11-864-01091
C/U AT SECOUND FLOOR PARKING GARAGE PLAN
SCALE: 1/4" = V -0"
FIRE ALARM SPECIFICATIONS
1.– Contractor shall supply to building Department as part of Fire
Alarm Permit, Updated shop fire alarm shop drawings reflecting
added devices Jc Battery Calculations. The contractor shall be
responsible to supply shop drawings Signed and sealed by a
Professional Engineer if requested by Fire Plan reviewer.
2.– All Fire Alarm System components shall be new and reflect UL
listing for fire service use.
3.– The installation of the Fire Alarm System shall also comply with
the NFPA -70 National Electrical code (NEC) 2008 edition and the
Florida Accessibility Code For Building Construction 94 edition.
The installation shall also comply with NFPA -101 and NFPA -72.
4.– The Fire Alarm System shall consist of an Automatic Fire Detec-
tion and Notification System.
5.– All Fire Alarm equipment for this project shall be rated "POWER
LIMITED "
6.– The Fire Alarm Control Panel shall have standby battery backup
as per NFPA 72, providing battery power capacity for entire
system to operate for 24 hours in normal mode and
then, at the end of the period, for 5 minutes in the emergency
mode.
7.– Cable size shall comply with article 760 -71 and the cable insta-
llation shall comply with the separation and use of conductors
and cables as specified in articles 760 -54 and 760 -61 of the
National Electrical Code.
8.– Building wiring shall specifically conform with the National Electri-
cal Code article 760 part C for Power – Limited Fire Protection
Signal Circuits with emphasis on article 760 -52(b) on Power Li-
mited Wiring Methods and Materials.
S.– MINIMUM CABLE SIZE:
A. –# 16 AWG Copper (2 –# 16 FPLP) for : Smoke Detectors, Duct
Detectors and Pull Stations.
B. –# 14 AWG Copper (2--# 14 FPLP) for: Strobes and Horn no-
tification devices.
10.– All new wiring installed in ducts, plenums and other spaces used
for environmental air shall be type FPLP, as per NEC ( National
Electrical Code) article 760 -61.
11.– Alarm notification devices shall be audible and /or visual and shall
be done via Horn and Strobe devices. Strobes shall be clear xe-
non type, with intensity of 75 candelas as per Article 4.28 (1)
through (5) of the ADA guidelines of July 26, 1992 and as per
article 4.28.2 is 4.28.3 of the Florida Accessibility Code for Buil-
ding Construction.
12.– Strobe and Horn devices shall be placed 80" (6 * -8 ") above the
highest floor level within the space or 6- below the ceiling whichever
is lower as per ADA guidelines and article 4.28 (6) of the Florida
Accessibility Cade for Building Construction.
13.– The distance from any place to a notification device shall not ex-
ceed 50' as per article 4.28 (7) and (8) of the Florida Accesibi-
lity Code for Building Construction.
14.– Pull Stations shall be installed at 48" AFF as per article 4.2.5 of
the Florida Accessibility Code for Building Construction.
15.– The location of the audible devices has been designed as to be
effectively heard 15 dB above ambient noise level obtained under
normal condition of occupancy as NFPA 72.
16.– Activation of the Duct detector in the air handling unit (AHU) shall
cause the automatic shut –down of that AHU.
17.– This design was based on calculations over a set of plans pro-
vided to the design architect. If the post installation on –site tests
conducted by the authority having jurisdiction determines that, be-
cause unforeseeable conditions or changes in field parameters, the
audible alarm level falls below the required level in specific areas,
specific areas, the number of audible strobe /horns shall be in-
creased to comply with the requirements and to the satisfaction
of the authority having jurisdiction.
BLITSTEIN DESIGN
da ASSOCIATES
AR0007570
ARCHITECTURE - INTERIOR DESIGN
285 Sevilla Avenue Coral Gables, Fl 33134
305 - 444 -4433 fax 305 - 444.0181
EMAIL- bdamiamiebellsouth,net
XISTING KITCHEN
:XISTING TO REMAIN.
10 WORK
N EXIT CORRIDOR
TO EXITING FA PANEL —@
TO EXITING FA PANEL
TVF"—VV--,
PARTIAL FIRE ALARM RISER
NTS
fW_ LAMP YDTES=
1- TiUL01NG FULL SPRINKLER CONNECTED EXISTING TO FIRE ALARM PANEL.
2- All HANDLERS UNITS HAVE DUCT SMOKE DETECTORS IN SUPPLY SECTION
CONN= TO EXISTING FIRE ALARM PANEL.
3- E)STING FIRE ALARM PANEL IN KITCHEN MACK AREA,
FW ALAM DEVM
a FIRE ALARM FULL STATION (42" A F.F.)
MATCH WITH EXISTING
FIRE ALARM HORN WITH STROBE LIGHT (SO A F.F.)
MATCH WITH EXISTING
@ DUCT SMOKE DETECTOR
Proposed Interior Build -out for:
Everything i Entertainment
Space #6 - South Miami Municipal ParkingFacility - 5829 S.W. 73rd Street, South Miami, Florida 33143
SCOPE OF WORK
1— THE SCOPE OF WORK IS A DINNING SECTION REMODELING OF EXISTING RESTAURANT.
2— POWER AND LIGHTING EXISTING KITCHEN, BAR AND BATHROOMS AREAS ARE EXISTING TO REMAIN.
3— AHU UNITS 1, 2 AND 3 ARE EXISTING TO PIE RELOCATED AND AHU #6 IS NEW. C/U 1,2 AND 3
AREA EXISTING TO REMAIN IN SAME LOCATION, ONLY NEW C/U #6 IS NEW INSTALLATION IN FOUR
FLOOR PARKING GARAGE.
date 06 /27/14
revision
" , t 3J r
�IX i .'`.', rJi i l and ,� 1
be slala n.` (A fo- P 8'-011 Z ", r ,V ^l tD N I"In'
Approved for 'z. 2ding Permit orilyt
Date ?,/ -/ 5� BY— �� w
sheet title
POWER PLAN
project number
drawn by A. F.
• Y• Y • W W
EXISTING CHAIN LINK
•
• V i V i
• i•
FENCE TO REMAIN
30-10- 30
V y
�+ U
Y
WP
go. V V
Y
V W
r--.._.._......------
NEW EXISTING C/U
• W
Y i W
W
I
C /U #6 / r \1 MDP2 -11
u
Wrrrr
• y y V
1
•
V
V U
l
Y
Y
4r•V
WP
I— ,- - - - - --
- - -- -- r- - - -- -�
B -32 I EXISTING C/U I EXISTING C/U
I
L..- — — — — — —I L- - - - - -�
EXIST. IN ` /LI I EXISTING /U
I I
zm
EXIST \ /U I EXISTING C/U
I
-- - - ---I L------ .._.--
91
C/U AT SECOUND FLOOR PARKING GARAGE PLAN
SCALE: 1/4" = V -0"
FIRE ALARM SPECIFICATIONS
1.– Contractor shall supply to building Department as part of Fire
Alarm Permit, Updated shop fire alarm shop drawings reflecting
added devices Jc Battery Calculations. The contractor shall be
responsible to supply shop drawings Signed and sealed by a
Professional Engineer if requested by Fire Plan reviewer.
2.– All Fire Alarm System components shall be new and reflect UL
listing for fire service use.
3.– The installation of the Fire Alarm System shall also comply with
the NFPA -70 National Electrical code (NEC) 2008 edition and the
Florida Accessibility Code For Building Construction 94 edition.
The installation shall also comply with NFPA -101 and NFPA -72.
4.– The Fire Alarm System shall consist of an Automatic Fire Detec-
tion and Notification System.
5.– All Fire Alarm equipment for this project shall be rated "POWER
LIMITED "
6.– The Fire Alarm Control Panel shall have standby battery backup
as per NFPA 72, providing battery power capacity for entire
system to operate for 24 hours in normal mode and
then, at the end of the period, for 5 minutes in the emergency
mode.
7.– Cable size shall comply with article 760 -71 and the cable insta-
llation shall comply with the separation and use of conductors
and cables as specified in articles 760 -54 and 760 -61 of the
National Electrical Code.
8.– Building wiring shall specifically conform with the National Electri-
cal Code article 760 part C for Power – Limited Fire Protection
Signal Circuits with emphasis on article 760 -52(b) on Power Li-
mited Wiring Methods and Materials.
S.– MINIMUM CABLE SIZE:
A. –# 16 AWG Copper (2 –# 16 FPLP) for : Smoke Detectors, Duct
Detectors and Pull Stations.
B. –# 14 AWG Copper (2--# 14 FPLP) for: Strobes and Horn no-
tification devices.
10.– All new wiring installed in ducts, plenums and other spaces used
for environmental air shall be type FPLP, as per NEC ( National
Electrical Code) article 760 -61.
11.– Alarm notification devices shall be audible and /or visual and shall
be done via Horn and Strobe devices. Strobes shall be clear xe-
non type, with intensity of 75 candelas as per Article 4.28 (1)
through (5) of the ADA guidelines of July 26, 1992 and as per
article 4.28.2 is 4.28.3 of the Florida Accessibility Code for Buil-
ding Construction.
12.– Strobe and Horn devices shall be placed 80" (6 * -8 ") above the
highest floor level within the space or 6- below the ceiling whichever
is lower as per ADA guidelines and article 4.28 (6) of the Florida
Accessibility Cade for Building Construction.
13.– The distance from any place to a notification device shall not ex-
ceed 50' as per article 4.28 (7) and (8) of the Florida Accesibi-
lity Code for Building Construction.
14.– Pull Stations shall be installed at 48" AFF as per article 4.2.5 of
the Florida Accessibility Code for Building Construction.
15.– The location of the audible devices has been designed as to be
effectively heard 15 dB above ambient noise level obtained under
normal condition of occupancy as NFPA 72.
16.– Activation of the Duct detector in the air handling unit (AHU) shall
cause the automatic shut –down of that AHU.
17.– This design was based on calculations over a set of plans pro-
vided to the design architect. If the post installation on –site tests
conducted by the authority having jurisdiction determines that, be-
cause unforeseeable conditions or changes in field parameters, the
audible alarm level falls below the required level in specific areas,
specific areas, the number of audible strobe /horns shall be in-
creased to comply with the requirements and to the satisfaction
of the authority having jurisdiction.
BLITSTEIN DESIGN
da ASSOCIATES
AR0007570
ARCHITECTURE - INTERIOR DESIGN
285 Sevilla Avenue Coral Gables, Fl 33134
305 - 444 -4433 fax 305 - 444.0181
EMAIL- bdamiamiebellsouth,net
XISTING KITCHEN
:XISTING TO REMAIN.
10 WORK
N EXIT CORRIDOR
TO EXITING FA PANEL —@
TO EXITING FA PANEL
TVF"—VV--,
PARTIAL FIRE ALARM RISER
NTS
fW_ LAMP YDTES=
1- TiUL01NG FULL SPRINKLER CONNECTED EXISTING TO FIRE ALARM PANEL.
2- All HANDLERS UNITS HAVE DUCT SMOKE DETECTORS IN SUPPLY SECTION
CONN= TO EXISTING FIRE ALARM PANEL.
3- E)STING FIRE ALARM PANEL IN KITCHEN MACK AREA,
FW ALAM DEVM
a FIRE ALARM FULL STATION (42" A F.F.)
MATCH WITH EXISTING
FIRE ALARM HORN WITH STROBE LIGHT (SO A F.F.)
MATCH WITH EXISTING
@ DUCT SMOKE DETECTOR
Proposed Interior Build -out for:
Everything i Entertainment
Space #6 - South Miami Municipal ParkingFacility - 5829 S.W. 73rd Street, South Miami, Florida 33143
SCOPE OF WORK
1— THE SCOPE OF WORK IS A DINNING SECTION REMODELING OF EXISTING RESTAURANT.
2— POWER AND LIGHTING EXISTING KITCHEN, BAR AND BATHROOMS AREAS ARE EXISTING TO REMAIN.
3— AHU UNITS 1, 2 AND 3 ARE EXISTING TO PIE RELOCATED AND AHU #6 IS NEW. C/U 1,2 AND 3
AREA EXISTING TO REMAIN IN SAME LOCATION, ONLY NEW C/U #6 IS NEW INSTALLATION IN FOUR
FLOOR PARKING GARAGE.
date 06 /27/14
revision
" , t 3J r
�IX i .'`.', rJi i l and ,� 1
be slala n.` (A fo- P 8'-011 Z ", r ,V ^l tD N I"In'
Approved for 'z. 2ding Permit orilyt
Date ?,/ -/ 5� BY— �� w
sheet title
POWER PLAN
project number
drawn by A. F.
• Y• Y • W W
•
•
• V i V i
• i•
„ y •
V y
�+ U
Y
• •
go. V V
Y
V W
V
• W
Y i W
W
W
u
Wrrrr
• y y V
Y
•
V
V U
•GV VWV •
Y
Y
4r•V
• r •
Y W V 4 G V Y f
V v y u u �• •u u
V W W V y V V V 4
• W • V V V• H
4 Y •• (Y I ♦•• Y N• i
,y V IJ • W _ •
• J U U
M J • y r
W � V V- V • I U r U • y• Y• •
Ij
II
I I
I
N I I
F - -_J
N
F
I
I
I
I
I
I
I
I
I
I
I - - -- J
I
I
I
I
I I
I
(
I
1 I
I
I
I
I
I
I
I
I
I
I
I�
71
I
I
and • i
i �
�
F�
may` y
r1 D�. �. i '. •i 6'
W
u)
GUIROLA & ASSOCIATES P.A.
CONSULTING ENGINEERS
P.E. No 57468
David Guirola
Electrical Engineer
1150 NW 72nd AVE, 5451
MIAMI, FLORIDA 33126
P,H: (305) 513 -SCC5
CA 00006112 EMAIL: GUIRO 5eAOL.COM
Scale: AS SHOWN
sheet number
I llll�
E -1
E