12-864-003PANEL NOTES OEXISTING BRANCH CIRCUIT AND CIRCUIT BREAKER TO REMAIN. O CONNECT NEW BRANCH CIRCUIT TO EXISTING SPARE BREAKER AS INDICATED. O ELECTRICIAN TO VERIFY THAT PANEL HAS ISOLATED GROUND BUS. BRANCH CIRCUIT SHALL HAVE ISOLATED GROUND. PROVIDE BRANCH CIRCUIT W/ A DEDICATED NEUTRAL AND DEDICATED ISOLATED GROUND CONDUCTOR. TO EXISTING UTILITI EXISTING BRANCH CIRCUIT PANEL "1L" (SECT 1) SCHEDULE VOLTS: 120 /240V WIRE 3 R.M.S. SYM: 10,000 NEMA TYPE: 1 MrR: EXISTING PHASE 1 AMP: 125 TYPE: MLO MOUNTING: RECESSED MODEL- EXISTING KVA EXISTING DISTRIBUTION PANEL DP -1 SERVICE: 120/24OV, MF'R: EXISTING MOUNTING: SURFACE 30, 4W CK'T# C.B. COND. AMP: 600 R.M.S. SYM: EXISTING TYPE: MLO COT N0. DESCRIPTION KVA KVA a- 0 AMP PROTECTION FEEDER REMARKS POLES FRAME C.B. 1 PANEL "C" - 12.0 V) 50 2 - 125 - AO 2 SPARE 3 4 - - - 2 - 15 - AO 3 PANEL "A" - 38.4 20 160.0 2 - 200 - AO 4 PANEL "B" 28.8 ELEC. RM. RECEP. 1 120.0 2 - 150 - AO 5 SPARE - - - - 2 - 35 - 0 6 SPARE 9 10 - - - 2 - 30 - AO 7 RTU -2 - - 12.5 20 30.0 3 - 50 - AO 8 RTU -4 T 10.4 SPARE - 3 - 40 - AO 9 SPARE - - - - 2 - 100 - AO 10 RTU -5 15 16 14.6 - 35.0 3 - 60 - 0 TOTAL 116.7 280.5 - NOTES O EXISTING FEEDER AND CIRCUIT BREAKER TO REMAIN. EXISTING BRANCH CIRCUIT PANEL "1L" (SECT 1) SCHEDULE VOLTS: 120 /240V WIRE 3 R.M.S. SYM: 10,000 NEMA TYPE: 1 MrR: EXISTING PHASE 1 AMP: 125 TYPE: MLO MOUNTING: RECESSED MODEL- EXISTING KVA CIRCUIT DESCRIPTION WIRE GND. COND. C.B. CK'T# C.B. COND. GND. WIRE CIRCUIT DESCRIPTION KVA EXISTING ACOUSTICAL CEILING AND SUSPENSION SYSTEM a- 0 ELEC. ROOM LGTS. 1 - - - 20 1 2 20 - - - REFRIGERATOR RECEP. 1 V) TO MATCH EXISTING (TYP.) 15 W of I 1.2 COPIER RECEP. 1 - - - 20 3 4 20 - - _ MICROWAVE RECEP. 1 NEW TV RECEP. 3 2 - - - 20 5 6 20 M 2 )RINKING FOUNTAIN RECE 1 Li toi =:% v ELEC. RM. RECEP. 1 - - - 20 7 6 1 20 - - - KITCHEN RECEP. 1 - a� B Q SPARE - - - 20 9 10 20 - - _ RECEPTACLES 1 o SPARE - - - 20 11 12 20 - - - SPARE s 2 W T SPARE - - - 20 13 14 20 - - - SPARE 1 Q - SPARE - - - 20 15 16 20 - - - SPARE 1 _ SPARE - - - 20 17 18 5 - - - WATER HEATER 1 F�+ - SPARE - - - 20 19 20 OFt$4AA SPACE - - - - 21 22 - - - - SPACE SPACE - - - - 23 24 - - - - SPACE L.IJ - SPACE - - - - 25 26 - - - _ SPACE _ U - SPACE - - - - 27 26 - - _ _ SPACE _ - SPACE � � o I - 129 30 - - - - SPACE - Uj ~ W 2.0 1,6 TOTAL TOTAL 4.0 4.4 z z TOTAL CONNECTED LOAD BY PHASE - PHASE A KVA = 6.0 AMPS = 50.0 PHASE C KVA = 6.0 AMPS = N� TOTAL = 12.0 TOTAL AMPS = Al I \IJLI\ SCALE: NTS EXISTING BUILDING GROUNDING ELECTRODE SYSTEM 1 ND PANEL SCHEDULE LEGEND. EXISTING TO REMAIN c I 0C 3' -0" . 2' -7" . 2' -7^ . 3' -0" 10" 10" ^ SEE FINISH PLAN NOTES ON E . 1 -4 SHEET A -1 TYP. 18 17 17 18 L� =� L_J ____j �:j 13 17 8' -5y" 16 co 101 N 10001, NNI 1-11, 18 ` EXTEND CABINET (ONE EXTEND CABINET (ONE DOOR) AS SHOWN. DOOR) AS SHOWN. MATCH EXISTING FINISH - MATCH EXISTING FINISH 15 15 15 8' -1 Oy" 11' -1y" 8' -1 Oy" 28 -11" TELLER LINE BACK COUNTER G� AND PLASMA TV MOUNTING HT'S SCALE: 1/4" = 1' -0" G5 I LLLLI \ LI M SCALE: l/4" = 1' -0" KEEP COUNTER TOP AS NEEDED AT BOTH SIDES EXIST. GYP. BD. WALL TO REMAIN CABINET TO BE REMOVED I >1 III k I I OLI TI ON PNL -B MP PNL -C PNL -A 10 30 10 10 150A 600A 125A 200A ELECTRICAL ROOM / PANEL INFORMATION R E m 11'_03/q VIDEO @ gFSCALE- E R A Ro A 1It r r r W U O I tV = I W w � , 2 L PLASTIC LAMINATE CLAD END PANEL (N.I.C.) C7 PLASTIC LAMINATE CLAD WOOD BASE (N.I.C.) 4 1 i 0• 5 z 6 z W U z EXISTING ACOUSTICAL CEILING AND SUSPENSION SYSTEM a- 0 z 9 FLAT -PANEL TELEVISION (N.I.C.) w co Uw O 12 _j En U W 0 EXISTING PLASTIC- LAMINATE -CLAD BACKSPLASH - U 1 V) TO MATCH EXISTING (TYP.) 15 W of I N �N U PORTION OF EXISTING CABINET TO REMAIN - REWORK TO MATCH EXISTING Id LL_ 0= LLJ X� NEW GYPSUM BOARD WALL TO BE PAINTED TO MATCH EXISTING N O Oaw ch o) S.. 0 �r. � O H- M 2 m 11'_03/q VIDEO @ gFSCALE- E R A Ro A 1It r r r A FLAT PANEL TELEVISION (NIC) B VIDEO MONITOR WALL MOUNTING BRACKET (N.I.C.) C BASE TO MATCH EXISTING D PLYWOOD SHEATHING E NEW %" GYPSUM WALL BOARD F NON STRUCTURAL METAL STUD FRAMING, BRACE TO STRUCTURE ABOVE EVERY OTHER STUD. G NON STRUCTURAL METAL STUD FRAMING H ALIGN I STUD BRACE Ljj LOCATE (6) 2X4 J -BOXES FOR POWER /DATA ORIENT RECEPTACLES HORIZONTALLY. COORDINATE LOCATIONS WITH VIDEO MONITOR MFR. ELECTRICAL RENOVATION NOTES THE SCOPE OF ECTRICAL WORT( SHALL INCLUDE IT IS NOT LIMITED TO THE FOLLOWING. 1. ELECTRICAL CONTRACTOR SHAD MAKE A THOROUGH SURVEY OF EXISTING CONDITIONS & OF THE ELECTRICAL SYSTEM To FAMILIARIZE HIMSELF, IN ORDER TO INSTALL THE NEW ELECTRICAL SYSTEM PROPOSED, PRIOR To BD /CONSTRUCTION. ELECTRICAL CONTRACTOR SHALL IDENTIFY ALL THE BRANCH CIRCUITS BEING FED FROM EXISTING PANELS 2. ALL EQUIPMENT SCHEDULED TO BE REUSED, SHALL BE RECONDITIONED To LIKE NEW. IF COST TO REPAIR OR RECONDITION EXCEEDS NEW COST , THEN THE EQUIPMENT SHALL BE REPLACED. 3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR RECONNECTING ALL ELECTRICAL EQUIPMENT N ORDER TO HAVE A COMPLETE WORKING JOB, WHETHER OR NOT THE EQUIPMENT ON THE NEW PLANS. 4. DUE TO THE NATURE OF THIS PROJECT, THE ELECTRICAL CONTRACTOR MUST CHECK OUT ALL EXISTING CIRCUITS STARTING AT THEIR DISTRIBUTION POINTS IN ORDER TO SEE IF THEY ARE STILL. ALIVE. 5, WHEN INSTALLING NEW EQUIPMENT, THE ELECTRICAL CONTRACTOR SHOIJ D USE EXISTING CONDUITS AND AVAILABLE CIRCUITS IF POSSIBLE ALL REUSED CIRCUIT BREAKERS, OUTLETS, SWITCHES, ETC., SHALL BE INSPECTED AND REPLACED AS NEEDED. 6. ALL ELECTRICAL EQUIPMENT REMOVED SHALL BE KEPT IN A SECURE AREA UNTIL OWNERS DECIDE WHAT TO DO WITH IT. 7. THE ELECTRICAL CONTRACTOR SHALL NOT OVERLOAD ANY EXISTING PANEL BOARDS OR FEEDERS AND SHALL NOT EXCEED BOx OF THEIR RATED VALUE B. ELECTRICAL CONTRACTOR SHALL VERIFY ALL ELECTRICAL REQUIREMENTS FOR ALL EQUIPMENT PRIOR TO INSTALLATION. 9. ELECTRICAL CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO BID AND INSTALLATION, INFORM THE ENGINEER OF RECORD OF ANY DISCREPANCY BETWEEN THE DOCUMENTS AND THESE CONDITIONS AND HE SHALL INCLUDE IN HIS BID TO CORRECT THE SAME AS DIRECTED. THE ENGINEER AND THE ARCHITECT ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER THE CONTRACT HAS BEEN AWARDED. 10. THE INTENT OF THE ELECTRICAL DESIGN IS TO UTILIZE AS MUCH OF THE ELECTRICAL EQUIPMENT AS POSSIBLE, THEREBY ELIMINATING EXCESSIVE COST, CONSTRUCTION, AND TIME 11. ELECTRICAL CONTRACTOR SHALL KEEP AS -BOLTS AND SUBMIT TO ENGINEER OF RECORD FOR RENEW. ALL CHANGES SHALL BE FORWARDED A MINIMUM OF (2) WEEKS PRIOR TO FINAL INSPECTION. ANY EXPENSES, SUCH AS REVISIONS OR AS- BUL1S, NECESSARY FOR FINAL C.O. SHALL AT THE EXPENSE OF THE OWNER. 12. ELECTRICIAN SHALL MARK PANEL CIRCUIT NUMBERS AT ALL DEVICES /J- BOXES. 13. ALL ELECTRICAL PANELS SHALL BE LABELED AND PROVIDED WITH A TYPED, UP To DATE PANEL SCHEDULE. ELECTRICAL DEMOLITION NOTES: 1. - Fixtures and equipment to be demolished, shall be removed by the electrical contractor and salvage value shall be reflected in a reduction of the bid /proposal. 2. Remove existing wiring and equipment /devices which are not necessary for the function of new equipment /devices and the function of existing equipment /devices remaining. Leave abandoned wiring entirely, unless otherwise noted, and remove accessible raceways, cut, cap and patch over concealed conduits at a point of emergence. Existing panel directories shall be replaced new type written directories to reflect as -built conditions, with spare or space indicated in pencil. Provide new labels on the left and even number labels on the right. Existing equipment and materials that are removed shall not be reused except where specifically noted. Dispose of scrap debris. Maintain electrical continuity to equipment /devices which shall remain, contractor shall be guided by owner,architect as to the requirement for removal of equipment /devices which may not be indicated Remove existing wiring devices as required for the removal of walls and /or the installation of new wall finishes where devices are removed. Contractor shall also remove outlet box, conductors, conduit and mounting hardware, exception to this requirement may be where contractor proposes to reuse conduit concealed or outlet box recessed in existing wall or floor slab for new work, if approved in advance by architect. Z .��. , J. •� ,�:...�;, •f} -l: Rr SOU" R-O WE. F 7 {� ni iii i. AI A, i >i:'L7.f`:'1: i ;,iS iSE .. C .,. .,. ..1 I) : -Y: �• ARE ' •I� !Jf't♦ J >Sl; �.' 2 f %iii; F�.(.}J: I :i fii { J \. Y f.. J.♦ \ l 1: Tl�::.. l;F.:1:�:4 , t4: .,;;tvC,:.. "'T:: r : ?.. ... ....,..... ' �� ....:Y ° ;c;;EE.:1 T l�'i.�.i�; xrr_i. . J� : it..t .�:. . {P�.J...,. i{, t!,.:� . .. .r;.� : .. ;:._• ...:.s:.. .. THIS CRAWIN% IS „•,T >i:- RIZL.:, ir'ITHCUT ;f'EC•H, . WR17EN .:i.;i ?..S•;,IN. r:.. fdn' ?T' FE.��. >; i;. Inv INTERIOR ELEVATION S SECTIONS AND DETAILS SCALE: AS NOTED y KEY NOTES: = SOLID SURFACING COUNTERTOP 2 L PLASTIC LAMINATE CLAD END PANEL (N.I.C.) 31 PLASTIC LAMINATE CLAD WOOD BASE (N.I.C.) 4 1 i 0• 5 6 7 EXISTING ACOUSTICAL CEILING AND SUSPENSION SYSTEM 8 9 FLAT -PANEL TELEVISION (N.I.C.) 10 VIDEO MONITOR WALL - MOUNTING BRACKET 11 PLASTIC- LAMINATE -CLAD ARCHITECTURAL CABINET 12 WOOD LAMINATE PANELS TO MATCH EXISTING G.C. TO CONTINUE 13 CABINETRY AND CUT/ EXISTING PLASTIC- LAMINATE -CLAD BACKSPLASH ADJUST AS NEEDED. FINISH 14 PLASTIC- LAMINATE -CLAD COUNTERTOP (N.I.C.) TO MATCH EXISTING (TYP.) 15 BASE TO MATCH EXISTING 16 PORTION OF EXISTING CABINET TO REMAIN - REWORK TO MATCH EXISTING Id EXISTING GYPSUM BOARD WALL TO BE PAINTED TO MATCH EXISTING PATCH AND REPAIR ALL AREAS AS REQUIRED FOR NEW CONSTRUCTION. 18 NEW GYPSUM BOARD WALL TO BE PAINTED TO MATCH EXISTING N SECTION KEY NOTES: A FLAT PANEL TELEVISION (NIC) B VIDEO MONITOR WALL MOUNTING BRACKET (N.I.C.) C BASE TO MATCH EXISTING D PLYWOOD SHEATHING E NEW %" GYPSUM WALL BOARD F NON STRUCTURAL METAL STUD FRAMING, BRACE TO STRUCTURE ABOVE EVERY OTHER STUD. G NON STRUCTURAL METAL STUD FRAMING H ALIGN I STUD BRACE Ljj LOCATE (6) 2X4 J -BOXES FOR POWER /DATA ORIENT RECEPTACLES HORIZONTALLY. COORDINATE LOCATIONS WITH VIDEO MONITOR MFR. ELECTRICAL RENOVATION NOTES THE SCOPE OF ECTRICAL WORT( SHALL INCLUDE IT IS NOT LIMITED TO THE FOLLOWING. 1. ELECTRICAL CONTRACTOR SHAD MAKE A THOROUGH SURVEY OF EXISTING CONDITIONS & OF THE ELECTRICAL SYSTEM To FAMILIARIZE HIMSELF, IN ORDER TO INSTALL THE NEW ELECTRICAL SYSTEM PROPOSED, PRIOR To BD /CONSTRUCTION. ELECTRICAL CONTRACTOR SHALL IDENTIFY ALL THE BRANCH CIRCUITS BEING FED FROM EXISTING PANELS 2. ALL EQUIPMENT SCHEDULED TO BE REUSED, SHALL BE RECONDITIONED To LIKE NEW. IF COST TO REPAIR OR RECONDITION EXCEEDS NEW COST , THEN THE EQUIPMENT SHALL BE REPLACED. 3. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR RECONNECTING ALL ELECTRICAL EQUIPMENT N ORDER TO HAVE A COMPLETE WORKING JOB, WHETHER OR NOT THE EQUIPMENT ON THE NEW PLANS. 4. DUE TO THE NATURE OF THIS PROJECT, THE ELECTRICAL CONTRACTOR MUST CHECK OUT ALL EXISTING CIRCUITS STARTING AT THEIR DISTRIBUTION POINTS IN ORDER TO SEE IF THEY ARE STILL. ALIVE. 5, WHEN INSTALLING NEW EQUIPMENT, THE ELECTRICAL CONTRACTOR SHOIJ D USE EXISTING CONDUITS AND AVAILABLE CIRCUITS IF POSSIBLE ALL REUSED CIRCUIT BREAKERS, OUTLETS, SWITCHES, ETC., SHALL BE INSPECTED AND REPLACED AS NEEDED. 6. ALL ELECTRICAL EQUIPMENT REMOVED SHALL BE KEPT IN A SECURE AREA UNTIL OWNERS DECIDE WHAT TO DO WITH IT. 7. THE ELECTRICAL CONTRACTOR SHALL NOT OVERLOAD ANY EXISTING PANEL BOARDS OR FEEDERS AND SHALL NOT EXCEED BOx OF THEIR RATED VALUE B. ELECTRICAL CONTRACTOR SHALL VERIFY ALL ELECTRICAL REQUIREMENTS FOR ALL EQUIPMENT PRIOR TO INSTALLATION. 9. ELECTRICAL CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS PRIOR TO BID AND INSTALLATION, INFORM THE ENGINEER OF RECORD OF ANY DISCREPANCY BETWEEN THE DOCUMENTS AND THESE CONDITIONS AND HE SHALL INCLUDE IN HIS BID TO CORRECT THE SAME AS DIRECTED. THE ENGINEER AND THE ARCHITECT ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING FROM VERIFIABLE EXISTING CONDITIONS DISCOVERED AFTER THE CONTRACT HAS BEEN AWARDED. 10. THE INTENT OF THE ELECTRICAL DESIGN IS TO UTILIZE AS MUCH OF THE ELECTRICAL EQUIPMENT AS POSSIBLE, THEREBY ELIMINATING EXCESSIVE COST, CONSTRUCTION, AND TIME 11. ELECTRICAL CONTRACTOR SHALL KEEP AS -BOLTS AND SUBMIT TO ENGINEER OF RECORD FOR RENEW. ALL CHANGES SHALL BE FORWARDED A MINIMUM OF (2) WEEKS PRIOR TO FINAL INSPECTION. ANY EXPENSES, SUCH AS REVISIONS OR AS- BUL1S, NECESSARY FOR FINAL C.O. SHALL AT THE EXPENSE OF THE OWNER. 12. ELECTRICIAN SHALL MARK PANEL CIRCUIT NUMBERS AT ALL DEVICES /J- BOXES. 13. ALL ELECTRICAL PANELS SHALL BE LABELED AND PROVIDED WITH A TYPED, UP To DATE PANEL SCHEDULE. ELECTRICAL DEMOLITION NOTES: 1. - Fixtures and equipment to be demolished, shall be removed by the electrical contractor and salvage value shall be reflected in a reduction of the bid /proposal. 2. Remove existing wiring and equipment /devices which are not necessary for the function of new equipment /devices and the function of existing equipment /devices remaining. Leave abandoned wiring entirely, unless otherwise noted, and remove accessible raceways, cut, cap and patch over concealed conduits at a point of emergence. Existing panel directories shall be replaced new type written directories to reflect as -built conditions, with spare or space indicated in pencil. Provide new labels on the left and even number labels on the right. Existing equipment and materials that are removed shall not be reused except where specifically noted. Dispose of scrap debris. Maintain electrical continuity to equipment /devices which shall remain, contractor shall be guided by owner,architect as to the requirement for removal of equipment /devices which may not be indicated Remove existing wiring devices as required for the removal of walls and /or the installation of new wall finishes where devices are removed. Contractor shall also remove outlet box, conductors, conduit and mounting hardware, exception to this requirement may be where contractor proposes to reuse conduit concealed or outlet box recessed in existing wall or floor slab for new work, if approved in advance by architect. Z .��. , J. •� ,�:...�;, •f} -l: Rr SOU" R-O WE. F 7 {� ni iii i. AI A, i >i:'L7.f`:'1: i ;,iS iSE .. C .,. .,. ..1 I) : -Y: �• ARE ' •I� !Jf't♦ J >Sl; �.' 2 f %iii; F�.(.}J: I :i fii { J \. Y f.. J.♦ \ l 1: Tl�::.. l;F.:1:�:4 , t4: .,;;tvC,:.. "'T:: r : ?.. ... ....,..... ' �� ....:Y ° ;c;;EE.:1 T l�'i.�.i�; xrr_i. . J� : it..t .�:. . {P�.J...,. i{, t!,.:� . .. .r;.� : .. ;:._• ...:.s:.. .. THIS CRAWIN% IS „•,T >i:- RIZL.:, ir'ITHCUT ;f'EC•H, . WR17EN .:i.;i ?..S•;,IN. r:.. fdn' ?T' FE.��. >; i;. Inv INTERIOR ELEVATION S SECTIONS AND DETAILS SCALE: AS NOTED y a 0) V Ar ` C 00 1 i 0• uc°a r i rn rn ID •U a 0) V C C 00 ■� rn rn a •U ` c6 N ro " aT o � c N ch o) S.. g. 23 M0o �r. � _o Li toi =:% v ^� a_-� E L�.. a� B Q • Ca �.� t ,^ V i U '2•s N i- m o N a C W T ■� T 7 O qt 0 t O N_ -L Q a v 0 R'Ytw1�.� N F�+ z OFt$4AA 0 v Q CD L.IJ U P7 4, Lj Q re) U•r) o E � � o J Uj Q U F- Uj ~ W � z z N� ::D CD 00 C/') C/- U-5 cn a 0 a •U N N v t o N a C t a v 0 N v Q sheet no. A -2 9 e W a