Loading...
15-310-011GRILLE, REGISTER & DIFFUSER SCHEDULE OUTSIDE PLAN MANUF. & MODEL NUMBER MODULE NECK FACE BORDER FINISH BLOW MAT'L OPTIONS/NOTES MARK �• SIZE SIZE SIZE TYPE PATTERN IS A TITUS - CT480 SEE PLAN SEE PLAN SEE PLAN 1 26 1 1 ALU SBD / 1,2,3,4 B TITUS - MCD -AA SEE PLAN SEE PLAN SEE PLAN 1 1 26 1 4 1 ALU I OBD / 1,2,3 BORDER TYPE: 1 SURFACE BLOW PATTERN 1 1 -WAY' FINISH 01 ALUMINUM OPTIONS SRA SQ. TO RD. ADAPT. EG EQUALIZING GRID MOUNT 1H 1 -WAY, HORIZ. 04 MILL (STANDARD) PFA ALUM PLASTER FRAME TRV THROW RED. VANES 2 SNAP -IN 1V 1 -WAY, VERTICAL 26 WHITE VD VOLUME DAMPER L FRONT BLADE LONG 3 LAY -IN 2 2 -WAY, OPPOSITE 2C 2 -WAY, CORNER 6. RD RADIAL DAMPER ORIENTATION 1) O/A 4 SPLINE 3 3 -WAY MATERIAL ROBD RADIAL OBD S FRONT BLADE SHORT 5 DROPPED 4 4 -WAY ST'L 22 GAUGE STEEL SBD SINGLE BLADE DAMPER ORIENTATION 6 BEVELED 5 RADIAL ALU ALUMINUM EQT EARTHQUAKE TABS C CONCEALED BORDER F DB WB Phone(754)300 -7770 EACH OBD OPPOSED BLD. DAMPER BO BLANK OFF NOTES 1. FOR BLOW PATTERN, REFER TO FLOW ARROWS INDICATED ON PLANS. ABSENCE OF FLOW ARROW INDICATES REMOVAL OF AIR PATTERN CONTROLLER UNLESS OTHERWISE SPECIFIED. (EA.) 2. PROVIDE ADAPTER FOR DUCT CONNECTION TO DEVICE IF NECK SIZE AND DUCT SIZE DO NOT MATCH. k4 3. CONFIRM BORDER TYPE AND FINISH WITH ARCHITECT /OWNER PRIOR TO PURCHASING. 4. SINGLE BLADE DAMPER (MODEL AG -30) TO BE SCREW DRIVER ADJUSTABLE FROM FACE OF DIFFUSER. 5. OPPOSED BLADE DAMPER (MODEL AG -95) TO BE ADKISTABLE FROM THE DIFFUSER FACE BY REMOVING CORE MODULE. HVAC DESIGN REQUIREMENTS YES NO OUTSIDE - PER :! i SELECTION BASED ON TYPE/ X TABLE i • i X FIRE RATED ENCLOSURE PEOPLE/ Vi; �• - X PROVIDED SONES IS MAKE HP ..; i i RETAIL SERVICE 10.5A e PKU I WEIGHT TOTAL 120 CFM GREENHECK SP —B50 BATHROOM 50 0.1 1 594 115 -1 -60 DIRECT 1.1 11 LB STORAGE GENERAL 1. FAN NOTES: PROVIDE MOTOR STARTERS, DISCONNECTS AND ALL ASSOCIATED CONTROLS ON ALL FANS. 2. PROVIDE BACKDRAFT DAMPER FOR ALL EXHAUST FANS. + + + + CFM 5. PROVIDE MOTOR HEATERS SIZED AS REQUIRED FOR FIELD CONDITIONS. 6. PROVIDE FACTORY FAN MOUNTING SUPPORT -LEGS, CURBS, HANGING CLIPS, ETC.. 7. 1) O/A EXCLUSION BASED ON i N OF OCCUPIABI E SPACE. PROVIDE ALUMINUM GRULLE WITH WHITE ENAMEL FINISH. TYPE AND HVAC DESIGN REQUIREMENTS YES NO FAN SCHEDULE - X SELECTION BASED ON TYPE/ X SMOKE DAMPER(S) MOTOR DATA X FIRE RATED ENCLOSURE UNIT X MARK - X CFM IN WG. DRIVE SONES - NOTES MAKE — MODEL NO. HP RPM LTS-PH-HZ W SERVICE 10.5A e PKU I WEIGHT TOTAL TEF -1 GREENHECK SP —B50 BATHROOM 50 0.1 1 594 115 -1 -60 DIRECT 1.1 11 LB 1 -8 GENERAL 1. FAN NOTES: PROVIDE MOTOR STARTERS, DISCONNECTS AND ALL ASSOCIATED CONTROLS ON ALL FANS. 2. PROVIDE BACKDRAFT DAMPER FOR ALL EXHAUST FANS. 3. COORDINATE WITH ELECTRICAL CONTRACTOR BEFORE BIDDING OR ORDERING ANY EQUIPMENT. 4. SEE GENERAL, AIR CONDITIONING, DUCTWORK, AND COORDINATION NOTES FOR OTHER FIELD SUPPLIED ITEMS. 5. PROVIDE MOTOR HEATERS SIZED AS REQUIRED FOR FIELD CONDITIONS. 6. PROVIDE FACTORY FAN MOUNTING SUPPORT -LEGS, CURBS, HANGING CLIPS, ETC.. 7. TEF -1 TO BE INTERLOCKED WITH PKU -1. 8. PROVIDE ALUMINUM GRULLE WITH WHITE ENAMEL FINISH. HVAC DESIGN REQUIREMENTS YES NO DUCT SMOKE DETECTOR - X FIRE DAMPER(S) - X SMOKE DAMPER(S) - X FIRE RATED ENCLOSURE - X FIRE RATED ROOF /FLOOR CEILING ASSEMBLY - X FIRE STOPPING - X SMOKE CONTROL - X DRAWING KEY NOTES 4 "0 TOILET EXHAUST FAN TO EXISTING WALL CAP. PROVIDE BACKDRAFT DAMPER. CONTRACTOR TO EXTEND EXISTING DUCTWORK AS NECESSARY IN ORDER TO CONNECT TO NEW TEF -1. SEPERATE 10' -0" MINIMUM FROM MECHANICAL INTAKE OPENING. PROGRAMMABLE THERMOSTAT AT 48" A.F.F. COORDINATE FINAL LOCATION WITH OWNER /ENGINEER FOR APPROVAL. r 3 J CONTRACTOR TO PROVIDE SOFFIT TO ACCOMODATE DUCTWORK. COORDINATE EXACT LOCATION OF SOFFIT WITH ARCHITECT. REPORT ANY DISCREPENCY TO ENGINEER. NEW AIR - COOLED PACKAGED UNIT TO BE INSTALLED ON NEW WALL SUPPORT BRACKET. REFER TO STRUCTURAL ENGINEER FOR DETAILS. CONTRACTOR TO FIELD VERIFY REQUIRED BRACKET SIZE IN ORDER TO PROVIDE ADEQUATE CLEARANCE ABOVE CONDENSER FAN. REFER TO MANUFACTURERS SPECIFICATIONS. REPORT ANY DISCREPENCY TO ENGINEER.' 18 "02" MIAMI -DADE APPROVED HURRICANE RESISTANT LOUVER TO BE INSTALLED ABOVE WINDOW. PROVIDE PLENUM AND CORROSION RESISTANT INSECT SCREEN. MANUFACTURER - GREENHECK MODEL ESD -635D OR APPROVED EQUAL. r-F-'\ RETURN PLENUM ABOVE CEILING. PLENUM ENCLOSURES SHALL BE CONSTRUCTED OF MATERIALS PERMITTED FOR THE TYPE OF CONSTRUCTION CLASSIFICATION PER FMC 602.2. ALL MATERIALS WITHIN PLENUM TO BE IN COMPLIENCE WITH FMC 602.2.1. r% CONTRACTOR TO TRANSITION AND EXTEND RETURN DUCT FAR ABOVE CEILING TO MECHANICALLY ATTACH INTAKE DUCT. FIELD VERIFY CLEARANCES AND CONSTRAINTS. REPORT ANY DISCREPENCY TO ENGINEER. �$ 4 "0 FLEXIBLE DUCT TAPPED OFF TOP OF MAIN TRUNK. CONTRACTOR TO RUN ABOVE CEILING BETWEEN TRUSS WEBBING. (TYPICAL) MOTORIZED DAMPER (NORMALLY OPEN) INTERLOCKED WITH PKU -1 OPERATION, TURN TO OPEN WHEN UNIT START, RETURN TO CLOSED POSITION WHEN UNIT STOP. d CONTRACTOR TO FIELD COORDINATE EXACT PLACEMENT OF UNIT IN ORDER TO PENETRATE EXISTING 40 "x19" EXTERIOR WALL PENETRATION WITH SUPPLY AND RETURN DUCTWORK. CONTRACTOR TO VERIFY ALL CLEARANCE AND CONSTRAINTS ON SITE IN ORDER TO ADEQUATELY CLEAR BEAM. CONTRACTOR TO TRANSITION ACCORDINGLY UNDER BAR JOISTS INTO SOFFIT ALONG WEST EXTERIOR WALL. REPORT ANY DISCREPENCY TO ENGINEER. 'CONTRACTOR TO FIELD INSTALL ELECTRIC DUCT HEATER FROM MANUFACTURER ON DISCHARGE OF UNIT. REFER TO MANUFACTURERS SPECIFICATIONS FOR DETAILS. 0 o G FITTING ROOM 8' -3" A.F.F. 012 "x2" L.B. 25 CFM 48 "x4" L.B. RETURN MECHANICAL CEILING PLAN 1 SCALE: 1/4 " =1' -0" D 1 a CA r' rz,, 0 cl ce ry :s :A 91. n - x-12 "x2" L.B. f '; 25 CFM ,f �r �i o 02 v, ✓; Fl Y 9 cz .`, IX 1 Y �:d nM r^. E� �M Y u E Fey s� fi s? H U'jy � I AIR COOLED PACKAGED UNIT EQUIPMENT SCHEDULE 0 MARK DESIGN MANUFACTURER CFM EVAPORATOR COMPRESSOR CONDENSER HEATER HEATER MAX UNIT MAX ELECTRICAL CAPACITY UNIT W R/A FILTER e PKU I MODEL NO. TOTAL OUTSIDE ESP HP FLA ENTERING AIR TEMP; LEAVING AIR TEMP., NO TONS RLA /LRA TYPE OF NO FLA TYPE KW NO. of STAGES & MCA FUSE MCA FUSE VOLTS -PH -H BH SM H SEE TYPE REFRIGERANT OPERATING WEIGHT UNIT DIMENSIONS TYPE AND QUANTITY AND SERVED LOCATION APPLICABLE NOTES AIR AIR WSTUDIO AA 26002514 - 11126001404 1141 SE 6th TERRACE F DB WB F DB WB Phone(754)300 -7770 EACH EACH FAN Ek (EA.) (EA.) k4 KW/STAGE -I� LML iii � • � TYPE (I�) LxWxH( -) THICKNESS DIMENSIONS C\ T-1 X PKU -1 BARD PA13362 -A 1,200 140 0.5" 1/2 3.3 80/67 - 1 - 12/741 PROP. 1 1/6 1.1 ELEC. 5 1/5 26 30 24 35 230 -1- a 34,000 2 ,50 13.0 HORIZONTAL R -41 OA 410 x38.125 MERV 8 _ SEE SEE 1 -6 PLAN PLAN NOTES: 1) RATED AND CERTIFIED IN ACCORDANCE WITH ANSI /AHRI STANDARD 210/240 -2003 5) PROVIDE LIQUID LINE FILTER DRIER. 2) PROVIDE PROGRAMMABLE THERMOSTAT 6) PROVIDE FIELD INSTALLED ELECTRIC HEATER AS SPECIFIED. ELECTRIC HEATER REQUIRES INDIVIDUAL POWER CIRCUIT. 3) PROVIDE ECM INDOOR BLOWER MOTOR 4) PROVIDE ALUMINUM FINNED COPPER COILS. 0 o G FITTING ROOM 8' -3" A.F.F. 012 "x2" L.B. 25 CFM 48 "x4" L.B. RETURN MECHANICAL CEILING PLAN 1 SCALE: 1/4 " =1' -0" D 1 a CA r' rz,, 0 cl ce ry :s :A 91. n - x-12 "x2" L.B. f '; 25 CFM ,f �r �i o 02 v, ✓; Fl Y 9 cz .`, IX 1 Y �:d nM r^. E� �M Y u E Fey s� fi s? H U'jy � I 0 W 4 4 cn zg5 o w G WSTUDIO AA 26002514 - 11126001404 1141 SE 6th TERRACE SUITE 1 FF. LAUDERDALE, FL 33316 Phone(754)300 -7770 bbuUock @sustainable- logic.net �TE�a F'+�y k4 E -I� LML iii � • � �yi/d�•� V1 E C\ T-1 X LO .� iyt .map°. o jTc, , r co W 2 om W u z 0 w w Z w � z a U raw �a or- F- a R D `t4 z O PROJECT N0. DRAWN BY 15 -Oo8 BIB MECHANICAL CEILING PLAN, SCHEDULES AND NOTFS X1.1