12-1093-012GENERAL ELECTRICAL NOTES
1 . ALL WORK SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE,
FLORIDA BUILDING CODE AND OTHER APPLICABLE CODES AND STANDARDS.
2 . THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS AND
BOXES REQUIRED TO MAKE A COMPLETE NEAT INSTALLATION IN ACCORDANCE WITH
N.E.C.
3 . APPROVAL SHALL BE OBTAINED FROM AN STRUCTURAL ENGINEER PRIOR TO CUTTING
OR DRILLING ANY STRUCTURAL SUPPORT MEMBER.
4 . INSTALL POWER AND CONTROL WIRING AND REQUIRED CONTROL COMPONENTS FOR
AIR CONDITIONING SYSTEMS AS SHOWN/NOTED ON THESE DRAWINGS AND PER OTHER
APPLICABLE DRAWINGS / INSTRUCTIONS. SEE AIR CONDITIONING DRAWING.
5 . WIRE SIZE SHALL BE f 12 THHN / THWN UNLESS OTHERWISE NOTED ON PLANS.
CONDUCTOR # 6 OR LARGER SHALL BE THWN.
6 . ALL CONDUCTOR SHALL BE COPPER UNLESS OTHERWISE NOTED.
7 . ALL CONDUCTORS SHALL BE RUN IN CONDUIT (METALLIC TYPE). MC CABLE IS
PERMITTED AS AN OPTION. IF PVC SCHEDULE 40 IS USED FOR UNDERGROUND
FEEDERS ONLY, AN EQUIPMENT GROUND CONDUCTOR SIZED IN ACCORDANCE WITH
N.E.C. 250.122 MUST BE INSTALLED AND CONDUIT SIZE INCREASED AS REQUIRED.
8 . ALL MATERIALS SHALL BE U.L. APPROVED.
9 . ALL NON POWER RELATED WIRING IN CEILING AIR CONDITIONING PLENUM RUNNING
WITHOUT CONDUIT SHALL BE TEFLON COATED CLASSIFIED FOR USE IN PLENUMS.
EXTENDED AS REQUIRED.
11. FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE NOTED.
12. A/C EQUIPMENT WIRING, BREAKER AND FUSE SIZES ARE BASED ON A/C EQUIPMENT
SPECIFIED ON CONTRACT DRAWING. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL
WIRING, BREAKER AND FUSES SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE
REQUIREMENTS IF DIFFERENT FROM THAT SPECIFIED ON DRAWINGS, AS WELL AS ANY
FEEDER CHANGES BEING AFFECTED BY THIS CHANGE CONTRACTOR SHALL MAKE ABOVE
MENTIONED CHANGES AT NO EXTRA COST.
13. CONTRAC s OR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN OTHER TO
FURNISH AND INSTALL ALL CONTROL WIRING AND RACEWAYS, ALL POWER CONTROL
CIRCUIT WIRING AND RACEWAY AS SHOWN ON THE AIR CONDITIONING DRAWING OR
SPECIFICATIONS. IF AIR CONDITIONING IF DRAWING REFER TO MANUFACTURERS
WIRING DIAGRAMS, THE CONTRACTOR SHALL VERIFY WITH SAID MANUFACTURER ALL
REQUIREMENTS AND INCLUDE ALL RELATED WORK IN HIS CONTRACT.
14. ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH THE CEILING
SYSTEM MANUFACTURER RECOMMENDATIONS AND LOCAL CODE REQUIREMENTS.
15. RISERS ARE DIAGRAMMATIC ONLY. THEY DO NOT SHOW EVERY BEND REQUIRED FOR
THE INSTALLATION.
16 . THIS DRAWING IS A GUIDE FOR THE ELECTRICAL INSTALLATION OF ELECTRICAL SERVICE.
THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM.
17. ALL CABLES SHALL BE RUN WITHOUT SPLICES EXCEPT OTHERWISE INDICATED.
18. ALL PULL AND JUNCTION BOXES SHALL BE ACCESSIBLE AT ALL TIMES.
-• r •r • • • r r r
20 . ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER.
21. ALL ROUGH IN DIMENSION ARE TO CENTER LINE OF DEVICE UNLESS OTHERWISE NOTED.
22. ALL EXTERIOR SURFACE MOUNTED LUMINARIES, POSTS, POST TOPS, POLES AND AREA
LIGHTING. LUMINARIES TO HAVE FINISH COLOR TO MATCH ARCHITECTURAL WINDOW
FRAME COLOR & / OR EXISTING NEIGHBORHOOD EXTERIOR LIGHT FIXTURE COLOR
UNLESS OTHERWISE SPECIFICALLY NOTED.
23 . ALL PULL BOXES, HAND HOLES AND MAN HOLES TO HAVE COVER PLATE BOLTED TO
FRAME AND BONDED TO THE EQUIPMENT GROUND SYSTEM.
24 . ALL CONDUCTOR SPLICES IN EXTERIOR LOCATED PULL/PULL BOXES EXPOSED TO THE
WEATHER TO BE WEATHER SEALED BY USING AN APPROVED METHOD SUCH AS 3M
SCOTCHLOCK CONNECTOR EPDXY SEALING.
25 . CONTRACTOR IS ALLOWED TO REARRANGE THE DISTRIBUTION OF THE ELECTRICAL LOADS
CONNECTED TO THE BRANCH CIRCUITS IN FIELD, AS LONG AS LOAD BALANCE & INDEPENDENCE
CIRCUITS LOADING IS IN COMPLIANCE WITH NEC.
LIGHTING LEGEND
® RUSTIC PENDANT 4 LIGHTS (OWNER /ARCH. SELECTED) 45W MAX EA.
® RECESSED DOWNLIGHT — LV LED (OWNER /ARCH. SELECTED) 45W MAX EA.
I ® I RECESSED DOWNLIGHT — LV LED (OWNER /ARCH. SELECTED) 45W MAX EA. I
® RECESSED DOWNLIGHT — LV LED (OWNER /ARCH. SELECTED) 45W MAX EA.
�" DIRECTIONAL HALOGEN (OWNER /ARCH. SELECTED) 45W MAX EA.
E PENDANT (OWNER /ARCH SELECTED) 45W MAX EA.
*GC TO SUBMIT LIGHTING FIXTURE PACKAGE FOR OWNER AND ARCHITECT'S
APPROVAL.
LIGHTING FLOOR PLAN-
SCALE 1 /4" -1' -0"
-MAR 0 4 2013 �-
CRESPO CONSULTING
ENGINEERING INC.
7724 W 29 Ln #102
HIALEAH, Florida, 33018
Phone (786) 413 -6415 Fax (305) 824 -9597
CA# 27711 CCE# 07087
Elias P. Crespo P.E. LICENCE : 59295
Fri
L�J
N
T I T L E OF S H E E T
I S S U E j kill];
DATE
P R O J E CT NO.
DEC. 1 2011
1116
S E A L
SHEET NUMBER
-. .:
Eml
"rr owl
B," $ STATE 1�
•• c<t
1 OF 3 SHEET
•
AIA
ADOLFO LOPEZ.
LIC#0016093
a
•
•
N
T I T L E OF S H E E T
I S S U E j kill];
DATE
P R O J E CT NO.
DEC. 1 2011
1116
S E A L
SHEET NUMBER
-. .:
Eml
"rr owl
B," $ STATE 1�
•• c<t
1 OF 3 SHEET
•
AIA
ADOLFO LOPEZ.
LIC#0016093