Loading...
14-490-008RISER NOTES 1.- EXISTING METER SOCKET 400A, 3PHASE, 240V 2. EXISTING 200A, 3P, 240V, DISC. SWITCH WITH 2O0A FUSES (1 OF 2) 3. EXISTING 200A, 3P, 240V, DISC. SWITCH WITH 2O0A FUSES (2 OF 2) 4. # 1/0 AWG (PHASE), 1 # 1/0 (NEUTRAL) AND 1 #6 G IN 2" CONDUIT 5. EXISTING %* X 10' COPPER CLAD GROUNDING ROD, WITH # 2/0 GROUND ELECTRODE CONDUCTOR (PROPERLY SIZED GROUND CONNECTOR BURNDY TYPE "GAR" OR ILSCO TYPE "GPL"; CONNECT TO FOOTING / FLOOR SLAB STEEL AND TO THE BUILDING METAL WATER PIPE. 6. EXISTING ELECTRONIC TIMER -T1-, FOR SIGN CLOCK. 7. EXISTING ELECTRONIC TIMER "T2 ", FOR SITE LIGHTS 8. #3/0 AWG (PHASES), 1 # 3 (NEUTRAL), AND 1 #413 IN 2 "0 CONDUIT 9.- 1 #1 (PHASES) AND 1 #1 (NEUTRAL) & #6g IN 1 Y2 "O CONDUIT ELECTRICAL LEGEND AFF ABOVE FINISH FLOOR WALL MOUNTED FIXTURE GROUND FAUL GFCI CIRCUIT INTERRUPTOR w a_ CEILING TRACK LIGHTS ( TYP ) TYPICAL 4 4 ® WALL MOUNTED FIXTURE AND OUTLET. TYPE AS M INDICATED IN FIXTURE SCHEDULE UON UNLESS OTHERWISE NOTED J a� WALL MOUNTED EXIT FIXTURE. TYPE AS W N ~ � tC INDICATED IN FIXTURE SCHEDULE. WP WEATHER PROOF d) SINGLE RECEPTACLE OUTLET. MOUNT 18" AFF UON HOA HANDS OFF AUTO DUPLEX RECEPTACLE OUT. MOUNT 18" AFF C) MI LION, 20A, 120V . +46" MOUNTING HEIGH AFG/ z 1 to Z ABOVE FINISH GRADE N [� DITTO AS ABOVE, BUT GROUND FAULT INTERRUPTER F- CONDUIT STUBBED AND CAPPED O OR BUSHED U) QUADRUPLEX RECEPTACLE OUTLET. MOUNT 18" AFF. O-- CONDUIT UP I-Q FLUSH MOUNTED OUTLET BOX. HEIGHT AS REQUIRED cm FOR CONNECTION TO EQUIPMENT C-- CONDUIT DOWN �� FUSIBLE SAFETY SWITCH W/ NUMBER OF POLES AND RATING .. O ujZ AS REQUIRED NEMA -3R ENCLOSURE IF LOCATED OUTDOOR E5 SINGLE POLE SWITCH MOUNT 48" AFF CL MOTOR CONNECTION. NUMBER INDICATES HORSE POWER 2 F= FRACTINAL HP. ALL MOTORS SHALL BE PROVIDED WITH $3 THREE WAY SWITCH MOUNT 48" AFF DISCONNECTING MEANS AND OVERLOAD PROTECTION. INCANDESCENT LIGHT Q CIRCUIT BREAKER PANELBOARD. FLUORESCENT FIXTURE AND OUTLET. TYPE AS INDICATED IN FIXTURE SCHEDULE SPECIAL OUTLET (SECURITY CAMERA) O FLOOR OUTLET Q SPECIAL CABINET. TELEPHONE TYPE TERMINAL CABINET LION 120V ® EXHAUST FAN Q JUNCTION BOX ® DUPLEX RECEPTACLE CEILING MOUNTED V TELEPHONE OUTLET. MOUNT 18" AFF. SEE DETAIL AND NOTES FOR CONDUIT WIRING REQUIREMENTS. EMERGENCY LIGHT 2) E.L. EXIT SING Z METER Z ? INTERIOR ROOM Z Z 8 BUILDING 3 "0 FROM FPL Z D O O 1 Eli NEW I 9 EXISTING 4 O 125A I 200A O PANEL PANEL "B" "A 5 LG ROOM BUILDING METER INTERIOR DMEUTAIL WATER PIPE BUILDING STEEL EXISTING ELECTRICAL RISER DIAGRAM ELECTRICAL GENERAL NOTES 1. ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, (NEC) 2008 AND THE F.B.C. 2010, NFPA 70E, RULES, AND ORDINANCES HAVING JURISDICTION. 2• IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PROVIDE ALL LABOR, MATERIALS, AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK SHOWN AND /OR NOTED ON THE DRAWINGS AND SPECIFICATIONS. 3. ALL REQUIRED INSURANCE SHALL BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 4. ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE PRIOR TO BID AND VERIFY ALL CONDITIONS, LOCATIONS, DIMENSIONS AND COUNTS AS SHOWN AND /OR NOTED ON THE DRAWINGS. THIS SHALL INCLUDE ANY AND ALL FABRICATIONS REQUIRED PRIOR TO INSTALLATION. 5• IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCED ORDERING OF LONG LEAD ITEMS SO AS NOT TO INTERFERE WITH THE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. 6• CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN (1) YEAR FROM DATE OF ACCEPTANCE, UNLESS INDICATED OR SPECIFIED OTHERWISE. 7. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 8. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR TO ORIGINAL CONDITIONS ANY AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT AND FURNISHINGS CAUSED DURING PERFORMANCE OF WORK. 9. ALL ELECTRICAL EQUIPMENT, DEVICES, WIRE, ETC., SHALL BE LISTED FOR THE INTENDED USE, WITH UNDERWRITER'S LABORATORIES, INC. (UL) WHERE STANDARDS HAVE BEEN ESTABLISHED BY UL AS A MINIMUM, ALL EQUIPMENT SHALL MEET APPLICABLE STANDARDS FOR THE TYPE OF EQUIPMENT AND INTENDED USE OF THE FOLLOWING: A. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI). B. ILLUMINATING ENGINEERS SOCIETY (IES). C. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM). D. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA). NOTE: THESE STANDARDS ARE SUBORDINATE TO CODES AND STANDARDS SET BY UL. 10. IT SHALL NOT BE THE INTENT OF THESE PLANS AND /OR SPECIFICATIONS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR SHALL BE EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. 11. ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATICALLY. EXACT ROUTING SHALL BE DETERMINED IN THE FIELD, UNLESS OTHERWISE NOTED. THE ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL THE PROPER NUMBER OF CONDUCTORS IN ALL RACEWAYS AS REQUIRED TO ACCOMPLISH THE PROPER FUNCTIONING OF THE DEVICE OR EQUIPMENT AS SHOWN. 12. ELECTRICAL CONTRACTOR SHALL NOT SCALE DRAWINGS. CONTRACTOR SHALL REFER TO ELECTRICAL CONTRACTOR SHALL NOT SCALE DRAWINGS. CONTRACTOR SHALL REFER TO UNLESS NOTED OTHERWISE. 13. THE ELECTRICAL CONTRACTOR SHALL KEEP ALL AREAS IN WHICH WORK IS BEING PERFORMED, FREE FROM DEBRIS AT ALL TIMES AND SAID AREAS SHALL BE LEFT BROOM CLEAN AT THE END OF EACH WORKING DAY. 14. CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS, AND TESTING. 15. ARCHITECTURAL AND /OR ENGINEERING EXPENSES THAT ARE INCURRED DUE TO REVISIONS OR SUBSTITUTIONS REQUESTED BY THE CONTRACTOR SHALL BE PAID FOR BY THAT CONTRACTOR. 16• COORDINATE ALL ELECTRICAL SITE WORK WITH GENERAL CONTRACTOR PRIOR TO INSTALLATION. 17. FOR ELECTRIC POWER SYSTEM. A. COORDINATE POWER SERVICE WITH POWER COMPANY. B. VERIFY LOCATION OF POWER SERVICE TERMINATION WITH POWER COMPANY PRIOR TO SUBMITTING BID. 18. FOR TELEPHONE SYSTEM: A. PROVIDE GROUNDING FOR ALL TELEPHONE OUTLETS AND EQUIPMENT PER REQUIREMENTS OF TELEPHONE COMPANY. B. TELEPHONE CONDUITS SHALL NOT BE INSTALLED IN THE SAME TRENCH WITH POWER AND LIGHTING CONDUITS. C. MARK TERMINATIONS OF TELEPHONE CONDUIT AS DIRECTED BY TELEPHONE COMPANY. D. VERIFY LOCATION OF TELEPHONE SERVICE WITH TELEPHONE COMPANY, PRIOR TO SUBMITTING BID. E. USE EXTERIOR GRADE 3/4" PLYWOOD BACKBOARDS FOR MOUNTING TELEPHONE EQUIPMENT AND TERMINAL STRIPS. PAINT BOARD ON ALL SIDES AND EDGES WITH TWO COATS OF FLAT BLACK ASPHALT PAINT 19. ALL CONDUCTORS SHALL BE IN CONDUITS. ALL CONDUITS SHALL BE GALVANIZED RIGID STEEL (GRS) EXCEPT THAT: (A) PVC CONDUITS MAY BE USED UNDERGROUND PROVIDED ELBOWS AND RISERS ARE GRS, WHERE SUBJECT TO PHYSICAL DAMAGE (B) ELECTRICAL METALLIC TUBING (EMT) MAY BE USED IN OR ON WALLS OR CEILINGS WHERE NOT SUBJECT TO MECHANICAL DAMAGE, DAMP OR CORROSIVE CONDITIONS, (C) LIQUID TIGHT FLEXIBLE CONDUIT WHERE REQUIRED, (D) FLEXIBLE METALLIC CONDUIT (MC CABLE W /GROUNDING CONDUCTOR), WHERE REQUIRED IN DRY LOCATIONS ONLY. ALL CONDUITS IN HAZARDOUS AREAS (PER NEC) SHALL MEET THE REQUIREMENTS OF NEC CHAPTER 5. CONTRACTOR MAY USE ROMEX (R) INDOOR IN DWELLING UNITS. 20. FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE PULL BOXES, SUCH THAT NO SINGLE CONDUIT RUN HAS BENDS IN EXCESS OF 360. PULL BOXES SHALL BE SUITABLE AND APPROVED FOR THE INTENDED USE. WHERE CONDUITS PASS UNDERNEATH PAVED AREAS THEY SHALL BE RGS. WHERE UNDERGROUND CONDUITS ARE NOT EXPOSED TO MECHANICAL DAMAGE OR ARE NOT UNDER PAVED AREAS, THEY MAY BE SCHEDULE 40 PVC, BUT ALL CONDUIT RISERS SHALL BE RGS. RGS CONDUITS SHALL 22. APPLY BnmASTIC COATING TO ALL METALLIC CONDUITS IN SLABS OR UNiia ROUND. - � � � = 23. ALL CONDUCTORS SHALL BE COPPER U.O.N., TYPE THHN OR THWN INSULATION, RATED___ 75'C WET /DRY EXCEPT WHERE OTHERWISE REQUIRED BY U.L OR CODES UNLESS OTHERWISE NOTED. MINIMUM WIRE SIZE SHALL BE #12 AWG EXCLUDING CONTROL WIRING. 24. WIRE WAYS SHALL BE SIZED AS REQUIRED, PER NEC, UNLESS OTHERWISE NOTED. 25• ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT (NEMA 3R) WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT SHALL BE LIQUID- TIGHT. 26. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURE FOR OTHER CLASSIFIED AREAS. PROPER PLASTER RINGS SHALL BE USED WITH OUTLET BOXES. PROPER COORDINATION BETWEEN ELECTRICAL SUBCONTRACTOR AND GENERAL CONTRACTOR FOR PLASTER RING INITIATION WILL BE REQUIRED. NO "GOOF" RINGS SHALL BE ALLOWED. ALL OUTLET BOXES SHALL BE SECURELY FASTENED. 27. CONTRACTOR FOR PLASTER RING INITIATION WILL BE REQUIRED. NO "GOOF" RINGS 28. MOTOR STARTERS SHALL BE MANUAL OR MAGNETIC, AS INDICATED OR REQUIRED, WITH OVERLOAD PROTECTION FOR EACH PHASE. ALL MOTOR SHALL BE EQUIPED WITH DISCONNECT MOTOR STARTER COMBINATION. 29. FURNISH AND INSTALL DISCONNECT SWITCHES AND WIRING FOR AIR CONDITIONING EQUIPMENT PER MANUFACTURER RECOMMENDATIONS. CONTROLS SHALL BE PROVIDED BY DIVISION 15. ELECTRICAL CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATING FOR EQUIPMENT PROVIDED PRIOR TO INSTALLATION. 30. DISCONNECT SWITCHES SHALL BE SIZED PER NEC TO ACCOMMODATE EQUIPMENT SERVED, DISCONNECT SWITCHES SHALL BE SIZED PER NEC TO ACCOMMODATE EQUIPMENT SERVED, RATED, HEAVY -DUTY TYPE. 31. FUSES SHALL BE CURRENT LIMITING, PER U.L., RATED 600 VOLTS, UNLESS OTHERWISE NOTED. A. NONTIME DELAY FUSES IN MAIN SWITCHES AND SWITCHES FEEDING PANELS. B. TIME DELAY FUSES FOR MOTOR AND A/C CIRCUITS. 32• CIRCUIT BREAKERS SHALL BE BOLT -ON U.O.I., INVERSE TIME -TYPE (THERMAL - MAGNETIC). TWO AND THREE -POLE CIRCUIT BREAKERS SHALL HAVE COMMON TRIP. ALL PANELBOARDS SHALL HAVE COPPER BUS. 33. UNLESS NOTED AS EXISTING, ALL EQUIPMENT, WIRING, DEVICES, ETC. SHALL BE NEW. 34. WIREWAYS SHALL BE SIZED AS REQUIRED, PER NEC, U.O.N. 35. WHERE CORE DRILLING OF FLOOR /WALLS IS REQUIRED, CONTRACTOR SHALL SEAL OPENINGS WATERTIGHT AFTER UTILITIES HAVE BEEN INSTALLED. LOCATION OF CORED HOLES SHALL BE COORDINATED WITH LOCATION OF EQUIPMENT IN A MANNER TO BE CLEAN AND FUNCTIONAL THE CONTRACTOR SHALL INSTALL ONLY ONE CONDUIT PER HOLE AND SEAL THE OPENING AROUND THE CONDUIT AS SPECIFIED. 36. PROVIDE FIRE RETARDANT U.L APPROVED SEALANT ON ALL PENETRATIONS OF FIRE PROVIDE FIRE RETARDANT U.L APPROVED SEALANT ON ALL PENETRATIONS OF FIRE SIBILITY OF THE ELECTRICAL CONTRACTOR TO VERIFY, PRIOR TO SUBMITTING BID, LOCATIONS OF ALL SUCH FIRE RATED PARTITIONS, WALLS, AND STRUCTURAL SLABS. 37. BALLASTS SHALL HAVE MIN. POWER FACTOR OF 0.90. BALLASTS FOR METAL HALIDE AND HIGH PRESSURE SODIUM FIXTURES SHALL BE CONSTANT WATTAGE TYPE WITH 5% LAMP WATTS FOR 10% NOMINAL LINE VOLTAGE VARIATION. 38. THE EQUIPMENT GROUNDING TERMINAL BARS OF THE NORMAL AND EMERGENCY ELECTRICAL SYSTEM PANELBOARDS SERVING THE SAME BUILDING SHALL BE BONDED TOGETHER WITH AN INSULATED, CONTINUOUS, COPPER CONDUCTOR NOT SMALLER THAN NUMBER 6. 39. PROVIDE LAMPS WITH FIXTURES, SEE LUMINAIRE SCHEDULE FOR LAMP TYPE.CONTRACTOR SHALL VERIFY EACH FIXTURE VOLTAGE PRIOR TO ORDERING. 40. ALL CONNECTIONS TO GROUND RODS & BUILDING STEEL SHALL BE MADE WITH U.L. APPROVED WELDED CONNECTIONS, UNLESS NOTED OTHERWISE. THE CONTRACTOR SHALL FORM A GROUNDING ELECTRODE SYSTEM AS PER NEC 250 -50. 41. PROVIDE MOUNTING BACKBOARDS FOR ELECTRICAL AND COMMUNICATION EQUIPMENT. BACKBOARDS SHALL BE OF TYPE "AC" PLYWOOD, PAINTED ON BOTH SIDES AND EDGES WITH TWO COATS OF LIGHT GREY PAINT. 42. PROVIDE A FUSE HOLDER AND FUSE IN THE PRIMARY SIDE OF EACH UNGROUNDED CONDUCTOR FOR EACH BALLAST (BUSSMAN HEB AND FNQ OR EQUAL), AT THE HAND HOLE OF EACH EXTERIOR POLE MOUNTED LIGHTING FIXTURE OR J -BOX FOR WALL OR GROUND MOUNTED EXTERIOR FIXTURES. 43. PROVIDE TEMPORARY ELECTRICAL SERVICE FOR USE BY ALL TRADES DURING CONS TRUCTION AND REMOVE SAME AT COMPLETION OF PROJECT, 44. THE ELECTRICAL CONTRACTOR SHALL FURNISH A COMPLETE SET OF AS -BUILT DRAWINGS, SHOWING ALL CHANGES AND DEVIATIONS TO THE ARCHITECT /ENGINEER PRIOR TO COMPLETION OF THE PROJECT. 45. PREPARE AND AFFIX A TYPEWRITTEN DIRECTORY TO THE INSIDE COVER OF EACH PANEL BOARD INDICATING LOADS SERVED BY EACH CIRCUIT AND PANEL FEEDING THE BOARD. PANELBOARD INDICATING LOADS SERVED BY EACH CIRCUIT AND PANEL FEEDING THE 46. BOARD.CONTRACTOR TO VERIFY SPECIFIC TYPE OF METER CAN TO BE USED WITH F.P.L. PRIOR TO BID.ALL 3 PHASE METER AND COMMERCIAL USE SHALL HAVE LEVELER BY PASS AS PER FPL REQUIREMENTS: A. PROVIDE A PERMANENT SIGN ON THE MAIN ELECTRICAL ROOM DOOR TO THE BLDG. STATING THAT THE SERVICE DISCONNECTS ARE LOCATED INSIDE. B. SIGNS SHALL BE PLACED AT THE MAIN DISCONNECT EQUIPMENT INDICATING TYPE AND LOCATION OF ON -SITE EMERGENCY POWER SOURCES. C. VOLTAGE AND SERVICE NUMBER SHALL BE INDICATED AT EACH DISCONNECT. FOR EMERGENCY EXIT SIGNS AND EMERGENCY BATTERY PACKS MAKE CONNECTION 47. AHEAD OF ALL SWITCHES. PROVIDE SELF TEST DEVICES. THE CONTRACTOR SHALL SUBMIT 6 COPIES OF EQUIPMENT SHOP DRAWINGS FOR 48. ELECTRICAL EQUIPMENT TO THE ENGINEER FOR REVIEW, PRIOR TO ORDERING SUCH EQUIPMENT. C, ITIV I- uul�Uirl� r: err uC"URt ,L v;�C7-10fj r ALL DRAMNGS AND WRITTEN MATERIAL IN APPEARING HEREIN CONSTITUTE ORIGINAL AND UNPUBLISHED WORK OF THE ARCHITECT. THE SAME MAY NOT BE DUPLICATED. USED OR DISCLOSED VATHOUT WRITTEN CONSENT OF THE ARCHITECT. JB No.: 13.05855. RET REVISIONS: DATE: 12/16/2013 CHECKED BY: DRAWN BY: AM P LOT: 100% SHEET INDEX: ELECTRICAL PLAN, NOTES, DETAILS SHEET No.: E -1 a a w a_ M J J J a� O W N ~ � tC = O O W �aW° Q M CD C) MI W o z 1 to Z , N [� W �' O U) 9) (1) 0) O LLJ cm .. O ujZ E5 CL o =O tl O r ALL DRAMNGS AND WRITTEN MATERIAL IN APPEARING HEREIN CONSTITUTE ORIGINAL AND UNPUBLISHED WORK OF THE ARCHITECT. THE SAME MAY NOT BE DUPLICATED. USED OR DISCLOSED VATHOUT WRITTEN CONSENT OF THE ARCHITECT. JB No.: 13.05855. RET REVISIONS: DATE: 12/16/2013 CHECKED BY: DRAWN BY: AM P LOT: 100% SHEET INDEX: ELECTRICAL PLAN, NOTES, DETAILS SHEET No.: E -1 a a w a_ M � tC CD Q M CD MI W o z U , N [� WW co Q cm r ALL DRAMNGS AND WRITTEN MATERIAL IN APPEARING HEREIN CONSTITUTE ORIGINAL AND UNPUBLISHED WORK OF THE ARCHITECT. THE SAME MAY NOT BE DUPLICATED. USED OR DISCLOSED VATHOUT WRITTEN CONSENT OF THE ARCHITECT. JB No.: 13.05855. RET REVISIONS: DATE: 12/16/2013 CHECKED BY: DRAWN BY: AM P LOT: 100% SHEET INDEX: ELECTRICAL PLAN, NOTES, DETAILS SHEET No.: E -1