ELECTRICAL SPECIFICA TIONS
GENERAL
A. SEE SECTION 100 OF THE GENERAL SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
B. COORDINATE WITH ALL TRADES TO AVOID INTERFERENCE AMONG MECHANICAL, ELECTRICAL
ARCHITECTURAL AND STRUCTURAL ITEMS, PROVIDE ALL NECESSARY OFFSETS AND FITTINGS IN CIRCUITRY
AND OTHER ITEMS REQUIRED TO INSTALL THE WORK WITHOUT INTERFERENCES.
C. ALL EQUIPMENT INSTALLED SHALL BE NOW AND SHALL CONFORM IN ALL RESPECTS TO THE LATEST
APPROVED STANDARDS OF EFF., ANSI, NEMA AND UNDERWRITERS LABORATORIES, INC. UNLESS INDICATED
OTHERWISE. SUBSTITUTIONS SHALL ONLY BE ACCOMPLISHED AT THE DISCRETION OF THE ENGINEER.
D. SHOP DRAWINGS ARE TO BE SUBMITTED AND APPROVED BEFORE THE EQUIPMENT IS ORDERED SUBMIT
SIX (6) COPIES OF SHOP DRAWINGS TO THE ENGINEER.
E. UNLESS SPECIFICALLY INDICATED OTHERWISE, REMOVE ALL LIGHTING SWITCHES, AND ASSOCIATED
CIRCUITRY. CIRCUITRY TO BE REMOVED SHALL BE ALL CONDUCTORS AND ANY EXPOSED RACEWAYS AND
ALL RACEWAY THAT BECOMES EXPOSED UPON REMOVAL OF WALLS AND CEILINGS. NOT ALL DEVICES TO
BE REMOVED ARE INDICATED.
F. UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL CIRCUITRY, EQUIPMENT, DEVICES, ETC. NOT NOTED
AS EXISTING TO REMAIN OR TO BE RELOCATED, SHALL BE NEW. CONTRACTOR MAY REUSE. ALL
EXISTING WALL RECEPTACLES, AND FLOOR BOXES AND OUTLETS WHICH THE ENGINEER DEEMS ARE IN
REUSABLE CONDITION. REMOVE ALL DEVICES AND CIRCUITRY NOT BEING REUSED. CIRCUITRY TO BE
REMOVED SHALL BE REMOVED BACK TO THE SOURCE AND ALL HOLES SHALL BE REPAIRED TO CONFORM
TO FINISHED SURFACE. ALL CIRCUITS THAT ARE TO REMAIN IN SERVICE UPON COMPLETION OF THIS
PROJECT WHICH ARE PRESENTLY FED MUST BE CONTINUED IN SERVICE. OUTAGES EXISTING CIRCUITS
TO REMAIN SHALL BE COORDINATED WITH THE OWNER.
G. PROJECT ADJACENT MATERIALS INDICATED TO REMAIN. INSTALL AND MAINTAIN DUST AND NOISE BARRIERS
TO KEEP DIRT, DUST AND NOISE FROM BEING TRANSMITTED TO ADJACENT AREAS. REMOVE PROTECTION
AND BARRIERS AFTER DEMOLITION OPERATIONS ARE COMPLETE.
H. LOCATE, IDENTIFY AND PROTECT ELECTRICAL SERVICES PASSING THROUGH DEMOLITION AREA AND
SERVING OTHER AREAS OUTSIDE THE DEMOLITION LIMITS. MAINTAIN SERVICES TO AREAS OUTSIDE
DEMOLITION LIMITS. WHEN SERVICES MUST BE INTERRUPTED, INSTALL TEMPORARY SERVICES FOR
AFFECTED AREAS.
I. THE ENTIRE ELECTRICAL INSTALLATION SHALL CONFORM TO THE LATEST EDITIONS OF THE NATIONAL
ELECTRICAL CODE AND ALL OTHER RULES AND REGULATIONS OF THE LOCAL ELECTRICAL AND BUILDING
CODES.
J. ALL ELECTRICAL EQUIPMENT SHALL BEAR THE UNDERWRITER'S LABORATORIES LABEL.
K. ALL EQUIPMENT TO BE PROVIDED BY THE CONTRACTOR SHALL BE MANUFACTURED BY GENERAL ELECTRIC
OR SQUARE -D COMPANY, ONLY ONE OF THE MANUFACTURE'S ABOVE SHALL BE PERMITTED TO BE
SELECTED.
L. PROVIDE TEMPORARY SERVICE AS DIRECTED FOR LIGHTING AND POWER EQUIPMENT (DRILLS, SAWS, ETC.)
VERIFY TEMPORARY REQUIREMENTS WITH GENERAL CONTRACTOR, TEMPORARY LIGHTING AND POWER SHALL
MEET OSHA REQUIREMENTS AND LOCAL CODES. TEMPORARY POWER SHALL BE 120V.
M. ADVANCE NOTICE SHALL BE GIVEN TO OWNER BEFORE COMMENCEMENT OF WORK ON ANY ELECTRICAL
CIRCUITRY, WHETHER OR NOT A OUTAGE IS REQUIRED.
N. UNLESS SPECIFICALLY NOTED ON THE PLANS, ALL CIRCUITRY, EQUIPMENT, DEVICES, ETC.. NOT NOTED
"EXISTING TO REMAIN OR "TO BE RELOCATED" SHALL BE NEW.
0. ALL FEEDER RACEWAYS, ELECTRICAL PANELS AND ALL MAJOR PIECES OF EQUIPMENT SHALL BE CLEARLY
LABELED WITH MINIMUM 1" HIGH LETTERS.
P. ALL WORKMANSHIP, MATERIALS AND EQUIPMENT SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR
AFTER ACCEPTANCE OF AREA OF TENANT.
Q. THE CONTRACTOR SHALL VISIT EXISTING SITE AND DETERMINE CONDITIONS WHICH MAY AFFECT HIS OR
HER BID.
S. THE CONTRACTOR SHALL RESTORE ALL AREAS AND SYSTEMS DISTURBED BY HIS WORK TO THE SATISFACTION
OF THE PROJECT MANAGER.
T. THE WORK SHALL CONFORM TO THE LATEST EDITION OF THE LOCAL UNIFORM STATEWIDE BUILDING CODE
AND THE AUTHORITIES DESIGN MANUAL. A LICENSED QUALIFIED ELECTRICIAN SHALL BE ON THE JOB
SITE AT ALL TIMES DURING THE EXECUTION OF ANY ELECTRICAL WORK.
U. EXCEPT AS OTHERWISE NOTED, ALL EXISTING ELECTRICAL WORK WHICH WILL NOT BE RENDERED ABSOLUTE
AND WHICH MAY BE DISTURBED DUE TO ANY CHANGES REQUIRED UNDER THIS CONTRACT SHALL BE
RESTORED TO ITS ORIGINAL OPERATING CONDITION.
V. FINAL TESTING AT THE TIME OF FINAL INSPECTION AND TESTS. ALL CONNECTIONS AT PANELBOARDS,
DEVICES AND EQUIPMENT AND ALL SPLICES MUST BE COMPLETED. EACH BRANCH CIRCUIT AND ITS
RESPECTIVE, CONNECTED EQUIPMENT MUST TEST FREE OF SHORT CIRCUITS.
W. UPON COMPLETION OF THE WORK, CLEAN AND POLISH ALL EXPOSED SURFACES IN ACCORDANCE WITH
THE MANUFACTURER'S RECOMMENDATIONS.
JOB RESPONSIBILITY:
A. PROVIDE ADEQUATE STORAGE FACILITIES FOR MATERIAL AND EQUIPMENT DURING THE PROCESS OF
THE WORK.
B. BE RESPONSIBLE FOR THE CONDITION OF ALL MATERIAL AND EQUIPMENT EMPLOYED IN THE
ELECTRICAL INSTALLATION UNTIL FINAL ACCEPTANCE BY THE OWNER. PROJECT SAME FROM ANY
CAUSE WHATSOEVER.
C. BE RESPONSIBLE FOR THE REPLACEMENT OF ALL DAMAGED OR DEFECTIVE WORK, MATERIALS
EQUIPMENT DO NOT INSTALL SENSITIVE OR DELICATE EQUIPMENT UNTIL MAJOR CONSTRUCTION
WORK IS COMPLETED.
D. OBSERVE AND CONFORM TO APPLICABLE SAFETY REGULATIONS, INCLUDING THOSE REQUIRED BY
THE OWNER'S REPRESENTATIVES.
E. ERECT AND MAINTAIN SUITABLE BARRIERS, PROTECTIVE DEVICES, LIGHTS AND WARNING SIGNS FOR
THE PROTECTION OF NEGLIGENCE, STRIKES, VIOLENCE OR THEFT UP TO THE TIME OF FINAL ACCEPTANCE BY
THE OWNER.
G. BE RESPONSIBLE FOR ANY LOSS OR INJURY TO PERSONS OR PROPERTY RESULTING FORM NEGLECT OR
ANY OTHER CAUSES ON THE PAINT OF THE EMPLOYEES.
H. DO NOT LEAVE ANY ELECTRICAL WORK IN HAZARDOUS CONDITION, EVEN TEMPORARY.
I. ERECT, MAINTAIN AND FINALLY REMOVE ALL SCAFFOLDS, STAGING, FORMS, PLATFORMS AND LADDERS
REQUIRED FOR THE ELECTRICAL INSTALLATION.
J. DO NOT INSTALL WORK FOR WHICH AN EXTRA CHARGE IS TO BE MADE WITHOUT WRITTEN
APPROVAL FROM THE OWNER'S REPRESENTATIVE AND THE OWNER. A WRITTEN REQUEST FOR EXTRA
WORK SHALL STATE THE NATURE OF THE WORK, BY WHOM REQUESTED AND THE PRICE TO BE
CHARGED.
LEGEND:
3) EXIT LIGHT WITH BATTERY
EXIT BACK -UP -90 MIN.
DUPLEX RECEPTACLE.
-e SINGLE OUTLET
® SPECIAL OUTLET
NEW WIRING
NOT WIRE
NEUTRAL WIRE
HOME RUN TO PANELBOARD
GROUND WIRE SIZED AS PER NEC ART. 250
C1�C7 EXIT LIGHT /EMERG. COMBO WITH BATTERY
BACK -UP -90 MIN.
EMER. LIGHT WITH BATTERY
BACK -UP -90 MIN.
EF. EXHAUST FAN
TELEPHONE OUTLET
I DATA
NOTE:
COORDINATE WITH OWNER REPRESENTATIVE
FOR NUMBER AND LOCATION OF TELEPHONE
OUTLETS AND PROVIDE THEM ACCORDINGLY
WITH ALL ASSOCIATED RUNS TO TELEPHONE
BO. IN TEL. ROOM.
RACEWAYS, BOXES, CONDUITS.
1. WIRING METHODS: a. EXPOSED CONDUIT b. CONCEALED CONDUIT OR AS APPROVED ARMOR -CLAD (MC)
CABLE.
2. ALL CIRCUITRY IN FINISHED AREAS SHALL BE RUN CONCEALED. MINIMUM SIZES CONDUIT SHALL BE 112 ".
J. CONDUIT CONNECTIONS AND COUPLINGS SHALL BE OF THE ALL -STEEL COMPRESSION TYPE WITH
INSULATED THROAT
4. EXPOSED AND CONCEALED CIRCUITRY WHETHER CONDUIT AND WIRE OR CABLE) SHALL BE RUN TIGHT
TO CEILING SLAB (AS HIGH AS POSSIBLE TO MAXIMIZE HEADROOM) IN A NEAT, WORKMANLIKE MANNER
ALL RUNS SHALL BE PARALLEL OR PERPENDICULAR TO BUILDING WALLS.
5. ALL CIRCUITRY RUNS INDICATED ARE DIAGRAMMATIC. THE CONTRACTOR SHALL DETERMINE IN THE FIELD
THE MOST SUITABLE ROUTES.
6. ALL EMPTY RACEWAYS SHALL CONTAIN A DRAG WIRE. EMPTY RACEWAYS 2" OR LARGER IN SIZE SHALL
- HAVE A MAXIMUM OF 3 -90 DEGREE BENDS. PROVIDE 314" EMT FROM EACH TELEPHONE OR
COMMUNICATIONS OUTLET DEVICES TO CEILING SPACE FOR ALL INSULATED WALLS.
7. OUTLET BOXES SHALL BE A MINIMUM OF 4" SQUARE WITH THE APPROPRIATE PLASTER RING OR TILE
COVER.
8. WHERE EXISTING WALLS ARE FURRED OUT AND DEVICES ARE NOT NOTED TO BE REMOVED
PROVIDE EXTENSION BOXES TO BRING FACE OF DEVICES FLUSH WITH NEW FINISH SURFACE
AND CONTINUE IN SERVICE.
9. FINAL CONNECTION TO ALL MOTORS OR VIBRATING EQUIPMENT SHALL BE WITH FLEXIBLE
CONDUIT.
10. PROVIDE PULL. JUNCTION, OUTLET AND FLOOR BOXES WHERE SHOWN AND REQUIRED. SIZE
AS REQUIRED BY THE NEC AND OTHER APPLICABLE STATE AND LOCAL CODES.
11. ALL JUNCTION BOXES SHALL BE OF CODE GAUGE AND OF THE SIZE REQUIRED TO ACCOMMODATE
CONDUCTORS SHOWN.
WIRE AND CABLE:
1. ALL CONDUCTORS SHALL BE COPPER, MINIMUM #12 (EXCEPT CONTROL CONDUCTORS AND LIGHTING
TIPS AS PERMITTED BY NEC, CONDUCTORS FOR SWITCHING LIGHTS SHALL NOT BE CONSIDERED
CONTROL CONDUCTORS) WITH 600 VOLT TYPE '7H11N -THWN" INSULATION. CONDUCTORS J10 AND
LARGER SHALL BE STRANDED.
2. WHERE APPROVED BY THE AUTHORITIES HAVING JURISDICTION AND THE OWNER "MC" CABLE MAY BE
UTILIZED FOR INTERIOR BRANCH CIRCUITS.
J. ALL WC" CABLE SHALL HAVE A GREEN INSULATED GROUND WIRE IN ADDITION TO THE BONDING WIRE
4. ALL 120 VOLT CIRCUIT HOMERUNS WHICH ARE OVER 100 LINEAR FEET SHALL BE #10 CONDUCTORS
MINIMUM.
5. RUN MULTIPLE HOMERUNS TO ALTERNATELY NUMBERED PANELBOARD CIRCUITS (I.E. 1,3,5)
6. ALL CIRCUITRY RUNS ARE DIAGRAMMATIC. THE CONTRACTOR SHALL DETERMINE IN THE FIELD THE
MOST SUITABLE ROUTES. ALL RECEPTACLES, LIGHTING FIXTURES, MOTORS, ETC. SHALL BE GROUNDED
PER NEC.
7. (ALL RECEPTACLE CIRCUITS SHALL CONTAIN A 1112 INSULATED GROUND CONDUCTOR.)
8. THE CONTRACTOR'S RESPONSIBILITY TO BALANCE ALL PHASES IN THE PANEL. (BOARD LOAD)
9. ALL MOTOR CONNECTIONS OUTSIDE SHALL BE DONE WITH FLEXIBLE SEALITE CONDUIT.
10. ALL WIRING AND EQUIPMENT FOR 'PLACES OF ASSEMBLY" SHALL COMPLY WITH ARTICLE 318 OF THE
NEC. CIRCUIT NUMBERS SHOWN ARE FOR IDENTIFICATION ONLY.
11, WIRE AND CABLE SHALL BE AS MANUFACTURED BY ANACONDA, WALKER, GENERAL CABLE, GENERAL
ELECTRIC OR SIMPLEX AND SHALL BE COPPER, MINIMUM CONDUCTIVITY OF 987.
WIRING DEVICES, SWITCHES, RECEPTACLES AND TELEPHONE OUTLETS
1. THE LOCATION OF ALL WIRING DEVICES AND TELEPHONE OUTLETS SHALL BE VERIFIED
BEFORE INSTALLATION WITH THE ARCHITECT. THE ARCHITECT MAY, AT HIS OPTION, RELOCATE ANY
DEVICES 5 FEET AT NO CHARGE TO THE OWNER.
2. WHERE TWO OR MORE DEVICES ARE SHOWN TOGETHER ON THE PLANS. A MULTI -GANG BOX AND
PLATE SHALL BE USED. DEVICES OF DIFFERENT VOLTAGES SHALL BE SEPARATED BE
PERMANENTLY INSTALLED BOX PARTITIONS.
J. ALL OUTLETS SHOWN ON A WALL BACK TO BACK SHALL BE OFFSET A MINIMUM OF 6"
HORIZONTALLY, 2' -0" IN RATED WALLS.
4. WALL MOUNTED WIRING DEVICES SHALL BE IVORY IN COLOR EQUAL TO THE FOLLOWING: a. SINGLE
POLE SWITCH: HUBBELL 1221 b. DUPLEX RECEPTACLE: HUBBELL 5352 c. DUPLEX RECEPTACLE -
HUBBELL 5352- ORANGE COLOR FOR COMPUTER CIRCUITS, IDENTIFY CIRCUITS ON DEVICE PLATE.
5. DEVICE PLATES AS DIRECTED BY THE ARCHITECT
6. COORDINATE LIGHT SWITCHES SHOWN ON DRAWING WITH DOOR SWINGS. LOCATE LIGHT SWITCH
ON LOCK SIDE OF DOOR.
7. COORDINATE WALL MOUNTED TELEPHONE OUTLET LOCATION WITH THE ARCHITECT
TELEPHON /DATA CONDUCTORS WILL BE INSTALLED BY OTHERS. PROVIDE FOR COMPLETE
INSTALLATION OF FLOOR DEVICES INCLUDING ALL ACCESSORIES,
8. MOUNTING HEIGHT FOR RECEPTACLES AND TELEPHONE OUTLETS SHALL BE PER PLANS OR AS
REQUIRED BY THE LOCAL JURISDICTION REQUIREMENTS. IF NOT NOTED PROVIDE AT 18" A.F.F.
BY THE LOCAL JURISDICTION REQUIREMENTS.
9. MOUNTING HEIGHT FOR SINGLE POLE TOGGLE SWITCHES SHALL BE 48" A.F.F. OR AS REQUIRED
10. THE TELEPHONE SYSTEM OUTLET LOCATIONS SHALL BE AS SHOWN ON THE DRAWINGS AND
AS REQUIRED BY THE TELEPHONE COMPANY FOR INSTALLATION THE ELECTRICAL CONTRACTOR
SHALL FURNISH DEVICE RING AND 114" NYLON PULL CORD FOR EACH LOCATION TO FACILITATE
THE PULLING OF CABLES IN THE FUTURE. PROVIDE BLANK DEVICE PLACES 11. EACH
RECEPTACLE AND OUTLET SHALL BE LABELED TO INDICATE PANEL AND CIRCUIT BREAKER'S)
SUPPLYING THE RECEPTACLE OR OUTLET. PROVIDE PRESSURE SENSITIVE, LAMINATED LABEL WITH
BLACK LETTERS ON WHITE BACKGROUND. LETTERING HEIGHT IS 1/8"
DISCONNECTS
1. PROVIDE SAFETY SWITCHES INDICATED AND AS REQUIRED BY CODE WITH RATINGS AS
REQUIRED BY THE SYSTEM VOLTAGE, PHASE AND LOAD SERVED.
2. PROVIDE NON -FUSED SAFETY SWITCHES UNLESS SPECIFICALLY NOTED FUSED AND NEMA I
ENCLOSURES UNLESS NOTED OTHERWISE. PROVIDE NEMA 3R ENCLOSURES IN ALL EXTERIOR OR
DAMP LOCATIONS AND NEMA 4 ENCLOSURES IN ALL WET LOCATIONS STARTING SHALL HAVE
OVERLOAD PROTECTION IN EACH PHASE 1,L-OR MOTORS 1 f3WP OR
4. L.ACH .>A/ i-7 .ii'11(.i -1 .i1'.. _ •i „. .,�r. I i ,r >'t•.., r':rt irr; l ilti`l!! tit
THE PAIVLL AND
INDOORS SHE §LL HL L /,'&L-.LL'D W11H LAMINAIL Pfd S U r.' atr�;rilvf LAllr. L WIN LLA(_'K LL.IlERS
ON WHITE BACKGROUND. LETTER HEIGHT IS 1/8 SA1 =LlY SWITCHES MOUNTED OUTDOORS SHALL
BE LABELED WITH ENGRAVED BAKELITE WITH WHITE LETTERS ON BLACK BACKGROUND. LETTER
HEIGHT IS 114"
PANEL BOARD
1. BEFORE ORDERING CIRCUIT BREAKER, COORDINATE ALL CIRCUIT BREAKER TRIPS WITH MECHANICAL
EQUIPMENT MANUFACTURER'S REQUIREMENTS, COORDINATE CONDUCTOR SIZE WITH ACTUAL MOTORS AND
OTHER MECHANICAL AND ARCHITECTURAL EQUIPMENT FURNISHED BEFORE INSTALLING CIRCUITRY.
2, PANEL BOARD BUS SHALL BE COPPER.
3. PANEL BOARD SHALL BE EQUAL TO SQUARE D, TYPE NEHB OR NQOD UNLESS INDICATED OTHERWISE.
4. ALL PANELBORDS SHALL BE EQUIPPED WITH COMMON KEYED LOCKS. PROVIDE A MINIMUM OF TWO
KEYS PER PANEL. PANEL BOARDS SHALL BE COMPETE WITH COVERS AND TRIMS AND SHALL CONTAIN
GROUND BUS.
5. IN PANLEBOARDS, "EQUIPPED SPACE" OR "SPACE" IS DEFINED TO INCLUDE ALL NECESSARY BUS, DEVICE
SUPPORTS AND CONNECTIONS FOR INSERTION OF A FURTHER DEVICE.
6. PROVIDE A TYPED CIRCUIT DIRECTORY FOR EACH PANEL BOARD INSTALLED UNIT THIS CONTRACT, IN
PLASTIC SLEEVE ATTACHED TO DOOR, WITH COPY OF DIRECTORY TO TENANT
7 PANEL BOARD CIRCUITING SHALL MATCH THE DRAWINGS. CIRCUITING CHANGES MUST BE APPROVED BY THE
ENGINEER.
8. CIRCUIT BREAKERS: MOLDED CASE CIRCUIT BREAKER: FRAME SIZE TRIP RATING NUMBER OR POLES
AND AUXILIARY DEVICES A INDICATED; INTERRUPTING CAPACITY RATING TO MEET AVAILABLE FAULT
CURRENT. 10,000 SYMMETRICAL BUS AMPERES MINIMUM; WITH APPROPRIATE APPLICATION LISTING WHEN
USED FOR SWITCHING FLUORESCENT LIGHTING LOAD OR HEATING, AIR CONDITIONING, AND REFRIGERATION
EQUIPMENT.
FIRE ALARM SYSTEMS
1. FIRE ALARM SYSTEMS: EXTEND THE EXISTING FIRE ALARM SYSTEM TO INCORPORATE ALL CHANGES
RESULTING FROM THE NEW WORK. INCLUDE ALL WIRING, RACEWAYS, PULL BOXES, TERMINAL
CABINETS, MOUNTING BOXES AND ALL MISCELLANEOUS ITEMS REQUIRED FOR A COMPLETE
OPERATION.
LIGHTING FIXTURES
1. REFER TO ARCHITECTURAL DRAWINGS FOR FIXTURE TYPES, QUANTITIES AND LOCATIONS. SEE
ENGINEERING PLANS FOR CIRCUITING.
2. PROVIDE FINISHING FRAMES FOR ALL RECESSED LIGHTING FIXTURES. TYPE TO BE COMPATIBLE
WITH CEILING, COORDINATE ALL FIXTURE TYPES WITH CEILING SYSTEM BEFORE ORDERING FIXTURE
PROVIDE ALL MOUNTING ATTACHMENT'S FOR A COMPLETE INSTALLATION
3. PROVIDE A COMPLETE AND OPERABLE LIGHTING SYSTEM, WHICH SHALL INCLUDE IN PART
FLORESCENT LIGHTING FIXTURES, BALLAST, LAMPS, LENSES, SUPPORTS, CANOPIES, FRAMES
HARDWARE AND ANY OTHER NECESSARY APPURTENANCES AS MAY BE REQUIRED.
4. PROVIDE ALL NECESSARY ACCESSORY FITTINGS, HANGERS, CLAMPS, BRACKETS, YOKES, PLASTER
FLANGES AND MISCELLANEOUS DEVICES AS REQUIRED FOR A COMPLETE INSTALLATION
5, PROVIDE LAMPS FOR EACH TYPE OF LIGHTING FIXTURE IN ACCORDANCE WITH THE FIXTURE
MANUFACTURERS LAMP REQUIREMENTS AND RECOMMENDATIONS, UNLESS INDICATED OTHERWISE.
ALL TRACK AND ACCENT LAMPS TO BE INSTALLED AT FOR THE TYPE REQUIRED
6, FLORESCENT LIGHTING BALLAST SHALL BE HIGH POWER FACTOR TYPE. CLASS P, ENERGY
SAVING, CBM AND ETL CERTIFIED AND RATED FOR SYSTEM VOLTAGE AND FREQUENCY WITH THE
QUIETEST SOUND LEVEL RATING AVAILABLE FOR THE TYPE REQUIRED,
7. COLOR OF LIGHTING FIXTURES SHALL BE AS SELECTED BY THE ARCHITECT.
8. OUTLET BOXES SERVING LIGHTING FIXTURES SHALL BE LABELED ON THE COVER PLATE TO SHOW
THE PANEL AND CIRCUIT BREAKER(S) SUPPLYING THE FIXTURE(S). OUTLET BOXES LOCATED
ABOVE SUSPENDED CEILINGS. IN MECHANICAL OR ELECTRICAL ROOMS OR OTHER SPACES NOT
EXPOSED TO GENERAL VIEW MAY BE MARKED WITH INDELIBLE MARKING PEN. OUTLET BOXES
EXPOSED TO GENERAL VIEW SHALL BE LABELED AS SPECIFIED FOR RECEPTACLES.
EXECUTION
A. PROVIDE ALL WORK, EQUIPMENT AND MATERIALS INDICATED
B. INSTALL SUPPORTING DEVICES TO FASTEN ELECTRICAL COMPONENTS SECURELY AND PERMANENTLY
IN ACCORDANCE WITH NEC REQUIREMENTS AND ANY ADDITIONAL LOCAL CODES.
C. ELECTRICAL IDENTIFICATION
1. PROVIDE COLOR CODING FOR FEEDERS AND BRANCH CIRCUIT CONDUCTORS AS FOLLOWS
208 120 VOLTS PHASE 4801277 VOLTS
BLACK A BROWN
RED B ORANGE
BLUE C YELLOW
WHITE NEUTRAL GRAY
GREEN GROUND GREEN
2. APPLY CIRCUIT DESIGNATION LABELS OF ENGRAVED PLASTIC LAMINATED FOR
DISCONNECT SWITCHES, BREAKERS, PUSHBUTTONS, PLOT LIGHTS, AND SIMILAR ITEMS FOR
POWER DISTRIBUTION AND CONTROL COMPONENTS ABOVE.
D. GROUNDING
1, GROUNDING ELECTRICAL SYSTEMS AND EQUIPMENT IN ACCORDANCE WITH NEC EXCEPT WHERE
GROUNDING IN EXCESS OF NEC REQUIREMENTS IS INDICATED.
2. ALL CIRCUITS SHALL CONTAIN AN INSULATED GROUNDING CONDUCTOR. THIS SHALL APPLY
WHETHER INDICATED ON THE DRAWINGS OR NOT.
J. SEPARATELY DERIVED SYSTEMS REQUIRED BY NEC TO BE GROUNDED SHALL BE GROUNDED
AS APPROVED BY THE AUTHORITY HAVING JURISDICTION.
E. LIGHTING
1. COORDINATE LIGHTING FIXTURES WITH MECHANICAL EQUIPMENT AND ARCHITECTURAL CEILING
PLAN GRID LAYOUT INDICATED IS APPROXIMATE. FINAL LOCATION OF LIGHTING FIXTURES
SHALL BE AS DIRECTED IN THE FIELD BY THE ARCHITECT,
12 -1 -10
I.L.A. project # 1070.00
I. Leon & Assoc., Inc.
Consulting Engineers
15521 SW 149th. COURT
MIAMI, FLORIDA 33187
CA # 6577
ileanandassoc ®bellsouth.net
phone # 305 232 0031
seal:
Ismael Leon, P.E., # 40168
8000 NW 7 Street, Suite 101
Miami, Florida 33126
T. 3 0 5- 7 4 0 - 0 1 5 0
F. 305 - 740 -01 58
e -mail: tag- db!0tagdbi.com
corporate license AAC 002228
Copyright Notice: These drawings, designs and
ideas are the property of The Architects Group, Inc.
and are protected under the copyright laws of
Florida. No part thereof shall be copied, or used in
connection with any work other than for the specific
project for which they have been prepared without
written consent of The Architects Group, Inc.
v-
N
W
W
z
OL
0
00
W
"W�
G2
V
<_N
z
z
i_I
J Lil
L
ry
J ..J
ii
W
W
1-I LLI
""
z
z
°G
cv r
W
LLl Ld
-y o
0
DATE: 11/17/10
JOB NO: 101 ,3-01
DRAWN: it
CHECKED: r'p
REVISIONS:
Pedro P. Ramos, A.I.A.
- FL. Lic. 10590
SI -IFLT TITLE:
ELECRICAL
NOTES
`E)HLET NLIMFEI;" „a
E -3
�t
n
W
ry
z
D
OL
0
00
LL
V
Z
z_
cn
W
0
LW
L.L
ry N
0
�F>
�
N
7
L
LL
zz=
L
v,
W
s
�-
DATE: 11/17/10
JOB NO: 101 ,3-01
DRAWN: it
CHECKED: r'p
REVISIONS:
Pedro P. Ramos, A.I.A.
- FL. Lic. 10590
SI -IFLT TITLE:
ELECRICAL
NOTES
`E)HLET NLIMFEI;" „a
E -3
�t
n