14-235-0081.00 - GENERAL PROVISIONS 1.1 PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT FOR A COMPLETE AND PROPERLY OPERATING PLUMBING SYSTEM. i 1.2 CODES AND STANDARDS: ALL PLUMBING WORK SHALL BE IN STRICT COMPLIANCE WITH THE STANDARD PLUMBING CODE 2010 EDITION AND ALL LOCAL CODES HAVING JURISDICTION. 1.3 ALL PLUMBING WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER. 1.4 CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS AND FEES, ETC., REQUIRED FOR THE EXECUTION OF THIS WORK. 1.5 CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER TRADES BEFORE FABRICATION OR INSTALLATION. OFFSETS AND /OR TRANSITIONS REQUIRED SHALL BE PROVIDED WITHOUT ADDITIONAL COST. CONTRACTOR SHALL COORDINATE AND INSTALL HIS WORK IN A TIMELY MANNER TO PREVENT DELAYS IN THE CONSTRUCTION. 1.6 CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR OR REPLACE DAMAGED EQUIPMENT AND /OR MATERIAL 1.7 PROVIDE ALL MATERIALS REQUIRED TO PROPERLY SUPPORT ALL PIPING AND EQUIPMENT. PIPE HANGERS SHALL BE ADJUSTABLE TYPE AND BE SPACED IN ACCORDANCE WITH THE STANDARD PLUMBING CODE. PROVIDED PLASTIC COATED RING ON HANGERS FOR COPPER PIPING TO PROVIDE DIELECTRIC ISOLATION. 1.8 PROVIDE DIELECTRIC UNIONS OR FLANGES BETWEEN COPPER AND STEEL PIPING AND BETWEEN BRASSWARE AND STEEL DO NOT USE STEEL AND COPPER PIPING IN THE SAME SYSTEM WITHOUT SUCH ISOLATION. 1.9 PROVIDE REDUCING FITTINGS (REDUCING BUSHINGS SHALL NOT BE USED) WHERE CHANGES IN PIPE SIZES OCCUR. 1.10 THIS CONTRACTOR SHALL SUPPLY AND INSTALL ALL SERVICES THROUGHOUT THE BUILDING AND MAKE CONNECTION TO SITE UTILITIES APPROXIMATELY 5' -0" OUTSIDE THE BUILDING. CONTRACTOR SHALL SUPPLY AND INSTALL FIXTURES, FITTINGS, VALUING AND TRIM AND MAKE READY FOR USE ALL FIXTURES, EQUIPMENT, ETC. 1.11 SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS. 2.00 - BASIC MATERIALS AND METHODS 2.1 ABOVEGROUND WATER PIPE AND FITTINGS - TYPE "L" COPPER. 2.2 PROVIDE UNIONS OR FLANGES IN ALL DOMESTIC WATER SERVICE LINES AT EACH PIECE OF EQUIPMENT, SPECIALTY VALVES OR AT OTHER LOCATIONS REQUIRED FOR READY DISCONNECT. 2.3 WATER HAMMER ARRESTORS SHALL BE INSTALLED AT THE LOCATIONS ON THE PLANS AND IN ACCORDANCE WITH PDI STANDARD WH -201. PRODUCTS SHALL BE EQUAL TO THOSE MANUFACTURED BY PRECISION PLUMBING PRODUCTS OR SIOUX CHIEF. 2.4 VALVES: PROVIDE VALVES TO ISOLATE EACH RISER, BRANCH LINE AND PIECE OF EQUIPMENT. 2.5 PROVIDE PRESSURE REDUCING VALVE AND AIR GAP CONNECTION AT DISHWASHER AS j REQUIRED BY CODE AND ACCORDING TO MANUFACTURER. 2.6 PROVIDE INUNE WATER FILTER AT COFFEE MAKER AND ICE MAKER TO REMOVE MATERIALS, TASTE AND ODOR - "EVERPURE OR "SYSTEMS IV". 2.7 ABOVEGROUND SANITARY, WASTE, SANITARY VENT AND STORM PIPING - PVC (DWV) SOLID WALL SHALL BE PERMITTED TO BE USED. PVC (DWV) SHALL NOT BE USED IN RETURN AIR PLENUMS. 2.8 BELOWGROUND SANITARY, WASTE AND VENT - PVC (DWV) SOLID WALL SHALL BE PERMITTED TO BE USED. PVC SHALL NOT BE USED FOR DRAINAGE IN HIGH TEMPERATURE DISCHARGE AREAS SUCH AS KITCHENS AND BOILER ROOMS. 2.9 INSTALL GRAVITY LINES SLOPED AT 1/8" PER FOOT FOR PIPE 3" AND LARGER AND 1/4" PER FOOT FOR PIPE SMALLER THAT 3 ". VERIFY INVERT ELEVATION WITH SITE PIPING PRIOR TO ANY PIPE BEING INSTALLED. 3.00 - PLUMBING FIXTURES AND TRIM 3.1 ALL PLUMBING FIXTURES SHALL BE "FIRST QUALITY" AS DEFINED AND SET FORTH IN COMMERCIAL STANDARD CS77 -28 AS PROMULGATED BY THE U.S. DEPARTMENT OF COMMERCE. 3.2 ALL FIXTURES ARE TO BE WHITE VITREOUS CHINA UNLESS OTHERWISE SPECIFICALLY NOTED. 3.3 FIXTURES AND FITTINGS PROPOSED SHALL BE FROM ONE MANUFACTURER AND OF SIMILAR CHARACTER IN ANY ROOM OR LOCATION. ESCUTCHEONS, HANDLES, ETC., ON THE DIFFERENT FIXTURES SHALL BE OF THE SAME DESIGN. 3.4 PROVIDE FIXTURE CARRIERS AS RECOMMENDED BY FIXTURE MANUFACTURER AND /OR CONSTRUCTION METHOD. 3.5 PROVIDE ACCESS PANELS TO ALL VALVES WITHIN CHASES OR ABOVE NON - ACCESSIBLE CEILINGS. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPES. 3.6 FLOOR DRAIN TRAP SEALS SHALL HAVE AN APPROVED AUTOMATIC PRIMING DEVICE DESIGNED FOR THAT PURPOSE. 3.7 ALL CONCEALED TRAPS, PRIMERS, VALVES, CLEANOUTS, ETC. LOCATED IN TILED AREAS SHALL BE PROVIDED WITH AN ACCESS PANEL 4.00 - INSULATION , 4.1 ABOVE GROUND HOT WATER - FIBERGLASS, 1" THICKNESS, ASJ JACKET, DOUBLE SEALING LAP JOINT, 0.24 K AT 757. INSULATION AND ADHESIVES INSTALLED IN RETURN AIR PLENUMS SHALL HAVE A MAXIMUM FLAME SPREAD RATING OF 25 AND A MAXIMUM SMOKE DEVELOPED RATING OF 50. 4.2 ABOVEGROUND CONDENSATE PIPING SHALL BE 1/2" FLEXIBLE UNICELLULAR POLYOLEFIN FOAM AND SHALL HAVE A MAXIMUM FLAME SPREAD RATING OF 25 AND A MAXIMUM SMOKE DEVELOPED RATING OF 50 - IMCOA "IMCOLOCK" 5.00 - VALVES AND COCKS 5.1 VALVES 2" AND SMALLER SHALL BE BALL VALVES, 150 PSI SWP, 400 PSI WOG STANDARD PORT BALL, BRONZE TRIM, CAST BRONZE BODY, CHROMIUM- PLATED BRASS BALL, BRONZE NON- BLOWOUT STEM, TEFLON SEAT, DOUBLE 0 -RING STEM SEALS, ZINC- COATED STEEL HANDLE WITH PLASTIC COATED HAND GRIP, 90 DEGREE OPERATION FROM FULL OPEN TO TIGHT SHUT -OFF - STOCKHAM S214- BR -T -T, STOCKHAM S216- BR -T -S OR EQUAL 5.2 CHECK VALVES, ROUGH BRASS, REGRINDING BRONZE DISC - STOCKHAM B -345; B -309 OR EQUAL 6.00 - STERILIZATION 6.1 DOMESTIC WATER PIPING SHALL BE THOROUGHLY FLUSHED OUT AND STERILIZED IN ACCORDANCE WITH THE STANDARD PLUMBING CODE. PLUMBING GENERAL. NOTES 1. READ THE SPECIFICATIONS. 2. UTILITIES AND SERVICES INDICATED ARE TAKEN FROM VARIOUS OLD AND NEW SURVEYS, AS -BUILT RECORDS AND FIELD INVESTIGATIONS. UNFORSEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE FIELD LOCATED EXACTLY AS SHOWN ON DRAWINGS. COOPERATION WITH OTHER TRADES IN ROUTING AND BURIAL DEPTHS, AS DETERMINED DURING CONSTRUCTION WILL BE NECESSARY. 3. FIELD VERIFY EXISTING INSTALLATIONS. MODIFY EXISTING PLUMBING SYSTEMS, WHICH ARE TO REMAIN ACTIVE, TO FACILITATE RECONNEC11ON AND EXTENSION OF THE NEW WORK. 4. NOTIFY OWNER AT LEAST 24 HOURS PRIOR TO INTERRUPTING EXISTING SERVICE. SCHEDULE DISCONNECTION AND TIE -INS TO MINIMIZE DISRUPTION OF SERVICES. SERVICES ARE NOT TO BE LEFT DISRUPTED DURING NON- NORMAL CONTRACTOR WORKING HOURS. 5. PIPE ROUTING SHOWN IS SCHEMATIC AND IS NOT INTENDED TO INDICATE EXACT ROUTING AND ANY ADDITIONAL OFFSETS AND FITTINGS REQUIRED FOR PROPER INSTALLATION AND TO MAINTAIN CLEARANCES. VERIFY STRUCTURAL, MECHANICAL AND ELECTRICAL INSTALLATIONS AND OTHER POTENTIAL OBSTRUCTIONS AND ROUTE PIPING TO AVOID INTERFERENCES. 6. PROVIDE ALL OFFSETS AND FITTINGS AND MAKE CONNECTION TO SITE UTILITIES. 7. CONCEAL PIPING ABOVE CEILINGS, WITHIN WALLS OR CHASES EXCEPT IN MECHANICAL ROOMS OR AS SPECIFICALLY NOTED. PROVIDE ACCESS PANELS FOR ALL VALVES CONCEALED IN WALLS OR ABOVE NON- ACCESSABLE CEILINGS. 8. SLEEVE AND FIRE STOP PENETRATIONS OF RATED WALLS, FLOORS, CEILINGS AND ROOFS. FLASH AND COUNTERFLASH ROOF PENETRATIONS. 9. WHEN BEAM SLEEVE PENETRATIONS ARE NECESSARY, COORDINATE PENETRATIONS WITH ALL TRADES, THE ARCHITECT AND THE STRUCTURAL ENGINEER. 10. PROVIDE FOUNDATION PAD PENETRATION SLEEVES. ALLOW 1" MINIMUM CLEARANCE BETWEEN SLEEVE INSIDE SURFACE AND PIPE EXTERIOR. 11. SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS. 12. PROVIDE AUTOMATIC TRAP PRIMERS FOR FLOOR DRAIN TRAP SEALS. 13. PROVIDE, WHEN REQUIRED BY CODE, AN AIR GAP SERVING INDIVIDUAL FIXTURES, DEVICES, APPLIANCES AND APPARATUS. 14. ALL EXPOSED PIPE AND FITTINGS IN FINISHED AREAS SHALL BE CHROME PLATED. 15. MOUNT HOSE BIBBS 24" ABOVE FINISH GRADE. 16. PROVIDE CLEANOUTS IN ACCORDANCE WITH APPROPRIATE CODES AND REGULATIONS. 17. COORDINATE EXACT FLOOR DRAIN LOCATIONS WITH ARCHITECTURAL DRAWINGS. SET FLOOR DRAINS BELOW FINISH FLOOR TO ALLOW FOR FLOOR SLOPING TO THE DRAIN. 18, PROVIDE ALL OFFSETS AND FITTINGS AND MAKE CONNECTION TO SITE UTILITIES. 19. COORDINATE PIPING WITH ALL ELECTRICAL EQUIPMENT (PANELS, TRANSFORMERS, ETC.) PRIOR TO ANY INSTALLATION. DO NOT ROUTE ANY PIPING OVER ANY ELECTRICAL PANELS UNDER ANY CIRCUMSTANCES. ANY PIPING RUN OVER PANELS SHALL BE REROUTED AT NO ADDITIONAL COST. PLUMBING SPECIFIC NOTES: 1. PROVIDE ANTI -SCALD VALVE TO SHOWER, BATHTUB, PER FBC 2010 PLUMBING 424.3. 2. BATHROOM WALL AND FLOOR SHALL HAVE A SMOOTH, HARD, NON - ADSORBENT SURFACE PER SECTION 1210.1 OF F.B.C. 2010 3. ALL STEEL STUDS SUPPORTING ALL WALL HUNG PLUMBING FIXTURES SHALL BE DOUBLE OR NO LESS THAN 20 GAUGE PER SECTION 2517.5..1.1 OF F.B.C. 2010 4. PROVIDE WATER HAMMER ARRESTORS IN ALL QUICK CLOSING VALVES. 5. PROVIDE FIXTURE COMPLIANCE WITH REFERENCE STANDARDS PER FBC PLUMBING SECTION 406 TO 421 6. ALL PLUMBING FIXTURES SHALL COMPLY WITH MIAMI DADE COUNTY ORDINANCE 108 -14 FOR PLUMBING FIXTURES MAXIMUM FLOW RATE AND CONSUMPTION. 7. DOMESTIC WATER SHALL USE COPPER PIPE TYPE L SANITARY AND WASTE SHALL USE DWV PVC. PLUMBING DRAWING INDEX SHEET DESCRIPTION ISSUED P -0.0 PLUMBING LEGEND, GENERAL NOTES & DETAILS YES P -1.0 PLUMBING FLOOR PLANS SANITARY & WATER SUPPLY YES P -2.0 PLUMBING ISOMETRICS YES PLUMBING SYMBOL LEGEND CD - ABOVE GROUND CONDENSATE DRAIN - - CD - - - BELOW GROUND CONDENSATE DRAIN _ - DOMESTIC COLD WATER - DOMESTIC COLD WATER - DOMESTIC HOT WATER - DOWN - DOMESTIC HOT WATER RECIRCULATING S - ABOVE GROUND SANITARY ___S___ - BELOW GROUND SANITARY -V_ _ _ _ - SANITARY VENT ST - ABOVEGROUND STORM - - ST- - - BELOW GROUND STORM STO - OVERFLOW STORM DRAIN - - STO- - - BELOW GROUND OVERFLOW STORM E - EXISTING LINE TO BE CAPPED -I! G - HOSE BIBB OR WALL HYDRANT CO H - CLEAN OUT PLUG CO - FLOOR CLEAN OUT FD MC FD ®C - FLOOR DRAIN (0) - ROOF DRAIN FS - FLOOR SINK ,.. - CONNECT TO EXISTING �- - DEMOLISH TO POINT INDICATED - WASH MACHINE BOX - GATE VALVE - ELECTRIC WATER HEATER TANK TYPE - BALL VALVE a - CHECK VALVE(SWING) 1/2 " - REDUCED PRESSURE BACKFLOW PREVENTOR DW - RELIEF OR SAFETY VALVE 101W DIRECTION OF FLOW ___ ELBOW, TURNED DOWN AS SELECTED BY OWNER. UNDER COUNTER - ELBOW, TURNED UP 9- - PRESSURE REDUCING VALVE r - SHUT -OFF VALVE TO VERTICAL ___S___ - EXISTING UNDERGROUND SANITARY LINE S - ABOVE GROUND SANITARY - - EXISTING COLD WATER LINE - - - EXISTING HOT WATER LINE - - - -V-' - - - - - EXISTING VENT LINE -SHEET NOTE CALLOUT �j -SHEET NOTE CALLOUT �1 -SHEET NOTE CALLOUT ------ DE - - - -- - EXISTING LINE TO BE DEMOLISHED CD - CONDENSATE DRAIN CO - CLEANOUT CONT - CONTINUATION CW - DOMESTIC COLD WATER DN - DOWN EXIST - EXISTING HW - DOMESTIC HOT WATER IE - INVERT ELEVATION RPBP - REDUCED PRESSURE BACKFLOW PREVENTOR SAN - SANITARY SF - SQUARE FEET ST - STORM STO - OVERFLOW STORM DRAIN VTR - VENT THRU ROOF IM - ICE MAKER SH - SHOWER BT - BATHTUB LAV - LAVATORY WC - WATER CLOSET KS - KITCHEN SINK IN-1 - INSTANTANEOUS WATER HEATER WMB - WASH MACHINE BOX EWH - ELECTRIC WATER HEATER TANK TYPE AAV - AIR ADMITTANCE VALVE NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT. SLOPE OF HORIZONTAL DRAINAGE PIPE: PIPE SIZES OF X OR LESS SHALL BE RUN AT A SLOPE OF 1/4" PER FOOT PIPE SIZES OF 3" TO 6" SHALL BE RUN AT A SLOPE OF 1/8" PER FOOT PIPE SIZES OF 8 OR LARGER SHALL BE RUN AT A SLOPE OF 1/16" PER FOOT PLUMBING FIXTURE CONNECTION SCHEDULE NO. DESCRIPTION WASTE VENT WATER REMARKS COLD HOT WC WATER CLOSET 3" 2" 1/2" -- FLUSH VALVE TYPE TANK, 1.28 GPF, FLOOR MOUNTED. LAV LAVATORY 1 1/4" 1 1/2" 1/2" 1/2- / AS SELECTED BY OWNER. PROVIDE 0.5 GPM FAUCET SH SHOWER [1] 2" 2" 1/2" 1/2" PROVIDE 1.5 GPM SHOWER HEAD BT BATHTUB [1] 2" 2" 1/2" 1/2" AS SELECTED BY OWNER. PROVIDE 1.5 GPM SHOWER HEAD KSK KITCHEN SINK 2" 2" 1/2" 1/2 " AS SELECTED BY OWNER. PROVIDE 1.0 GPM FAUCET WM CLOTHES WASHER 2" 2" 1/2" 1/2 " AS SEI D BY OWNER. PROVIDE RECESSED BOX, GUY GREY T200 ORE UAL DW DISH WASHER 101W ___ ___ 1/2" AS SELECTED BY OWNER. UNDER COUNTER [1] PROVIDE ANTI -SCALD VALVE. NOTES: 1.- All exposed trim, such as P- traps, angle stops, and supplies shall be chrome plated. 2.- All fixtures shall comply with Reference Standards as per FBC 2010 Plumbing 406 through 421. 3.- All Plumbing Fixtures to be specified by Architect. Please see Architectural Drawing for further information. ELECTRIC WATER HEATER SCHEDULE MARK EWH -1 - - KW 4.5 - - KW PER ELEMENT 4.5 - - NUMBER OF ELEMENTS 1 - - ELEMENT OPERATION SIM - - RECOVERY (GPH) @70'F 87 - STORAGE(GALLONS) 80 - - STORAGE TEMP('F) 120 - - SIZE(D "xH ") (25 "x61 ") - - VOLTS /PHASE /HERTZ 240/1/60 - - OPERATING WEIGHT(LBS) 700 - - MANUFACTURER LOCHINVAR - - MODEL NUMBER LTA082KDEF - - FIRST HOUR RATING (GPH) 87 - - E.F (ENERGY FACTOR) 0.93 - - EXTERIOR CLEAN OU T DETAIL No Scale 18 "x18 "x4" THICK SCORIATED CLEANOUT COVER CONCRETE COLLAR IN AREAS W /NO SLAB (ZURN - Z -1406) LEANOUT PLUG 1:._......... ....,_.: j .:.....,.,_ .._._ COMBINATION WYE & wTH BEND ``0111lttttttjltf 4 � � ST E OF Evelio Rodriguez, P.E. Lic. No. 74127 11123 SW 128 PL Miami, FL 33186 Tel. 786.223.4927 N a> rn -v 0 X 0 .(D w Q. 0 r� cV d- 0 N rri 0 v rn 3 v Q Z w 0 w J 0 Z M D J IL a ci z M J IL a� as a. w D 4 i 0 'v cn v M 0 E v -zs a� 0 CL 0 L_ CL ..t 0 N 1 N U Q .o L IL 0 N U z ca Z it w w Z a Z w X c� U w Uj Q ca a U_1 i ui E C rn C v 0 �0503 = m BY z J co co � U C Q ° r- Q C\2 Q (D w o W l W � in [~� W Cyr) W M Q d- ►� W 00 Li O �Q� N0�j CZ O CD o N V- oo:�;CL z J w (D � U C Elf ° r- Q C/D Q (D o W CD > in M 0- 1-- <C (D O C/D Q (D W -J t" 0 < W � M C/-) O Li O CZ O CD N DRAWN M.C.S.R. CHECKED M.E.S. PROYEC MANAGER Q.R. DATE FEBRUARY 2014 SCALE SHOWN JOB No. 2014 SHEET P-0.0 1 OF SHEETS 3