15-310-010GRILLE, REGISTER & DIFFUSER SCHEDULE
OUTSIDE AIR CALCULATIONS
PLAN
MARK
MANUF. & MODEL NUMBER
MODULE
SIZE
NECK
SIZE
FACE
SIZE
BORDER
TYPE
FINISH
BLOW
PATTERN
MAT'L
OPTIONS/NOTES
A
TITUS - CT480
SEE PLAN
SEE PLAN
SEE PLAN
1
01
1H
ALU
SBD / 1,2,3,4
B
11TUS - MCD -AA
SEE PLAN
SEE PLAN
SEE PLAN
1
01
4
ALU
OBD / 1,2,3
C
TITUS - MCD -AA
SEE PLAN
SEE PLAN
SEE PLAN
1
01
2C
ALU
OBD / 1,2,3
BORDER TYPE:
1 SURFACE
BLOW PATTERN
1 1- WAY,
FINISH
01 ALUMINUM
OPTIONS
SRA SQ. TO RD. ADAPT. EG
EQUALIZING GRID
T
MOUNT
1H 1 -WAY, HORIZ.
04 MILL (STANDARD)
PFA ALUM PLASTER FRAME TRV
THROW RED. VANES
2 SNAP
1V 1 -WAY VERTICAL
2 2 -WAY, OPPOSITE
26 WHITE
VD VOLUME DAMPER L
FRONT BLADE LONG
3 LAY -IN
2C 2 -WAY, CORNER
RD RADIAL DAMPER
ORIENTATION
5.
4 SPLINE
3 3 -WAY
MATERIAL
ROBD RADIAL OBD S
FRONT BLADE SHORT
5 DROPPED
4 4-WAY
ST'L 22 GAUGE STEEL
SBD SINGLE BLADE DAMPER
ORIENTATION
6 BEVELED
5 RADIAL
ALU ALUMINUM
EQT EARTHQUAKE TABS C
CONCEALED BORDER
EACH
EACH
OBD OPPOSED BLD. DAMPER BO
BLANK OFF
NOTE
1. FOR BLOW PATTERN, REFER TO FLOW ARROWS INDICATED ON PLANS. ABSENCE OF FLOW ARROW INDICATES REMOVAL OF
AIR PATTERN CONTROLLER UNLESS OTHERWISE SPECIFIED.
2. PROVIDE ADAPTER FOR DUCT CONNECTION TO DEVICE IF NECK SIZE AND DUCT SIZE DO NOT MATCH.
/, AGE
3. CONFIRM BORDER TYPE AND FINISH WITH ARCHITECT /OWNER PRIOR TO PURCHASING.
4. SINGLE BLADE DAMPER (MODEL AG -30) TO BE SCREW DRIVER ADJUSTABLE FROM FACE OF DIFFUSER.
5. OPPOSED BLADE DAMPER (MODEL AG -95) TO BE ADJUSTABLE FROM THE DIFFUSER FACE BY REMOVING CORE MODULE.
HVAC DESIGN
REQUIREMENTS
YES NO
OUTSIDE AIR CALCULATIONS
-
�� ABLE
TYPE/
-
X
403,3a�
APPLICATION
X
AREA
PEOPLE/
NO. OF
CFM/P
CFM/
CFM
CFM
CFM PROVIDED BY
SONES
SMOKE CONTROL
SO. FT.
1000 SQFT
PEOPLE
CAPACITY
SO. FT.
REQUIRED
PROVIDED
RETAIL
MODEL NO.
490
15
8
7.5
0.12
119
130 CFM
HP
WEIGHT
ENTERING AIR
TEMP;
TEF -1
GREENHECK
SP -950
BATHROOM
50
0.1
0.5A
PKU -1 (150 CFM)
STORAGE
DIRECT
163
-
-
0
0.12
20
20 CFM
3.
NOTES:
4.
SEE GENERAL, AIR CONDITIONING, DUCTWORK, AND COORDINATION NOTES FOR OTHER FIELD SUPPLIED ITEMS.
5.
1) O/A
EXCLUSION BASED ON DEFINITION OF OCCUPIABLE SPACE.
PROVIDE FACTORY FAN MOUNTING SUPPORT -LEGS, CURBS, HANGING CUPS, ETC..
7.
HVAC DESIGN
REQUIREMENTS
YES NO
FAN SCHEDULE
-
SELECTION BASED ON
TYPE/
-
X
MOTOR DATA
-
X
UNIT
-
MARK
FIRE RATED ROOF /FLOOR
CEILING ASSEMBLY
-
CFM
IN WG.
DRIVE
SONES
SMOKE CONTROL
NOTES
X
ELECTRICAL
CAPACITY
UNIT
MAKE
MODEL NO.
SERVICE
PKU
HP
RPM
VOLTS-PH-HZ
ESP
HP
WEIGHT
ENTERING AIR
TEMP;
TEF -1
GREENHECK
SP -950
BATHROOM
50
0.1
0.5A
594
115 -1 -60
DIRECT
1.1
11 LB
1 -8
gENERAL
1.
FAN NOTES:
PROVIDE MOTOR STARTERS, DISCONNECTS AND ALL ASSOCIATED CONTROLS ON ALL FANS.
2.
PROVIDE BACKDRAFT DAMPER FOR ALL EXHAUST FANS.
3.
COORDINATE WITH ELECTRICAL. CONTRACTOR BEFORE BIDDING OR ORDERING ANY EQUIPMENT.
4.
SEE GENERAL, AIR CONDITIONING, DUCTWORK, AND COORDINATION NOTES FOR OTHER FIELD SUPPLIED ITEMS.
5.
PROVIDE MOTOR HEATERS SIZED AS REQUIRED FOR FIELD CONDITIONS.
6.
PROVIDE FACTORY FAN MOUNTING SUPPORT -LEGS, CURBS, HANGING CUPS, ETC..
7.
TEF -1 TO BE INTERLOCKED WITH PKU -1.
8.
PROVIDE ALUMINUM GRULLE WITH WHITE ENAMEL FINISH.
HVAC DESIGN
REQUIREMENTS
YES NO
DUCT SMOKE DETECTOR
-
X
FIRE DAMPER(S)
-
X
SMOKE DAMPER(S)
-
X
FIRE RATED ENCLOSURE
-
X
FIRE RATED ROOF /FLOOR
CEILING ASSEMBLY
-
X
FIRE STOPPING
-
X
SMOKE CONTROL
-
X
DRAWING KEY NOTES
Q 4 "0 TOILET EXHAUST FAN TO EXISTING WALL CAP. PROVIDE BACKDRAFT DAMPER.
CONTRACTOR TO EXTEND EXISTING DUCTWORK AS NECESSARY IN ORDER TO CONNECT
TO NEW TEF -1. SEPERATE 10' -0" MINIMUM FROM MECHANICAL INTAKE OPENING.
PROGRAMMABLE THERMOSTAT AT 48" A.F.F. COORDINATE FINAL LOCATION WITH OWNER
/ENGINEER FOR APPROVAL.
CONTRACTOR TO PROVIDE SOFFIT TO ACCOMODATE DUCTWORK. COORDINATE EXACT
LOCATION OF SOFFIT WITH ARCHITECT. REPORT ANY DISCREPENCY TO ENGINEER.
�¢ NEW AIR - COOLED PACKAGED UNIT TO BE INSTALLED ON NEW WALL SUPPORT BRACKET.
REFER TO STRUCTURAL ENGINEER FOR DETAILS. CONTRACTOR TO FIELD VERIFY REQUIRED
BRACKET SIZE IN ORDER TO PROVIDE ADEQUATE CLEARANCE ABOVE CONDENSER FAN.
REFER TO MANUFACTURERS SPECIFICATIONS. REPORT ANY DISCREPENCY TO ENGINEER.
18 "x12" MIAMI -DADE APPROVED HURRICANE RESISTANT LOUVER TO BE INSTALLED ABOVE
WINDOW. PROVIDE PLENUM AND CORROSION RESISTANT INSECT SCREEN. MANUFACTURER -
GREENHECK MODEL ESD -635D OR APPROVED EQUAL.
RETURN PLENUM ABOVE CEILING. PLENUM ENCLOSURES SHALL BE CONSTRUCTED OF
MATERIALS PERMITTED FOR THE TYPE OF CONSTRUCTION CLASSIFICATION PER FMC 602.2.
ALL MATERIALS WITHIN PLENUM TO BE IN COMPLIENCE WITH FMC 602.2.1.
CONTRACTOR TO TRANSITION AND EXTEND RETURN DUCT FAR ABOVE CEILING TO
MECHANICALLY ATTACH INTAKE DUCT. FIELD VERIFY CLEARANCES AND CONSTRAINTS.
REPORT ANY DISCREPENCY TO ENGINEER.
4"O FLEXIBLE DUCT TAPPED OFF TOP OF MAIN TRUNK. CONTRACTOR TO RUN ABOVE
CEILING BETWEEN TRUSS WEBBING. (TYPICAL)
MOTORIZED DAMPER (NORMALLY OPEN) INTERLOCKED WITH PKU -1 COMPRESSOR, TURN
TO OPEN WHEN COOLING ENGAGED, RETURN TO CLOSED POSITION WHEN COMPRESSOR
STOP.
j p CONTRACTOR TO FIELD COORDINATE EXACT PLACEMENT OF UNIT IN ORDER TO
PENETRATE EXISTING 40 "x19" EXTERIOR WALL PENETRATION WITH SUPPLY AND RETURN
DUCTWORK. CONTRACTOR TO VERIFY ALL CLEARANCE AND CONSTRAINTS ON SITE IN
ORDER TO ADEQUATELY CLEAR BEAM. CONTRACTOR TO TRANSITION ACCORDINGLY UNDER
BAR JOIST'S INTO SOFFIT ALONG WEST EXTERIOR WALL. REPORT ANY DISCREPENCY TO
ENGINEER.
j j CONTRACTOR TO FIELD INSTALL ELECTRIC DUCT HEATER FROM MANUFACTURER ON
DISCHARGE OF UNIT. REFER TO MANUFACTURERS SPECIFICATIONS FOR DETAILS.
_12') CONTRACTOR TO PROVIDE 90' ELBOW OFF RETURN DIFFUSER.
ENTIRE SHEET REVISED: OWNER
REQUESTED REVISIONS 03.11.15
0
0
MECHANICAL CEILING PLAN
SCALE:114 "=1' -0"
c n
)OM
F.F.
a
14
o�
oa
a
w�
�Q
4'4
w
R
f-'4�
o�
R
ati
o
2
w�
o^
Q
2
0
w
2
c:
w�
�l
c2
Q
w�
o�
a�
V.
o
a
a
z
x
z
° G
p=
c�
6
ads
E�
�El
a
ow
�o
71
Tr5
N
Ca
r
1
AIR COOLED
PACKAGED UNIT EQUIPMENT SCHEDULE
MARK
DESIGN MANUFACTURER
CFM
EVAPORATOR
COMPRESSOR
CONDENSER
HEATER
HEATER
MAX
UNIT MAX
ELECTRICAL
CAPACITY
UNIT
R/A FILTER
PKU
MODEL NO.
TAR
OUTSIDE
ESP
HP
FLA
ENTERING AIR
TEMP;
LEAVING
R TEMP-,
N0.
R
NO.
(fA
�
KW
NO. OF
STAGES
MCA
FUSE
MCA
FUSE
VOLTS -PH -HZ
TMBH
SMBH
SEER
TYPE
REFRIGERANT
OPERATING
UNIT
DIMENSIONS
AND
QUANTITY
AREA
SERVED
LOCATION
APPLICABLE
NOTES
F 8
F
EACH
EACH
FAN
(EA)
/, AGE
�
DIMENSIONS
PKU -1
BARD PA13362 -A
1,240
140
0.5"
1/2
3.3
80/67
-
1
-
12/74
PROP.
1
1/6
1.1
ELEC.
5
1/5
26
30
24
35
230 -1 -60
34,000
25,500
13.0
HORIZONTAL
R -41 OA
410
x38.125
MERV� 6
PLAN
-
1 -6
PLAN
NOTES:
1)
RATED AND CERTIFIED IN ACCORDANCE WITH ANSI /AHRI STANDARD 210/240 -2003
5) PROVIDE LIQUID LINE FILTER DRIER.
2)
PROVIDE PROGRAMMABLE THERMOSTAT
6) PROVIDE FIELD INSTALLED ELECTRIC
HEATER AS SPECIFIED.
ELECTRIC HEATER REQUIRES INDIVIDUAL POWER CIRCUIT.
3)
PROVIDE ECM INDOOR BLOWER MOTOR
4)
PROVIDE ALUMINUM FINNED COPPER COILS.
0
0
MECHANICAL CEILING PLAN
SCALE:114 "=1' -0"
c n
)OM
F.F.
a
14
o�
oa
a
w�
�Q
4'4
w
R
f-'4�
o�
R
ati
o
2
w�
o^
Q
2
0
w
2
c:
w�
�l
c2
Q
w�
o�
a�
V.
o
a
a
z
x
z
° G
p=
c�
6
ads
E�
�El
a
ow
�o
71
Tr5
N
Ca
r
1