14-235-001FIRE ALARM NOTES 1. THE FIRE ALARM SYSTEM IS DESIGNED FOR NEW BUILDING AT 8575 NW 186TH ST MIAMI FL 33105 . IT IS A SCHEMATIC DESIGN AND THE CONTRACTOR SHALL PROVIDE A COMPLETE DESIGN AS REQUIRED AND SUBMIT SHOP DRAWINGS TO APPROVE FOR INSTALLATION. 2. ALL EQUIPMENT SHALL BE NEW AND U.L. LISTED. 3. THE DESIGN INSTALLATION OF THE FIRE ALARM SYSTEM SHALL ALSO COMPLY WITH THE NFPA -10 NATIONAL ELECTRIC CODE (NEC) AND THE FLORIDA BUILDING CODE (FBC) 11 -4283 V2001 EDITION. THE INSTALLATION SHALL ALSO COMPLY WITH NFPA -101 AND NFPA -72. 4. ALL WIRING TO CONFORM TO NFPA -70 ARTICLE 760. 5. ALL FIRE PENETRATIONS SHALL BE SEALED WITH U.L. APPROVED FIRE STOP MATERIALS. (SEE FIRE PENETRATION DETAIL). 6. MANUAL STATIONS TO BE INSTALLED AT 48' AFF /NOTIFICATION DEVICES AT 80' AFF FROM FLOOR TO BOTTOM OF APPLIANCES. 7. FIRE IAAARM SYSTEM SHALL BE SILENT KNIGHT (PANEL INTELLKNIGHT 5700) (OR EQUIVALENT). 8. FIRE ALARM CIRCUIT TO BE CLASS "B" FOR INITIATION AND CLASS "B" STYLE 4 FOR NOTIFICATION REPORTS. 9. ALL FIRE ALRM EQUIPMENT FOR THIS PROJECT SHALL RATED "POWER LIMITED ". 10. FIRE ALAM PANEL (SEE CONTRACTOR SHOP DRAWINGS). 11. SECURITY SYSTEM BY OTHER SHALL BE TIED INTO F/A AND SHALL OPEN UPON ALARM OR LOSS OF PRIMARY POWER. (IF APPLICABLE). 12. FIRE ALARM IS PROVIDED WITH 24 HOURS STANDBY AND 5 MINUTES IN ALARM BATTERY. 13. FACP TO BE ON DEDICATED CIRCUIT 120 V, AND MARKED RED FIRE ALARM. 14. ALL CONTROL RELAY TO BE WITHIN 3 FEET OF DEVICE BEING CONTROLLED. 15. MINIMUM CONDUIT SIZES 1/2" WITH 40 % %% FILL AS PER NEC 70. 16. ALL NOTIFICATION APPLIANCES TO ACTIVATE UPON ALARM. 17. SYSTEM TO BE REMOTE ALARM TYPE. 18. SYSTEM IS DESIGNED TO COMPLY WITH NFPA 101 CHAPTER 31 EXISTING APARTMENT BUILDING OCCUPANCY. 19. FACP. IS LOCATED AT MAIN ENTRANCE, THIS BUILDING HAS NOT REMOTE ANNUNCIATOR. 20. THE SYSTEM SHALL HAVE BATTERY BACK -UP FOR 24 HOURS IN THE SUPERVISORY MODE AND 5 MINUTES MINIMUM IN ALARM. 21 F.A. SYSTEM TO BE PROVIDED WITH EMERGENCY FORCES NOTIFICATION NFPA 101 - 16.3.4.4 AND 9.6.4 1. ACTIVATION OF ANY MANUAL INITIATION DEVICE WITHIN THE SYSTEM SHALL CAUSE THE FOLLOWING ACTIONS AND INDICATIONS: A) ACTIVATE THE NOTIFICATION CIRCUITS WITH THE EVACUATION TONE AND THE VISUAL SIGNALS (BUILDING AUDIBLE AND VISUAL NOTIFICATION). B) ACTIVATE THE ALARM LIGHT AT ANNUNCIATOR, IF ANY, AND NOTIFY ALARM TO REMOTE U.L. STATION (CONTINUOSLY ATTENDED CENTRAL STATION) C) DISPLAY A CUSTOM MESSAGE DESCRIBING THE LOCATION, TIME, AND DATE OF THE DEVICE INITIATING THE EVENT (IDENTIFICATION), D) SHUT DOWN ALL AIR CONDITIONING UNITS WITHIN THE PROTECTED SPACE, IF ANY. 2. ACTIVATION OF ANY AUTOMATIC FIRE DETECTION DEVICE WITHIN THE SYSTEM SHALL CAUSE THE FOLLOWING ACTIONS AND INDICATIONS: A) ACTIVATE THE NOTIFICATION CIRCUITS WITH THE EVACUATION TONE AND THE VISUAL SIGNALS (BUILDING AUDIBLE AND VISUAL NOTIFICATION). B) ACTIVATE THE ALARM LIGHT AT ANNUNCIATOR, IF ANY, AND NOTIFY ALARM TO REMOTE U.L. STATION (CONTINUOSLY ATTENDED CENTRAL STATION) C) DISPLAY A CUSTOM MESSAGE DESCRIBING THE LOCATION, TIME, AND DATE OF THE DEVICE INITIATING THE EVENT (IDENTIFICATION). 3. ACTIVATION OF SECOND DETECTOR WITHIN THE SYSTEM SHALL CAUSE THE FOLLOWING ACTIONS AND INDICATIONS: A) DISPLAY A CUSTOM MESSAGE DESCRIBING THE DEVICE IN ALARM, TIME, AND DATE AT THE FACP AND THE ALARM ANNUNCIATOR, IF ANY (IDENTIFICATION). B) ACTIVATE THE CORRESPONDING ALARM LIGHT AND SOUNDER IN A DISTINCTIVE MODE AT THE FIRE ALARM CONTROL PANEL AND ANNUNCIATORS, IF ANY. C) SOUND HORN /STROBE IN A DISTINCTIVE MODE WITHIN THE PROTECTED SPACE. D) NOTIFY SECOND ALARM TO REMOTE U.L. STATION (CONTINUOSLY ATTENDED CENTRAL STATION). 4. ACTIVATION OF ANY SUPERVISORY DEVICE WITHIN THE SYSTEM SHALL CAUSE THE FOLLOWING ACTIONS AND INDICATIONS: A) ACTIVATE THE SUPERVISORY LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL PANEL AND ANNUNCIATORS, IF ANY. B) DISPLAY A CUSTOM MESSAGE DESCRIBING THE LOCATION, TIME, AND DATE OF THE DEVICE INITIATING THE EVENT (IDENTIFICATION). C) NOTIFY TO U.L. CENTRAL STATION OF THE SUPERVISORY CONDITION. PANEL AND ANNUNCIATORS, IF ANY. 5. ACTIVATION OF ANY TROUBLE SIGNAL WITHIN THE SYSTEM SHALL CAUSE THE DEVICE INITIATING THE EVENT (IDENTIFICATION). FOLLOWING ACTIONS AND INDICATIONS: A) ACTIVATE THE TROUBLE LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL B) DISPLAY A CUSTOM MESSAGE DESCRIBING THE LOCATION, TIME, AND DATE OF THE C) NOTIFY TO U.L. CENTRAL STATION OF TROUBLE CONDITION. NOTE: TO COMPLY WITH THE MINIMUM REQUIREMENTS IT IS A SCHEMATIC DESIGN AND THE CONTRACTOR SHALL PROVIDE A COMPLETE DESIGN AS REQUIRED AND SUBMIT INSTALLATION DRAWINGS TO APPROVE. VOLTAGE DROP CALCULATION AND BATTERY CALS TO BE CALCULATED W /FINAL DRAWINGS FOR INSTALLATION. NO 11111 ;;i xjmw 1 SYMBOL LEGEND SYM. DESCRIPTION FACP FIRE ALARM CONTROL PANEL @J FIRE ALARM JUCTION BOX ® REMOTE ANNUNCIATOR PANEL nD SMOKE DETECTOR H HEAT DETECTOR RF MANUAL PULL STATION EN HORN STROBE, SELECTABLE CANDELA CONNECTED TO THE HORN ;o STROBE, SELECTABLE CANDELA ® TAMPER SWITCH ® FLOW SWITCH BATTERY CALCULATION' rAc: r NOTE: S -1 S -2 S -3 S -4 S -5 S -6 S -7 INITIATION CIRCUITS TO BE CLASS 'B' STYLE '4' NOTIFICATION CIRCUITS TO BE CLASS 'B' STYLE 'Y' SD -1 SD -2 SD -3 SD -4 SD -5 SD -6 SD -7 SD -8 SD -9 SD -10 SD -11 SD -12 SD -13 SD -14 SD -15 SD -16 PS -1 PS -2 rr TWO DEDICATED PHONE i \ 1 . -i • 7 LINES INTERNAL DIALER DESCRIPTION -- # •- .. C -12) 1 #12THHN GREEN CONNECTED TO THE GROUNDING SYSTEM rf_- FIRE ALARM RISER DIAGRAM FA -1 . • ii� -.- .� i I t _.. i -.3 / i. ..... NOTE: S -1 S -2 S -3 S -4 S -5 S -6 S -7 INITIATION CIRCUITS TO BE CLASS 'B' STYLE '4' NOTIFICATION CIRCUITS TO BE CLASS 'B' STYLE 'Y' SD -1 SD -2 SD -3 SD -4 SD -5 SD -6 SD -7 SD -8 SD -9 SD -10 SD -11 SD -12 SD -13 SD -14 SD -15 SD -16 PS -1 PS -2 System No, C -AJ -1149 F Rating - 2 Hr T Rating - 0 Hr a L Rating At Ambient - Less Than 1 CFM /sq f t L Rating At 400 F - 4 CFM /sq ft SECTION A -A 1. Floor or Wall Assembly - Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks •. Max diam of opening is 12 in. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Through Penetrants - One metallic pipe, conduit or tubing to be installed within the firestop system. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The annular space shall be 0 in. (point contact) to max 1 -1/4 in. The following types and sizes of metallic pipes, conduits or tubing may be used: A Steel Pipe - Nom 10 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit. C. Copper Tubing - Nom 4 in. diam (or smaller) Type L (or heavier) copper tubing. D. Copper Pipe - Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe. 3. PoWng Mlaterid - Min 3 in. thickness of min 4 pcf mineral wool, butt insulation for nom 4 in. diam (and smaller) pipes, conduits or tubings and a min 4 in. thickness of min 4 pcf mineral wool butt insulation for pipe greater than nom 4 in. diam, firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. 4. Fill, Void or Cavity MaoWml* - Seakmt - Min 1/2 in. thickness of fill material applied within the annulus, flush with the top surface of floor or both surfaces of wall. At the point of contact location between pipe and concrete, a min 1/2 in. diam bead of fill material shall be applied at the concrete /pipe interface on the top surface of floor and on both surfaces of wall. HUI CONSTRUCTION CfIRAGAIS, DIY OF HIM INC - CP601S, CP606 or FS -ONE Sealant (Note: L Ratings apply only when FS -ONE Sealant is used). *Bearina the UL Classification Marking G�SStFj�Q Reproduced by HILTI, Inc. Courtesy of MRESTOP SYS US Underwhers December 20, 2000 Inc C US - CEILING 3' -2" MIN. SMOKE DETECTOR A/C DIFFUSER SMOKE DETECTOR MOUNTING DETAIL 1 No Scale STROBE OR HORN /STROB 80" A.F.F. C 6" BELOW CEILING (WHICHEVER IS LOWER) 48" A.F.F. ADA HEIGHT REQUIREMENTS No -Scale W10111-1i P f • r* rI • � r • BOARD s ■ i t� i • 1 • rt � i � f i - i • i i ■ ■■ ■ f ■ DRAWN M.C.S.R. CHECKED M.E.S. PROYEC MANAGER O.R. DATE fEBRUARY 2014 SCALE SHOWN JOB No. 2014 SHEET FA -1 1 OF 1 SHEETS F.A.C.P. TWO DEDICATED PHONE LINES INTERNAL DIALER TO 20 CBK ON FOR CENTRAL STATION ELECTRICAL NOTIFICATION PANEL C(Ckt C -12) 1 #12THHN GREEN CONNECTED TO THE GROUNDING SYSTEM rf_- FIRE ALARM RISER DIAGRAM FA -1 System No, C -AJ -1149 F Rating - 2 Hr T Rating - 0 Hr a L Rating At Ambient - Less Than 1 CFM /sq f t L Rating At 400 F - 4 CFM /sq ft SECTION A -A 1. Floor or Wall Assembly - Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks •. Max diam of opening is 12 in. See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. 2. Through Penetrants - One metallic pipe, conduit or tubing to be installed within the firestop system. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The annular space shall be 0 in. (point contact) to max 1 -1/4 in. The following types and sizes of metallic pipes, conduits or tubing may be used: A Steel Pipe - Nom 10 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit. C. Copper Tubing - Nom 4 in. diam (or smaller) Type L (or heavier) copper tubing. D. Copper Pipe - Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe. 3. PoWng Mlaterid - Min 3 in. thickness of min 4 pcf mineral wool, butt insulation for nom 4 in. diam (and smaller) pipes, conduits or tubings and a min 4 in. thickness of min 4 pcf mineral wool butt insulation for pipe greater than nom 4 in. diam, firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. 4. Fill, Void or Cavity MaoWml* - Seakmt - Min 1/2 in. thickness of fill material applied within the annulus, flush with the top surface of floor or both surfaces of wall. At the point of contact location between pipe and concrete, a min 1/2 in. diam bead of fill material shall be applied at the concrete /pipe interface on the top surface of floor and on both surfaces of wall. HUI CONSTRUCTION CfIRAGAIS, DIY OF HIM INC - CP601S, CP606 or FS -ONE Sealant (Note: L Ratings apply only when FS -ONE Sealant is used). *Bearina the UL Classification Marking G�SStFj�Q Reproduced by HILTI, Inc. Courtesy of MRESTOP SYS US Underwhers December 20, 2000 Inc C US - CEILING 3' -2" MIN. SMOKE DETECTOR A/C DIFFUSER SMOKE DETECTOR MOUNTING DETAIL 1 No Scale STROBE OR HORN /STROB 80" A.F.F. C 6" BELOW CEILING (WHICHEVER IS LOWER) 48" A.F.F. ADA HEIGHT REQUIREMENTS No -Scale W10111-1i P f • r* rI • � r • BOARD s ■ i t� i • 1 • rt � i � f i - i • i i ■ ■■ ■ f ■ DRAWN M.C.S.R. CHECKED M.E.S. PROYEC MANAGER O.R. DATE fEBRUARY 2014 SCALE SHOWN JOB No. 2014 SHEET FA -1 1 OF 1 SHEETS