13-1330-007ICI I
INTAKE LOUVER EXHAUST LOUVER
24 "X12" 24 °X12"
SECOND FLOOR CONCRETE W X H SF -1 EF -1 W X H
A ,5 4... 'd
a . ,
Q
s
f
HOOD SCHEDULE
HOOD #
MFG.
MODEL #
LENGTH
TYPE
EXHAUST COLLAR
MATERIAL
WGT
SIZE
S.P.
CFM
1
#1
5' -6"
12"
20" x 8"
1/4"
440
1
HOOD
DEPOT
VHH- 0664224112
I
5' -6"
I
TYPE II
I HOOD
14" x 14"
1/4-
550
430 S/S
250 LBS
MUA PLENUM SCHEDULE
PLENUM #
HOOD #
LENGTH
WIDTH
SUPPLY COLLAR
AREA of MUA
PERF
VELOCITY THRU
MUA PERF
WGT
SIZE
S.P.
CFM
1
#1
5' -6"
12"
20" x 8"
1/4"
440
5.5 SQFT
80 FPM
40 LBS
FAN SCHEDULE
HOOD #
FANS
MFG.
MODEL #
CFM
S. P.
HP
VOLTAGE
RPM
AMPS
WGT
# 1
EF -1
' JENCO
TD -315
550
1 °'
335W
115V/10-
1550
2.8
35 LBS
#1
SF -1
JENCO
TD -315
440
1"
335W
115V/1
1450
2.8
35 LBS
HVAC DESIGN CRITERIA
YES
NO
FIRE DAMPER
550
X
SMOKE DAMPER
X
FIRE RATED CEILING
TOTAL AIR VOLUME -
X
DUCT SMOKE DETECTOR
X
FIRE RATED ENCLOSURE
X
AIR , BALANCE SCHEDULE
EX CFM
SUPPLY CFM
AIR EXHAUSTED FROM HOODS
550
AIR SUPPLIED TO HOODS
440
TOTAL AIR VOLUME -
550
440
3/8 "0 ALL THREADED ROD FASTENED TO
GENERAL NOTES:
TOP CORE OF EXISTING BAR JOIST W/ BEAM
CLAMPS AND TO 1 5/8" UNISTRUT OR 1. HEAT HOOD:
2 "X2 "Xi" ANGLE IRON W/ 3/8 "0 MATERIAL: 18 GAUGE STAINLESS STEEL CONSTRUCTION
BOLTS , WASHERS AND NUTS. ALL CONTINUOUS EXTERNAL LIQUID TIGHT WELDS,
POLISHED. ALL IN COMPLIANCE WITH NFPA #96 AND
LOCAL BUILDING CODES.
Q BAR JOIST
2. HEAT HOOD EXHAUST DUCTS:
MATERIAL: 24 GALVANIZED SHEET METAL. GAUGES,
3 /8" ALL — THREAD ROD TO HANGING AND REINFORCING PER SMACNA STANDARDS.
12 GA. HANGER WITH WASHERS
c� AND NUTS, TOP & BOTTOM. 3. HEAT HOOD SUPPLY DUCTS:
b TOP OF HOOD MATERIAL: GALVANIZED SHEET METAL GAUGES, HANGING
AND REINFORCING PER SMACNA STANDARDS.
4. HEAT HOOD EXHAUST FAN:
12 GA. HANGER AS SPECIFIED ON DRAWINGS AND CONFORMING TO
WELDED TO TOP A NATIONAL TESTING AUTHORITY FOR PERFORMANCE
OF HOOD CERTIFICATION AND UL LISTED SUBJECT BULLETIN 705.
5. HEAT HOOD SUPPLY FAN:
HOOD HANGING DETAIL AS SPECIFIED ON DRAWINGS AND CONFORMING TO
A NATIONAL TESTING AUTHORITY FOR PERFORMANCE
N.T.S. CERTIFICATION. TO BE LOCATED A MINIMUM OF
10' -0" FROM ANY EXHAUST FAN, PLUMBING VENT
AND FLUE STACKS.
„ 6. ELECTRICAL: c ENS •
1 4 ELECTRICAL HOOK UP AND EQUIPMENT SUCH AS':•
�x MOTOR STARTERS, SWITCHES, CONTROLS AND ; Na. 72500
7 COMPONENTS OTHER THAN WHAT IS SPECIFICALLY .-o• '�` '�
„ MENTIONED ON DRAWINGS IS BY OTHERS. O.T;• STATE ()P•�;
7. COMPLIANCE: '^'"� '�'''�.`,r, /ONAI.•
° '� „ SYSTEM TO BE MANUFACTURED AND INSTALLED IN \0-;L543 ln111111u��``
O 12" ACCORDANCE WITH NFPA #96, LOCAL FIRE
° PREVENTION BUREAU MECH. AND HEALTH DEPT. =-)
I e STANDARDS 7(3,-v Q 710 SOUTH POWERLINE ROAD CHIEF ENGINEER
13