14-885-001
rr tl O l P 1. -FIRE ALARM INITIAMh DEVIL A.-MANUAL FIRE ALARM eVLL UATIOn ACTIVATION OF ANY FIRE ALARM PULL STATION SHALL CAUSE THE FOLLOWING ACTION AND INDICATIONS: - ACTIVATE THE AUDIBLE AND VISUAL SIGNAL THROUGHOUT THE FACILITY. ACTIVATE THE ALARM LIGHT AND A DISTINCTIVE SOUND AT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATOR. ,; — INDICATE THE LOCATION OF THE PULL STATION BY DISPLAYING IN ENGUS14 THE ALARMED DEVICE ON THE FACP ALPHANUMERIC DISPLAY AND REMOTE ANNUNCIATOR. : — TRANSMITS A FIRE ALARM SIGNAL TO THE DESIGNATED LISTED CENTRAL STATION BY WAY OF DIGITAL ALARM COMMUNICATOR. B.— AUTOMATIC FIRF DFTFrTewcz (SMOK D TORc} ACTIVATION OF ANY AUTOMATIC FIRE DETECTION DEVICE SHALL CAUSE THE FOLLOWING ACTION AND INDICATIONS- - ACTIVATE THE AUDIBLE AND VISUAL SIGNAL THROUGHOUT — ACTIVATE THE ALARLIGHT AND SOUNDER AT THE FIRE ALARM CONTRCC. PANEL AND REMOTE ANNUNCIATOR. — INDICATE THE LOCATION OF THE AUTOMATIC DETECTOR BY DISPLAYING IN`ENGUSH, THE ALARMED DEVICE ON "THE FACP ALPHANUMERIC DISPLAY AND REMOTE ANNUNCIATOR. — TRANSMITS A FIRE ALARM SIGNAL TO THE DESIGNATED LISTED CENTRAL $ TATION BY WAY OF DIGITAL ALARM COMMUNICATOR. 2.— SUPERVISORY ALARM INITIATING DE4" Fc A. —DUCT DE TOR ACTIVATION OF ANY DUCT DETECTOR SHALL AUTOMATICALLY INITIATE THE FOLLOWING FUNCTIONS: — ACTIVATE THE SUPERVISORY LIGHT AND A DISTINCTIVE SOUND AT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATOR. — INDICATE THE LOCATION OF THE DUCT DETECTOR BY DISPLAYING IN ENGU$H THE ACTIVATED DEVICE ON THE FACP ALPHANUMERIC DISPLAY AND REMOTE ANNUNCIATOR. TRANSMITS A SUPERVISORY ALARM SIGNAL TO THE DESIGNATED LISTED CENTRAL STATION BY WAY OF DIGITAL ALARM COMMUNICATOR. B. -FM R EN Y "wFRATOR ACTIVATION OF ANY EMERGENCY GENERATOR SIGNAL (GENERATOR COMMON TROUBLE, GENERATOR RUNNING, SELECTOR NOT IN AUTO POSITION AND FUEL TROUBLE) SHALL AUTOMATICALLY INITIATE THE FOLLOWING FUNCTIONS: - ACTIVATE THE SUPERVISORY LIGHT AND A DISTINCTIVE SOUND AT THE FIRE -ALARM CONTROL PANEL AND REMOTE ANNUNCIATOR. - INDICATE THE EVENT TYPE ON THE FACP ALPHANUMERIC DISPLAY AND REMOTE ANNUNCIATOR. - TRANSMITS A SUPERVISORY ALARM SIGNAL TO THE DESIGNATED LISTED CENTRAL STATION BY WAY OF DIGITAL ALARM COMMUNICATOR. NOTE: NOTIFICATION APPLIANCES WILL NOT BE ACTIVATED. 3. -TROUB E gGNA S ' A. -MALI_ tJ FlR� A ARM ONTR PAN I THE OCCURRENCE OF ANY TROUBLE IN THE SYSTEM SHALL CAUSE THE FOLLOWING ACTION AND INDICATIONS: - ACTIVATE THE TROUBLE LIGHT AND A DISTINCTIVE TROUBLE SOUND AT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATOR. - DISPLAY THE TROUBLE - TRANSMITS A TROUBLE SIGNAL TO THE DESIGNATEDALISTEDUCENTRALSSTA ON By REMOTE OF D IGITAL AALARM COMMUNICATOR, 4, NOTE: TROUBLE SIGNALS AND THEIR RESTORATION TO NORMAL SHALL BE INDICATED WITHIN 200 SECONDS. -FARE SAFETY tN/`?tnNc A. =AHU SHUTDOWN - DUCT DETECTOR SHALL AUTOMATICALLY STOP THEIR RESPECTIVE AIR HANgLER UNIT ON DETECTING THE PRESENCE OF SMOKE. B.- ELEVATOR RECaII ACTIVATION OF THE AUTOMATIC DETECTOR IN ELEVATOR LOBBIES AND ELEVATOR)i MACHINE ROOM SHALL AUTOMATICALLY INITIATE THE FOLLOWING FUNCTIONS: L — INITIATE AN ALARM CONDITION IN THE BUILDING FOR EVACUATION PURPOSES. — INDICATE THE LOCATION OF THE AUTOMATIC DETECTOR BY DISPLAYING IN ENGLISH, THE ALARMED DEVICE ON THE FACP ALPHANUMERIC DISPLAY AND REMOTE ANNUNCIATOR. I — INITIATE THE AUTOMATIC RECALL OPERATION AS FOLLOWS: 1 =PRIMARY ELEVATOR RECALL• ACTIVATION OF THE ELEVATOR LOBBY SMOKE�DETECTOR LOCATED ON 2ND FLOOR SHALL INITIATE PRIMARY RECALL WHICH WILL BRING THE ELEVATOR.CAR TO THE 1ST FLOOR AND LOCK THE DOORS IN THE OPEN POSITION. t 2— SECONDARY O&MATOR RECALL= ACTIVATION OF THE ELEVATOR LOBBY SMOKE DETECTOR LOCATED ON THE 1ST FLOOR AND /OR THE SMOKE DETECTOR LOCATED IN THE ELEVATOR MACHINE ROOM SHALL INITIATE RECALL WHICH WILL BRING THE ELEVATOR CAR TO THE 2ND FLOOR AND LPCK THE DOORS IN THE OPEN 3— ELEVATOR WARNIN IGHTS• ACTIVATION OF THE ELEVATOR MACHINE ROOI, SMOKE DETECTOR SHALL ALSO INITIATE THE ELEVATOR WARNING LIGHTS TO ALERT THE FIREFIGHTERS AND;: OTHER EMERGENCY PERSONNEL THAT THE ELEVATORS ARE NO LONGER SAFE TO USE. THE MAXIMUM TIME PERIOD FROM ACTUATION OF THE INITIATING DEVICE UNTIL INITIATION OF ALL RELATED FUNCTIONS AS LISTED ABOVE SHALL BE TEN SECONDS. FIRE ALARM NOTES 1 —FIRE ALARM SYSTEM SHALL BE U.L. LISTED AND NFPA 72 APPROVED AND COMPATIBLE. 2 —RISER INTERCONNECTIONS ARE DIAGRAMMATIC ONLY. 3 —TOTAL ACTIVE AREA: 43,413 SO. FT. 4—FIRE ALARM SYSTEM TO BE `POWER LIMITED ". 5 —THE INSTALLATION SHALL COMPLY WITH NFPA 70 CHAPTER 760. 6 —ALL WIRING AND CONDUIT SIZE SHALL BE IN ACCORDANCE WITH MANUFACTURER RECOMMENDATION, LOCAL CODES AND NFPA. 7 —ALL CONDUCTORS SHALL BE SOLID OR STRANDED COPPER. 8— MAXIMUM CONDUIT FILLS TO BE 40X. MINIMUM RACEWAY SIZE W. 9— SYSTEM SHALL BE GROUNDED ACCORDING TO MANUFACTURER SPECIFICATION AND NEC ARTICLE 250. 10 —ALL FIRE WALL PENETRATION SHALL BE MADE WITH APPROVED (NEC) ELECTRICAL TUBING AND SEALED WITH A U.L LISTED FIRE STOPPER. (SEE FIRE STOP DETAIL). 11 —THE 120V AC POWER FEED FOR THE FIRE PANEL MUST BE FROM A DEDICATED CIRCUIT AND THE BREAKER MUST BE IDENTIFIED FIRE ALARM CIRCUIT AND HAVE A LOCK ON IT. 12 —VISUAL ALARM PER ANSI A117.1 APPROVED. WALL MOUNTS 80" A.F.F. TO BOTTOM OF STROBE LENS. 13 —ALL NEW WIRING INSTALLED IN DUCTS, PLENUMS AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP, AS PER NEC (NATIONAL ELECTRIC CODE) ARTICLE 760 -61. 14—ALL N.A.C. WIRING SHALL BE CLASS "B" (STYLE "Y). SIGNALING LINE CIRCUIT WIRING SHALL BE CLASS "B" (STYLE "4 "). 15— HORN /STROBES SHALL BE LOCATED AS PER NFPA 72, CHAPTER 7. 16— STROBE LIGHT CIRCUITS SHALL BE SYNCHRONIZED AT 1HZ PER NFPA 72. 17— UNLESS OTHERWISE NOTED ALL CEILING HEIGHTS DO NOT EXCEED 10' -0" AND ALL CEILINGS ARE FLAT. 18— FURNITURE AND EQUIPMENT SHALL NOT EXCEED 72" IN HEIGHT WHERE PLACED ALONG THE PATH OF VISUAL SIGNALS. 19 —ROOM CONTAINING F.A.C.P AND POWER SUPPLY. IS MECHANICALLY 'VENTILATED. 20 —NEW SYSTEM IS CLASSIFIED AS CERTIFICATED FOR CENTRAL STATION` SERVICE PER NFPA 72 8.3. 21 —NEW FIRE ALARM DEVICES TO BE COMPATIBLE WITH NEW SYSTEM AND RATED FOR FIRE USE. 22 —THE SYSTEM SHALL HAVE BATTERY BACK UP FOR 24 HRS IN STANDBY MODE AND 5 MINUTES IN ALARM. 23 —THE MS- 92DOUDLS CONTAIN ONE SLC (SIGNALING LINE CIRCUIT) WHICH SUPPORTS UP TO 198 ADDRESSABLE DEVICES (99 DETECTORS AND 99 MONITOR OR CONTROL MODULES), 3.0 AMPS NAC POWER EXPANDABLE TO 6.0 AMPS WITH OPTIONAL XRM -24B. • ALARM • . (FIRST FLOOR) n SCOPE OF WORK: 1. FURNISH AND INSTALL NEW FIRE ALARM SYSTEM AS FOLLOWS: ga DESCRIPTION 1 FIRE ALARM CONTROL PANEL FIRE -UTE 1 REMOTE ANNUNCIATOR FIRE -LITE 1 REMOTE POWER SUPPLY FIRE-LITE 18 ADDRESSABLE SMOKE DETECTOR FIRE -UTE. 4 ADDRESSABLE DUCT DETECTOR WP FIRE -UTE 6 ADDRESSABLE PULL STATION FIRE -UTE 1 CONVENTIONAL PULL STATION WP FIRE-LITE 5 ADDRESSABLE MINI MONITOR MODULE FIRE -LIE 7 ADDRESSABLE RELAY MODULE FIRE -UTE 6 HORN /STROBE WALL MOUNT SYSTEM SENSOR 9 HORN /STROBE WP WALL MOUNT SYSTEM SENSOR 1 HORN /STROBE CEILING MOUNT SYSTEM SENSOR 12 STROBE LIGHT WALL MOUNT SYSTEM SENSOR 3 STROBE LIGHT WP WALL MOUNT SYSTEM SENSOR THE WORK TO BE DONE COMPLIES WITH THE FLORIDA FIRE PREVENTION CODE 2010 EDITION, NFPA 72 2DO7 EDITION AND NFPA 70 2008 EDITION. . .•r r . � r r 1 101 DIE 0,10 IN r REVISIONS FIRE ALARM LEGEND SYMBOL • Lo DESCRIPTION MANUFACTURER MODEL FAC FIRE ALARM CONTROL PANEL FIRE-LITE MS- 920OUDLS aal i REMOTE ANNUNCIATOR FIRE -LITE ANN -80 RPS REMOTE POWER SUPPLY FIRE -LITE FCPS -24FS8 SD ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR FIRE -LITE SD355 MD WP t • ADDRESSABLE DUCT DETECTOR WEATHER PROOF FIRE -LITE DNRW ® • ADDRESSABLE RELAY MODULE FIRE -LIE CRF -300 ® ADDRESSABLE MONITOR MODULE FIRE -LIE MMF -301 17-0-1 ADDRESSABLE PULL STATION FIRE -LITE BG -12LX ®WP r PULL STATION WEATHER PROOF FIRE -LIE BG -12LOB tB HORN /STROBE WALL MOUNT MULTI - CANDELA SYSTEM SENSOR P2R " EBWP , HORN /STROBE WEATHER PROOF SYSTEM SENSOR P2RK © STROBE LIGHT WALL MOUNT MULTI - CANDELA SYSTEM SENSOR SR ® WP STROBE LIGHT WEATHER PROOF SYSTEM SENSOR SRK H HORN /STROBE CEILING MOUNT SYSTEM SENSOR PC2R REVISIONS 7i • Lo i i r • • i i 0 fn 1 t • •' ILL i co Lo • rl i • i i t in i f r i • , s UJI 7i FlRE -LINK CORPORA110N CERTIFICATE OF AUTHORIZATION 30381 ENRIQUE PEREZ P.E. ELECTRICAL ENGINEER, FL REG. No.71404 10277 N.W. 128 TERRACE HIALEAH GARDENS, FLORIDA 33018 TEL: (786)449 -4354 Email: enrique.perez.201OOgmail.com lzlt� 1 WE V ILL L_j , •• • i 0 .. .a r FlRE -LINK CORPORA110N CERTIFICATE OF AUTHORIZATION 30381 ENRIQUE PEREZ P.E. ELECTRICAL ENGINEER, FL REG. No.71404 10277 N.W. 128 TERRACE HIALEAH GARDENS, FLORIDA 33018 TEL: (786)449 -4354 Email: enrique.perez.201OOgmail.com lzlt� 1 WE V