14-490-014GENERAL NOTES 1.THE DRAWINGS ARE INTENDED TO SHOW THE GENERAL ARRANGEMENT, DESIGN AND EXTENT OF THE WORK AND ARE PARTLY DIAGRAMMATIC. THEY ARE NOT INTENDED TO BE SCALED FOR ROUGHING -IN MEASUREMENTS, OR TO SERVE AS SHOP DRAWINGS OR PORTIONS THEREOF. 2.ALL DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT, EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN. 3.THE CONTRACTOR AND ALL SUBCONTRACTORS SHALL VERIFY ALL GRADES, LINES, LEVELS, CONDITIONS AND DIMENSIONS AT THE JOB SITE AND AS SHOWN ON THE DRAWINGS. THEY SHALL REPORT ANY ERRORS OR INCONSISTENCIES IN THE ABOVE TO THE ARCHITECT BEFORE COMMENCING WORK.THE CONTRACTOR AND SUBCONTRACTORS SHALL LAYOUT THEIR WORK FROM ESTABLISHED REFERENCE POINTS AND BE RESPONSIBLE E ONSIBLE FOR ALL LINES, ELEVATIONS AND MEASUREMENTS TS IN CONNECTION WITH THEIR WORK. 4. PROTECTION: A. THE CONTRACTOR IS RESPONSIBLE AND SHALL COMPLY WITH ALL REQUIREMENTS OF FLORIDA BUILDING CODE ( 2004 FBC ) AND ALL LOCAL STATE AND FEDERAL LAWS. THE ENGINEER AND/OR HIS EMPLOYEES OR REPRESENTATIVES ARE NOT RESPONSIBLE FOR THE IMPLEMENTING, MAINTAINING, VERIFYING AND/OR MONITORING SAFETY PROCEDURES OR THE ADEQUACY OF SAFETY PROCEDURES BEING USED FOR THIS PROJECT. SAFETY- RELATED METHODS AND PROCEDURES ARE THE CONTRACTOR'S RESPONSIBILITY. B. PROVIDE ALL SHORING, BRACING AND SHEETING AS REQUIRED FOR THE PROPER EXECUTION OF THE WORK. REMOVE WHEN THE WORK IS COMPLETED. C. PROVIDE AND MAINTAIN GUARD LIGHTS AT ALL BARRICADES, RAILINGS, OBSTRUCTIONS IN THE STREETS ROADS OR SIDEWALKS AND ALL TRENCHES OR PITS ADJACENT TO PUBLIC WALKS OR ROADS. D. AT ALL TIMES PROVIDE PROTECTION AGAINST WEATHER (RAIN, WIND, STORMS OR HEAT) SO AS TO MAINTAIN ALL WORK, MATERIALS, APPARATUS AND FIXTURES FREE FROM DAMAGE. E. THE CONTRACTOR SHALL PAY FOR ALL DAMAGES TO ADJACENT STRUCTURES, SIDEWALKS AND TO STREETS OR OTHER PUBLIC PROPERTY OR TO ANY PUBLIC UTILITIES. F. AT THE END OF THE DAYS WORK, COVER ALL WORK LIKELY TO BE DAMAGED. ANY WORK DAMAGED BY FAILURE TO PROVIDE PROTECTION SHALL BE REMOVED AND REPLACED WITH NEW WORK AT THE CONTRACTOR'S EXPENSE. 5. CONTRACTOR AGREES THAT HE WILL HOLD OWNER, ENGINEERS AND /OR ANY OF THEIR EMPLOYEES OR AGENTS HARMLESS FROM ANY AND ALL DAMAGE AND CLAIMS WHICH MAY ARISE BY REASON OF ANY NEGLIGEN CE ON PAR OF THE CONTRACTOR, ANY OF HIS SUBCONTRACTORS AND /OR SUBCONTRACTORS, MATERIALS AND EQUIPMENT SUPPLIERS AND /OR ANY OF THEIR EMPLOYEES OR AGENTS, IN PERFORMANCE OF THIS CONTRACT; AND, IN CASE ANY ACTION IS BROUGHT THEREFORE AGAINST OWNER, ENGINEERS AND /OR ANY OF THEIR EMPLOYEES OR AGENTS, CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR DEFENSE THEREOF, AND UPON HIS FAILURE TO DO SO ON PROPER NOTICE, OWNER, ENGINEERS AND /OR ANY OF THEIR EMPLOYEES OR AGENTS RESERVE THE RIGHT TO DEFEND SUCH ACTION AND CHARGE ALL COSTS THEREOF TO CONTRACTOR. 6. IF ANY ERRORS OR OMISSIONS APPEAR IN THE DRAWINGS, SPECIFICATIONS OR OTHER DOCUMENTS THE CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY IN WRITING OF SUCH OMISSIONS OR ERRORS PRIOR TO PROCEEDING WITH ANY WORK WHICH APPEARS IN QUESTION. IN THE EVENT OF THE CONTRACTOR'S FAILING TO GIVE SUCH NOTICE, HE SHALL BE HELD RESPONSIBLE FOR THE RESULT OF ANY SUCH ERRORS OR OMISSIONS AND THE COST OF RECTIFYING THE SAME. 7. THE CONTRACTOR SHALL USE THE STRUCTURAL DRAWINGS TOGETHER WITH THE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS TO LOCATE DEPRESSED SLABS, SLOPES, DRAINS, OUTLETS, RECESSES, OPENINGS, REGLETS, BOLT SETTING, SLEEVES, DIMENSIONS, ETC. POTENTIAL CONFLICTS SHALL BE TRANSMITTED TO THE A/E BEFORE PROCEEDING WITH THE WORK. 8. SUBMIT THREE COPIES OF SHOP DRAWINGS FOR ARCHITECT'S REVIEW BEFORE STARTING FABRICATION. 9. NO SHOP DRAWINGS SHALL BE SUBMITTED FOR A/E REVIEW UNTIL AFTER THEY HAVE BEEN REVIEWED AND NOTED FOR CONSTRUCTION METHOD, DIMENSIONING AND OTHER TRADE REQUIREMENTS BY THE CONTRACTOR AND STAMPED WITH THE CONTRACTOR'S APPROVAL SEAL. ARCHITECT ASSUMES NO RESPONSIBILITY FOR DIMENSIONS, QUANTITIES, ERRORS OR OMISSIONS AS A RESULT OF CHECKING AND REVIEWING ANY SHOP DRAWINGS. ANY ERRORS OR OMISSIONS MUST BE MADE GOOD BY CONTRACTOR, IRRESPECTIVE OF RECEIPT, CHECKING OR REVIEW OF DRAWINGS BY ARCHITECT AND EVEN THOUGH WORK IS DONE IN ACCORDANCE WITH SUCH DRAWINGS. 10. VERIFICATION OF EXISTING CONDITIONS: INASMUCH AS THE REMODELING AND /OR REHABILITATION OF AN EXISTING BUILDING REQUIRES THAT CERTAIN ASSUMPTIONS BE MADE REGARDING EXISTING CONDITIONS, AND BECAUSE SOME OF THESE ASSUMPTIONS MAY NOT BE VERIFIABLE WITHOUT EXPENDING ADDITIONAL SUMS OF MONEY, OR DESTROYING OTHERWISE ADEQUATE OR SERVICEABLE PORTIONS OF THE BUILDING, THE OWNER AGREES THAT, EXCEPT FOR NEGLIGENCE ON THE PART OF THE DESIGN PROFESSIONAL, THE OWNER WILL HOLD HARMLESS, INDEMNIFY AND DEFEND THE DESIGN PROFESSIONAL FROM AND AGAINST ANY CLAIMS ARISING OUT PROFESSIONAL SERVICES UNDER THIS AGREEMENT. 11. THE REVIEW OF ALL STRUCTURAL SUBMITTALS BY THE STRUCTURAL ENGINEER OF RECORD SHALL BE TO INSURE THAT HIS INTENT HAS BEEN UNDERSTOOD AND THAT THE SPECIFIED CRITERIA HAVE BEEN USED. A COPY OF ALL STRUCTURAL SUBMITTALS WILL BE RETAINED FOR RECORD KEEPING PURPOSES ONLY. 12. WHERE CRITICAL DIMENSIONS CANNOT BE DETERMINED FROM THE PLANS, OR WHERE NEW WORK ADJOINS EXISTING CONSTRUCTION, OR WHERE ONE MATERIAL ADJOINS AN IN -PLACE MATERIAL, CONTRACTOR SHALL TAKE FIELD MEASUREMENTS AS REQUIRED TO COMPLETE SHOP DRAWINGS AND INSTALLATION. REPORT ANY DISCREPANCIES BETWEEN FIELD MEASURED DIMENSIONS AND SCALED DRAWING DIMENSIONS TO ARCHITECT BEFORE PROCEEDING WITH THE WORK. 13. WHERE A LINE OF STRUCTURE, OPENING LOCATION, OR DIMENSION IS CRITICAL AND BASED ON THE REQUIREMENTS OF ANOTHER TRADE OR SUBCONTRACTOR, THAT THE SUBCONTRACTOR SHALL SUBMIT A SHOP DRAWING WITH THE REQUIRED DIMENSIONAL INFORMATION UPON WHICH THE CONTRACTOR SHALL BASE THE LAYOUT AND CONSTRUCTION. THIS PROCEDURE IS MANDATORY FOR CURTAIN WALL SYSTEMS, ARCHITECTURAL PRECAST SYSTEMS AND ALL MECHANICAL AND ELECTRICAL OPENINGS. WOOD NOTES 1. PRIMARY WOOD FRAMING MEMBERS SHALL BE NO. 2 SOUTHERN PINE OR BETTER, SURFACED DRY, USED AT 19 % MAX M.C., WITH THE FOLLOWING STRESS RATING UNLESS OTHERWISE NOTED: Fb (SINGLE MEMBERS) = 1,200 PSI Fb (REPETITIVE MEMBERS) = 1,400 PSI Fv = 90 PSI Fc (PERPENDICULAR TO GRAIN) = 565 PSI E = 1,600,000 PSI 2. METAL STRAPS, CLIPS, AND HARDWARE SHALL BE GALVANIZED TREATED. 3. ALL WOOD IN CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESSURE TREATED. TERMITE PROTECTION TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED TERMITICIDES OR OTHER APPROVED METHODS OF TERMITE PROTECTION LEVELED FOR USE AS PREVENTIVE TREATMENT TO NEW CONSTRUCTION. IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE PREVENTION, THE INITIAL CHEMICAL SOIL TREATMENT INSIDE THE FOUNDATION PERIMETER SHALL BE DONE AFTER ALL EXCAVATIONS, BACKFILLING AND COMPACTION IS COMPLETED. SHEATHING USE 5/8" PLYWOOD APA RATED SHEATHING EXPOSURE I. INSTALL WITH THE LONG DIMENSION OR STRENGTH AXIS OF THE PANEL ACROSS SUPPORTS, AND WITH PANEL CONTINUOUS OVER TWO OR MORE SPANS. PANEL END JOINTS SHALL OCCUR OVER FRAMING. NAIL 10d ® 6" O.C. ALONG SUPPORT PANEL EDGES AND AT INTERMEDIATE SUPPORTS. NAIL 10d ® 4" O.C. ALONG THE PERIMETER OF THE ROOF. THIS IS BASED ON MAXIMUM SUPPORT SPACING OF 24" O.C. NAILS SHALL BE 8D NAILS "RING SHANK" WITH 1 3/4" MIN. PENETRATION ON MAIN MEMBER. WOOD TRUSSES 1. TRUSSES TO BE DESIGNED AND FABRICATED TO MEET THE REQUIREMENTS OF THE NATIONAL DESIGN SPECIFICATIONS FOR STRESS GRADE LUMBER AND ITS FASTENING AND TIMBER CONSTRUCTION STANDARD BY AITC. TRUSSES SHALL BE DESIGNED FOR SUPER - IMPOSED LOADS INDICATED IN PLAN. 2. TRUSSES SHALL BE ENGINEERED TO SPAN THE CONFIGURATION INDICATED ON THE DRAWINGS. PROVIDE (3) COPIES OF 24" X 36" OF TRUSS DRAWINGS AND ENGINEER'S CALCULATIONS WITH SEAL OF REGISTERED ENGINEER IN THE STATE OF FLORIDA FOR ARCHITECT'S APPROVAL PRIOR FABRICATION. 3. ALL ROOF JOISTS, TRUSSES, LOOKOUTS, BEAMS, & GIRDERS SHALL BE SECURED WITH APPROVED METAL TIES, CLIPS, AND ANCHORS AT CONNECTIONS. 4. ALL FRAMING AND TRUSS CORDS SHALL HAVE A MINIMUM OF 2X6 MEMBERS AS PER F.B.C. 2007 ZONING DEPARTMENT 5. TRUSSES OVER 35 FT. LONG OR 6'.0" HIGH SHALL BE INSPECTED BY A FLORIDA LICENSED ENGINEER AND LETTER OF RETENTION FOR SUPERVISION OF EREC11ON SHALL BE PART OF THE PERMIT DOCUMENTS. REINFORCING STEEL 1. TO BE NEW BILLET STEEL CONFORMING TO THE LATEST A.S.T.M. A615 GRADE 60 SPECIFICATIONS, FABRICATED IN ACCORDANCE WITH MANUAL OF STANDARD PRACTICE OF THE C.R.S.I. AND PLACED IN ACCORDANCE WITH A.C.I. 315 AND A.C.I. MANUAL OF STANDARD PRACTICE. 2. COLUMN REINFORCEMENT. E ENT: DOWELS TO BE SAME SIZE AND NUMBER AS VERTICALS ABOVE. LAP 48 BAR DIAMETER OR MINIMUM OF 18" U.O.N. PROVIDE RIGID TEMPLETS FOR DOWEL LOCATION. PROVIDE STANDARD HOOKS FOR ALL VERTICAL REINFORCEMENT AT DOWEL LOCATION. PROVIDE STANDARD HOOKS FOR ALL VERTICAL REINFORCEMENT AT 3. ALL DOWELS FOR COLUMNS AND WALLS TO BE SECURED IN POSITION I PR OR TO CONCRETING. DRILLING OR PUSHING THE DOWELS INTO POSITION IN WET CONCRETE IS NOT PERMITTED. 4. CONCRETE COVER UNLESS OTHERWISE DETAILED ON DRAWINGS: FOOTINGS 3 ", COLUMNS 1-1/2" TO - 11ES BEAMS 1 1 " 2 TO STIRRUPS INTERIOR TE R SLABS 3 " / 4 EXPOSED SLABS / 1 -1/2 ", LABS ON GRADE 1 -1/2" MEASURED FORM TOP OF SLAB. 5. SLAB AND BEAM REINFORCEMENT: PLACED IN ACCORDANCE WITH REINFORCING DIAGRAMS, LAPPED 36 BAR DIAMETER OR MINIMUM 18 ". BOTTOM BARS SPLICED ONLY AT SUPPORTS T OP BARS SPLICED ONLY AT MID-SPAN. ALL TOP BARS HOOKED AT NON - CONTINUOUS EDGES (U.O.N.). ALL HOOKS TO BE STANDARD 90 DEGREE OR 180 DEGREE HOOKS AS REQUIRED (U.O.N.) 6. ADDED REINFORCEMENT: PROVIDE ADDITIONAL CORNER BARS BENT 30" MINIMUM EACH WAY AT CORNERS IN OUTER FACES OF ALL BEAMS TO MATCH ALL HORIZONTAL BARS. ALL TIE BEAMS SHALL HAVE MINIMUM FOUR #3 TIES ® 12" O.C. AT CORNERS, AT EACH BEND AND AT 48" O.C. ELSEWHERE. 7. REINFORCEMENT SHOWN ON PLANS IS BOTTOM UNLESS MARKED "T" (TOP BARS). 8. THE CONTRACTOR SHALL INFORM THE REBAR DETAILER OF HIS PROPOSED REBAR SUPPORT METHOD AND CONSTRUCTION SEQUENCES. ALL SUPPORT ITEMS AND SPLICES REQUIRED SHALL BE SO DETAILED AND PROVIDED. STRUCTURAL AND MISCELLANEOUS STEEL: 1. ALL STRUCTURAL STEEL TO BE DOMESTIC ASTM A -36 (Fy' =36 K.S.I.) AND DESIGNED IN ACCORDANCE WITH THE LATEST A.I.S.C. "SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS: AND THE A.I.S.C. CODE OF STANDARD PRACTICE. 2. ANCHOR BOLTS TO BE (ASTM- A307), EXPANSION BOLTS HILTI "KWIKBOLTS" TO BE 3/4" DIAMETER, UNLESS OTHERWISE SPECIFIED. PROVIDE MATCHING H.S. NUTS AND WASHERS. 3. ALL WELDING TO BE CLASS E70XX IN ACCORDANCE WITH AMERICAN WELDING SOCIETY (AWS) "STRUCTURAL WELDING CODE - STEEL ", D1.1, AND AS INDICATED ON THE STRUCTURAL DRAWINGS. WELDING ELECTRODES, WELDING PROCESS, MINIMUM PREHEAT AND INTERPASS TEMPERATURES TO BE IN ACCORDANCE WITH THE AWS SPECIFICATIONS. ANY STRUCTURAL STEEL DAMAGED IN WELDING TO BE REPLACED OR ACCEPTABLY REINFORCED. ALL FULL PENETRATION GROOVE WELDS TO BE SUBJECT TO RADIOGRAPHIC, MAGNETIC PARTICLE, ULTRASONIC, AND LIQUID PENETRANT INSPECTION CONDUCTED BY AN INDEPENDENT TESTING AGENCY PAID BY THE OWNER. RUSTPROOF ALL FIELD WELDS WITH HEAVY DUTY RUSTPROOFING PAINT. 4. SPLICE LOCATIONS TO BE APPROVED BY ENGINEER. 5. SHOP COAT ALL STRUCTURAL STEEL WITH RUSTOLEM "769" RED PRIMER OR APPROVED EQUAL (U.O.N.) 6. SUBMIT ONE SEPIA AND ONE PRINT OF SHOP DRAWINGS FOR ENGINEER'S REVIEW BEFORE STARTING FABRICATION. FOUNDATION SCHEDULE Mark Size (WxD) In Reinforcing Looi itudinal TT Transversal Longitudinal g� Transversal TE -12 12" X 12" 1 #5 - 2 #5 - WF18 18" X 12" X X 3 #5 #4 ® 32" F- 4X2.5 4'X2.5'X18" 5 #5 3 #5 5 #5 3 #5 .... . �r � :"'. , . �'`' ,_ is art � . a.,,..., .... ...: } "fii �,, .1 ............4 , ..... ...q� >.. :.Y: .., . ... . ` .... �. :,.::: Z SB -1 COLUMN SCHEDULE MARK SIZE (WXH) REINFORCING REINFORCEMENT REMARKS VERTICAL TIES TC -1 8" X 12" 4 #5 #3 ®8 RECTANGULAR ............................... WAL L FOOTING MFWF .............................................................................. MASONRY FENCE , W­ ALL FOOTING ............................... . :. :.. •. SC -1 4 "O X 1/4" TUBULAR STEEL COLUMN 8" X 12" BEAM SCHEDULE MARK ELEV. SIZE ( W X D ) REINFORCEMENT STIRRUPS REMARKS TB -1 SEE PLAN 8" X 12" 2 #5 TOP. 2 #5 BOT. #3 0 8 CONCRETE ............................... WAL L FOOTING MFWF .............................................................................. MASONRY FENCE , W­ ALL FOOTING ............................... . :. :.. •. LO RCB -8 9' -0" 8" X 12" 2 #5 TOP. 2 #5 BOT. 6 #3 ® 4" ENDS BALANCE #3 ® 8 CONCRETE 9 W .... . �r � :"'. , . �'`' ,_ is art � . a.,,..., .... ...: } "fii �,, .1 ............4 , ..... ...q� >.. :.Y: .., . ... . ` .... �. :,.::: Z SB -1 10' -8" W 8 X 35 STEEL BEAM STEEL STRUCTURAL NOTES - GENERAL 1. CODES: ALL DESIGN AND WORK SHALL CONFORM TO THE FLORIDA BUILDING CODE 2010 AND ASCE 07-2010. 2. DIMENSIONS AND CONDITIONS: ALL DIMENSIONS AND CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR IN THE FIELD PRIOR TO CONSTRUCTION. ANY DISCREPANCIES` SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ENGINEER. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALE AT ALL TIMES. SCALE IS FOR GUIDELINE PURPOSES ONLY. IF DIMENSIONS ARE UNCLEAR, DO NOT SCALE. REQUEST CLARIFICATION FROM THE ARCHITECT OR ENGINEER. 3. METHODS & SAFETY: THE CONTRACTOR SHALL BE RESPONSIBLE E NSIBLE FOR ALL METHODS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION. TRUCTION. THE SAFETY AND SERVICEABILITY OF THE E P OJECT IS THE RESPONSIBILITY OF THE CONTRACTOR. 4. CONSTRUCTION LOADS: THE STRUCTURES INVOLVED HAVE BEEN DESIGNED ACCORDING TO THE LIVE AND DEAD LOADS AS LISTED UNDER THE DESIGN CRITERIA SECTION AND ACCORDING TO THE REQUIREMENTS SET FORTH BY THE PROPOSED USE OF THE STRUCTURE. THESE LOADS MAY NOT TAKE INTO ACCOUNT ANY AND ALL CONSTRUCTION LOADS WHICH MAY BE SUPERIMPOSED DURING CONSTRUCTION. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO ASSURE THAT CONSTRUCTION LOADS DO NOT EXCEED THE DESIGN LOADS OF THE STRUCTUR I E, ADD THE PROPER PLACEMENT OF MATERIALS AND FORMING AND SHORING TECHNIQUES ARE UTILIZED TO ASSURE PROPER AND SAFE DISTRIBUTION OF LOADS THROUGHOUT THE STRUCTURE. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO EMPLOY THE NECESSARY PROFESSIONAL SERVICES TO DETERMINE THE NECESSARY METHODS AND SUPPORTS REGARDING FORMING AND CONSTRUCTION LOADS. 5. CONFLICTS IN PLANS: IF CONFLICTS OCCUR IN PLANS BETWEEN ARCHITECTURAL AND ENGINEERING PLANS OR OTHERWISE, THE CONTRACTOR SHALL IMMEDIATELY CONTACT THE ARCHITECT FOR CLARIFICATION AND DIRECTION BEFORE PROCEEDING. 6. SHOP DRAWINGS: A. PRIOR TO FABRICATION OF ANY ITEMS, THE CONTRACTOR SHALL SUBMIT TO THE ARCHITECT FOR REVIEW BY THE ENGINEER COMPLETE SHOP DRAWINGS, PRECAST AND PRE STRESSED CONCRETE UNITS, STRUCTURAL AND MISCELLANEOUS STEEL, WOOD ROOF TRUSSES, AND ANY OTHER ITEMS OF CONSTRUCTION REQUIRING OFFSITE FABRICATION. B. REVIEW AND APPROVAL OF SHOP DRAWINGS IS FOR CONFORMANCE TO THE DESIGN CONCEPT AND LAYOUT ONLY. THE CONTRACTOR SHALL CHECK AND APPROVE THE SHOP DRAWINGS FIRST FOR COMPLIANCE AND COMPLETENESS BEFORE SUBMITTAL. APPROVAL BY THE ENGINEER IS NOT FOR THE PURPOSE OF APPROVING CHANGES OR SUBSTITUTIONS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DIMENSIONS, QUANTITIES, JOB CONDITIONS, AND COORDINATION WITH ALL PLANS AND OTHER TRADES. 7. OPENINGS IN SLABS, FLOORS, AND ROOFS: THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL REQUIRED OPENINGS PENINGS IN SLABS, FLOORS, AND ROOFS OR OTHER STRUCTURAL ELEMENTS. A PLAN OF ALL SUCH OPENINGS SHALL BE SUBMITTED FOR REVIEW PRIOR TO CONSTRUCTION OF SUCH OPENINGS. 8. SUBSLAB VAPOR BARRIER SHALL EXTEND INTO STEM WALL 1" MIN. AND CONCRETE SLAB SHALL BE POURED INTO THE STEM WALL TO COMPLETELY FILL CELLS - FBC 8303.1.2 9. ALL SLAB PENETRATIONS OR BLOCKED OUT WORK SPACES TO BE SEALED WITH AN APPROVED SEALANT TO A MINIUMUM DEPTH OF 1" TO PROTECT FROM RADON GAS - FBC B303.3.4 STRUCTURAL NOTES CONCRETE: SHALL ATTAIN A MINIMUM COMPRESSIVE STRENGTH OF 4,000 PSI AT 28 DAYS. MAXIMUM SIZE OF AGGREGATES: 3/4" MAXIMUM PERMISSIBLE SLUMP: 5" REINFORCING STEEL: SHALL CONFORM TO A.S.T.M. A -615 GRADE 60. REINFORCING STEEL SHALL BE DETAILED AND FABRICATED ACCORDING WITH THE "MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES." LAP CONTINUOUS REINF. 30 BAR DIA. IN BEAMS, 36 DIA. IN SLABS. LAP BOTTOM STEEL OVER SUPPORTS AND TOP STEEL AT MIDSPAN. HOOK ALL DISCONTINUOUS TOP REINFORCING. TURN ALL CORNERS WITH 2 #5 x 4' -0" CLEAR COVER FOR REINFORCING SHALL BE : MINIMUM TOLERANCE COVER +OR CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH 3" 3 8" EXPOSED TO EARTH OR WEATHER No.5 AND SMALLER BARS 1 1/2" 3/8" No.6 AND LARGER BARS 2" 3/8" NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND: ROOF SLAB 1" 1/8" STRUCTURAL SLAB AND WALLS 3/4" 1/8" BEAMS AND COLUMNS (PRIMARY REINFORCEMENT, TIES, STIRRUPS AND TIES, STIRRUPS AND SPIRALS) 11/2- 3/8" SLABS ON GRADE 1 1/2- 1/4- SLABS ON FILL: SHALL BE PLACED ON CLEAN, NON ORGANIC SOIL THROUGHLY MOISTENED IMMEDIATELY BEFORE CONCRETE IS POURED. SLABS ON FILL SHALL BE POURED IN A CHECKERBOARD SEQUENCE, EACH FRAGMENT OF WHICH IS NOT TO EXCEED A MAXIMUM AREA OF 400 SQ. FT. OR 30 LINEAR FT. IN ANY ONE DIRECTION. GENERAL: 1- PROVIDE POLYETHELENE MEMBRANE FOR ALL SLABS ON GRADE. (.006 IN. VISQUEEN.) 2- SLABS ON GRADE TO HAVE 1/2" EXPANSION JOINT MATERIAL AROUNG COLUMNS AND BLOCK WALLS. 3- ALL MASONRY WALLS ARE DESIGNED AS BEARING WALLS UNLESS OTHERWISE NOTED AND SHALL BE IN PLACED BEFORE SLABS AND TIE COLUMNS ARE POURED. GRAVITY DESIGN LOAD LL = ROOF = 30 PSF DL = ROOF = 25 PSF . .. . . . . . .. .. .. . .. .. .. .. .. .. . . . . . . . . . . .. .. .. .. .. .. .. .. . . . .. .. ... . .. .. . .. .. .. . . . . . . . . . .. .. .. .. . .. .. .. . . . . . .. .. .. .. .. .. .. . . . .. .. . . .. .. .. . .. .. .. .. .. .. . .. .. . . . .. .. .. .. . . . . . .. .. .. . .. .. .. .. .. .. . . . .. .. .. .. . .. .. .. . .. ... .. .. .. . . . . . . . .. ... . .. .. .. . . . . . . . . . . . . . .. .. . . . .. . .. .. .. .. . . . .. .. . ... .. .. .. . ABBREVIATION: TB ................ ... ... ..TI.E ... BEAM BM- - - - ---- - - - - -- -- BEAM ...- - - - - .....-... - - - - - -- - ..... ... ... EXT__-_____ EXTERNAL ______.____....____________._ UNO- - - . ------- - UNLESS.. NOTES .OTHERWISE. --- T ... &... R .............TOR... AND .... BOTTOM ......... ........ . ... . ... .... CMU .. .. ........... CO.NC,...MASONRY.. UNIT................. S.C. .............................................................................. SAW CUT WF ............................... WAL L FOOTING MFWF .............................................................................. MASONRY FENCE , W­ ALL FOOTING ............................... T.O. W ............. TOP..... OF... WAI_ ............................... O.C...... - . - ON ... CENTER -- -- ----- - . ...... . _.E.E< E.,___.__EI N l S H_EI.QOR__E LEVAIlQN ... SLOG ------ BUILDING - - - - - -- ---------------- ...E.W .................. EACH ... WAY ........ ................ ..... .......... .. ..PL ..................PRECAST.. LINTEL............ . .... M WF ................ MOROLI.THI C....WALL...FOO.TIN G ... I. E .. ......... ...... THICKENED ... EDGE .............. L_ GREATER OF GREATER OF L7 N 2 03L1 or 03L2 03L2 or 03L3 L4 or L3 4 v I= 4 3' -6" N jryTik �; ' - 6 3' -6 ' -6 min. $ min. min. CONT. min. /-"D" "E" BARS - "T" BARS D BARS °» 0" ,i 1 Clear -ffl I I I I ki I , I . T il - I I "B" BARS STIRRUPS OR TIE SEE °B" BARS 2" TYP 6" Typ SCHEDULE F E & NUMBER & S AC NG CONC. C DL. CONC. COL. I�L - -I- - - -I-- - L1 1 1 L2 L3 L4 TYPICAL BEAM BAR PLACING DIAGRAM NOTES : 1. PLACE A MAXIMUM OF 2 BARS PER LAYER IN 8" WIDE BEAMS. 2. SPLICE TOP BARS AT MID SPAN W/ 30 BAR DIAMETER LAP SPLICES. 3. PLACE "C" BARS OVER RIGHT HAND SUPPORT, UNLESS NOTED IN REMARKS. 4. SPLICE "I" BARS AT SUPPORTS W/ 30 BAR DIAMETER SPLICES. 5. "I" BARS AS SCHEDULED SHALL BE PLACED EACH SIDE OF BEAM. TERMITE TREATMENT CERTIFICATION NOTE: BUILDING (S) SHALL HAVE PRE - CONSTRUCTION TREATMENT PROTECTION AGAINST SUBTERRANEAN TERMITES IN ACCORDANCE WITH THE RULES AND LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES. A CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL COMPANY PERFORMING THE TREATMENT, THAT CONTAINS THE FOLLOWING STATEMENTS: "THE BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES." SOIL STATEMENT: SOIL OBSERVED TO BE SAND AND ROCK WITH BEARING CAPACITY OF 2000 PSF 1. AT THE TIME OF CONSTRUCTION, A LICENSED ARCHITECT OR REGISTERED PROFESSIONAL ENGINEER SHALL SUBMIT TO THE BUILDING OFFICIAL A LETTER ATTESTING THAT THE SITE HAS BEEN OBSERVED AND THE FOUNDATION CONDITIONS ARE SIMILAR TO THOSE UPON WHICH AND THE FOUNDATION CONDITIONS ARE SIMILAR TO THOSE UPON WHICH THE DESIGNED IS BASED. THE LETTER SHALL BE SIGNED AND SEALED. 2. THE IMPRESS SEAL OF THE ARCHITECT OR ENGINEER, AS APPLICABLE 3. A SPECIAL INSPECTOR, RETAINED BY THE OWNER, SHALL INSPECT AND SUPERVISE THE COMPACTION AND THE FOUNDATION. 4. SPECIAL INSPECTION: INSPECTION OF THE REINFORCED UNIT MASONRY AND /OR INSULATED CONCRETE FORMS PHASE OF THIS PROJECT IS REQUIRED. SUCH INSPECTION SHALL CONFORM TO THE REQUIREMENTS OF INSPECTION AS NDER THE SUPERVISION OF AA STANDARDS AS EGISTTERED AND ESSIONAL ENGINEER. COORDIENFORCING T SHALL BECIIVtADE WITH THE ARCHITECT AND ENGINEER BY THE CONTRACTOR TO SET UP A SCHEDULE OF INSPECTION PRIOR TO START OF CONSTRUCTION. THE COST OF SUCH INSPECTIONS, BY OTHER THAN THE ENFORCING AGENCY, SHALL BE PAID FOR BY THE OWNER. GROUTING: GROUTING SHALL CONFORM TO THE REQUIREMENTS OF ACI 530 -02 /ASCE 7 -05, PART 4.3 GROUTING PROCEDURES. IN NO CASE SHALL ANY LIFT BE GROUTED GREATER THEN 4' -0" IN HEIGHT. a ..... ..,...... w ; \ : , : ..:., . tom .. . ' ,. 7 Mi \A+ a: }1 I ,� '. I e ---***­***- .. - , 4. t ` ; IIIIIIIIIIIIII a qq :. .............,ate .....,, ,' :. _ , .,x..: ., ... •• .... .... , <�. -• ,gyp. , :.. «:' .. �` A , - O . • ... .. 11-1 ` .. �. ::. ., V . A 0 :• :. ::: .sl.. ` . :. :.. •. LO J. ...:,.!:2. .. •W` F ..,. .. '�' -sw �t2fF ', ;44£FRC543iAL`t>,v`Bd•`<•';' Zl llY F• J U, :... . au .1 -Q, : z .. ' , ... 0 p 9 W .... . �r � :"'. , . �'`' ,_ is art � . a.,,..., .... ...: } "fii �,, .1 ............4 , ..... ...q� >.. :.Y: .., . ... . ` .... �. :,.::: Z 3: n. . , . .. ; .�" CO[it# 3F a ,v :.7i... is :$S9• :�, - ;p €`T.i;' tr "`� �2 .. it�isA�s....,. W O .... i �> a i c \ z:: i. . 1. . . !!v, �. : :. n �. nj � :. ... t� O I. W R t' A y� : r���f p ..'. i s f� z ad t . I., :T, s� • . ;, ,. ::: .. r w 'ALt£ tiCHb H 7 .k- t• ,E'w v J3 Jai tF 1]�,1i �j .. � •• ,. w 2 .. .,,�, , ,. 6'HaTd, rE �3i43 W • �4 -4 ik'1'i63ilZ i, e• �-is' . :ai • ;' Z UA ` ....... : :�;, . :-% .... , META& *ai' aatA•.. ., ... ,., ., . . ,oti,ms» ' w �.'StatFar, .P �aii'trSt:aMitr �tivZ: ? y W p 11 �. zT.:. r. ,S` a .k y„ .'- ci ao O I" .�, e. V. •, ,I0`i�T�a:. auI », Sbzfiiiif�_ I o w ...Y . <t, .., .1 - .. ; i. : .. . •�r ,(..2 . , Il ...k. ", ft1 J ......., - :, 3, ti C ' N .b+ d ct t.. 4q LiJ �U) 1. .. . 1. t: . „... x . � .........a .; , ..: a , • � U) cc 1D = :..... ..,,.. .. r ' .. J,ii�'t.:Si '. . .: - ai .. I— V LLJ 2 :AS. .. ... .. iJt ..; �9 - , . :.. $f ,..r >..: . = Q ;�x ,y,Tet„i,g,.........., ..... y es"•Q6 ` O ......... :....: i ,. ,... ;; ! .,F .:- ........ :: <; ' ,�, Li - �r.... :. ..- - ai4' rd �: V, wry, �. ..� °s •.� .., . .. �• is �i % ,....,, %ko I ``.,`•�;3it'100HaibCi3R:Rn3� :,... �.•... ': . :• ;;:: 'R . . ...''.°J`Yti°44j.IT s: 1 " fix r % ;� >t - .. .. . :::.-: v., f. 2.. k '.vim.:' :...::: �. �riteii:i:::.. ' •• .... t, . '' % FNi' cs i .... .., ..........:.:. .: