCRM ANCHOR PRECAST JOIST x'31 »>lc;n�: ►'� h1JmT -'$uw 13!m 4 CONCRETE ANCHORS MANUFACTURED CONCRETE INSERTS HANGER STRAP HANGER ROD ALTERNATE POWER ACTUATM STUDS INTO STEEL RETAINING CUP --- HANGER ROD STRUCTURAL OR DECK NUi�( 6a C -CLAMP W/ RETAINING CUP HANGER STRAP ppJ 6a C --CLAMP W/ LOCK NUT (OPTIONAL) y WELDED STUDS GALVANIZED SHEET METAL COWL FILL WITH FOAM INSULATION (TYP.) TYPICAL SUPPORT BETWEEN FLOORS AT 8' -0. 0/C VERTICALLY II 12" CURB ROOFING l.d REFRIGERANT PIPE CHASE IN PARTTTION REFRIGERANT PIPING COWL DETAIL N.T.S. NOTES, DETAILS & SCHEDULES - HVAC SCALE: N.T.S. 1 1/e X 26 GA GALV. STEEL HANGER STRAP (5" O.C.) AIR DUCT (SEE PLAN VIEW) LOW FRICTION LOSS BRANCH TAKE -OFF FITTING METAL ROUND FITTING QUADRANT OPERATOR TO BE OUTSIDE INSULATION PROVIDE INSULATION GUARD WHERE NECESSARY SEAL JOINT W/ DUCT SEALER AND 6' MAX. TAPE AIR FLOW ,a INSULATE TOP OF DIFFUSER. DIFFUSER W/ OPPOSED BLADE DAMPER ADAPTOR ROUND TO SQUARE IF REQUIRED IT, W1163 y�. INSULATED FLEX. DUCT -BAND OF SAME SIZE AS HANGER STRAP SEAL JOINT WITH DUCT SEALER AND TAPE FLEXIBLE DUCT CONNECTION DETAIL N.T.S. s, d 1 i 1 SMACNA ICS IIIIIM 111=111 111=111 mm 111=111 111=111� = =� 1-1/2- PVC SCH. 40 SLEEVE (TYP.) REFRIGERANT PIPES - -� 8• MIN. PIPE SUPPORT w w ^^ +�...�� o a v a C. `n to >gz ai z � <0 0 W " Zip W era¢ -zr M 41nD z o cci .°� �Z °ate Cc ru YO_ vz-- u'°-�i iQ Go mow! x- WXWd'ZW �iWUZ�z Fri r � cy � w A � �Nzwz, V1 � -F Ti p� ®zz' wa z W J 0 W Q w�gOOg =�UVag .ri rya gQi -a .r2 owa.wo BOLT, SCREW OR WELD RUNNER TO DUCT VANES AND VANE RUNNERS DETAIL N.T.S. CONCRM ANCHOR PRECAST JOIST x'31 »>lc;n�: ►'� h1JmT -'$uw 13!m 4 CONCRETE ANCHORS MANUFACTURED CONCRETE INSERTS HANGER STRAP HANGER ROD ALTERNATE POWER ACTUATM STUDS INTO STEEL RETAINING CUP --- HANGER ROD STRUCTURAL OR DECK NUi�( 6a C -CLAMP W/ RETAINING CUP HANGER STRAP ppJ 6a C --CLAMP W/ LOCK NUT (OPTIONAL) y WELDED STUDS GALVANIZED SHEET METAL COWL FILL WITH FOAM INSULATION (TYP.) TYPICAL SUPPORT BETWEEN FLOORS AT 8' -0. 0/C VERTICALLY II 12" CURB ROOFING l.d REFRIGERANT PIPE CHASE IN PARTTTION REFRIGERANT PIPING COWL DETAIL N.T.S. NOTES, DETAILS & SCHEDULES - HVAC SCALE: N.T.S. 1 1/e X 26 GA GALV. STEEL HANGER STRAP (5" O.C.) AIR DUCT (SEE PLAN VIEW) LOW FRICTION LOSS BRANCH TAKE -OFF FITTING METAL ROUND FITTING QUADRANT OPERATOR TO BE OUTSIDE INSULATION PROVIDE INSULATION GUARD WHERE NECESSARY SEAL JOINT W/ DUCT SEALER AND 6' MAX. TAPE AIR FLOW ,a INSULATE TOP OF DIFFUSER. DIFFUSER W/ OPPOSED BLADE DAMPER ADAPTOR ROUND TO SQUARE IF REQUIRED IT, W1163 y�. INSULATED FLEX. DUCT -BAND OF SAME SIZE AS HANGER STRAP SEAL JOINT WITH DUCT SEALER AND TAPE FLEXIBLE DUCT CONNECTION DETAIL N.T.S. s, d 1 i 1